Nortek 1034920A Downflow Gas Furnaces Instruction Manual

June 12, 2024
NORTEK

INSTALLATION INSTRUCTIONS

INDUCER ORIFICE SELECTION

Refer to the tables below to select the appropriate orifice size for this replacement kit. The orifice size can also be found on the back side of each orifice.

G7, PGC2 UPFLOW / HORIZONTAL UNITS
CABINET SIZE INPUT (MBTUH) **ORIFICE SIZE (INCHES)***
A 38 0.88 [Single Stage] / 0.62 [Single Stage]
B 46 0.94
B 54 0.94 [Single Stage] / 0.75 [Single Stage]
B 57 0.75 [Two Stage]
B 60 0.88 [Two Stage] / 1.00 [Modulating]
B 61 1.00
B 72 1.00
C 72 1.16 [Single Stage] / 0.88 [Single Stage]
C 76 0.875 (Two Stage)
C 80 1.00
C 90 1.38 [Single Stage] / 1.13 [Single Stage]
C 100 1.25
D 108 N/A [Single Stage] / 1.16 [Single Stage]
D 120 N/A [Two Stage / Modulating] / 1.38 [Single Stage]
*G7 DOWNFLOW UNITS
A 38 0.56
B 54 0.94 [Single Stage] / 0.75 [Single Stage]
B 60 0.75
B 72 1.00
C 72 0.88
C 80 0.97
C 90 1.13
C 100 1.31
D 118 1.38
D 120 N/A [Single Stage] / 1.50 [Two Stage]

*NOTE: Model series in brackets where applicable

M7RL & M7TL DOWNFLOW GAS FURNACES
CABINET SIZE INPUT (MBTUH) **ORIFICE SIZE (INCHES)***
A 45  0.62
60 0.687
72 0.94
B 45 0.62
60 0.687
72 0.94
MG2S DOWNFLOW GAS FURNACE
ORIENTATION INPUT (MBTUH) ORIFICE SIZE (INCHES)
Front 45 0.5625
60 0.69
72 0.875
Top 45 0.58
60 0.75
72 0.84

Specifications & illustrations subject to change without notice or incurring obligations (05/23).
O’Fallon, MO, © Nortek Global HVAC LLC 2023. All Rights Reserved.


1034920A

(Replaces 10349200 )