Altronix RBSNTTL Ultra Sensitive Relay Module Instruction Manual
- June 4, 2024
- Altronix
Table of Contents
RBSNTTL
Ultra Sensitive Relay Module
Specifications:
- 12VDC to 24VDC operation.
- 3VDC to 24VDC 2mA – 16mA isolated trigger.
- DPDT contacts rated at 2A/120VAC/28VDC
- Snap track mountable (order part # ST1).
Board Dimensions (W x L x H):
1.9” x 2.75” x 1.1”
(48.26mm x 69.85mm x 27.94mm)
Installation Instructions:
- Connect 12VDC or 24VDC power supply (regulated) to the terminals marked [POS +] and [NEG –]. Carefully observe polarity.
- Connect trigger voltage to the terminals marked [TRG +] and [TRG –].
- Use output contacts to make and break load circuits.
Note: When using a common power source, the unused trigger terminal must be jumpered to its respective POS (+) or NEG (–) power supply terminal.
Altronix is not responsible for any typographical errors. Product
specifications are subject to change without notice.
140 58th Street, Brooklyn, New York 11220 USA | phone:
718-567-8181 | fax:
718-567-9056
website: www.altronix.com | e-mail:
info@altronix.com | Lifetime Warranty
IIRBSNTTL – Rev. 020106 F21U