DFC Series Packaged Heating and Cooling Unit Instruction Manual
- June 12, 2024
- DFC
Table of Contents
- DFC Series Packaged Heating and Cooling Unit
- SAFETY INSTRUCTIONS
- REPLACEMENT PARTS
- GENERAL INFORMATION
- UNIT LOCATION
- UNIT CLEARANCES
- ELECTRICAL WIRING
- CIRCULATING AIR AND FILTERS
- CONDENSATE DRAIN CONNECTION
- STARTUP, ADJUSTMENTS, AND CHECKS
- AIR FLOW ADJUSTMENTS
- SUPERHEAT AND SUBCOOLING
- MAINTENANCE
- APPENDIX A BLOWER PERFORMANCE DATA
- APPENDIX B ELECTRICAL DATA
- APPENDIX C UNIT DIMENSIONS
- WIRING DIAGRAMS
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
DFC SERIES
Packaged Heating and cooling Unit
15 to 25 ton
Instruction Manual
DFC Series Packaged Heating and Cooling Unit
NOTE: 25 ton model shown in picture.
20 ton model has 4 fans
15 ton model has 3 fans
RECOGNIZE THIS SYMBOL AS A SAFETY PRECAUTION.
These installation instructions cover the outdoor installation of single
package heating and cooling units. See the Specification Sheet applicable to
your model for information regardingaccessories.
*NOTE: Please contact your distributor or our website for the applicable
Specification Sheet referred to in this manual.
WARNING
ONLY PERSONNEL THAT HAVE BEEN TRAINED TO INSTALL, ADJUST, SERVICE,
MAINTENANCE OR REPAIR (HEREINAFTER, “SERVICE”) THE EQUIPMENT SPECIFIED IN THIS
MANUAL SHOULD SERVICE THE EQUIPMENT. THE MANUFACTURER WILL NOT BE RESPONSIBLE
FOR ANY INJURY OR PROPERTY DAMAGE ARISING FROM IMPROPER SERVICE OR SERVICE
PROCEDURES. IF YOU SERVICE THIS UNIT, YOU ASSUME RESPONSIBILITY FOR ANY INJURY
OR PROPERTY DAMAGE WHICH MAY RESULT. IN ADDITION, IN JURISDICTIONS THAT
REQUIRE ONE OR MORE LICENSES TO SERVICE THE EQUIPMENT SPECIFIED IN THIS
MANUAL, ONLY LICENSED PERSONNEL SHOULD SERVICE THE EQUIPMENT.
IMPROPER INSTALLATION, ADJUSTMENT, SERVICING, MAINTENANCE OR REPAIR OF THE
EQUIPMENT SPECIFIED IN THIS MANUAL, OR ATTEMPTING TO INSTALL, ADJUST, SERVICE
OR REPAIR THE EQUIPMENT SPECIFIED IN THIS MANUAL WITHOUT PROPER TRAINING MAY
RESULT IN PRODUCT DAMAGE, PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
WARNING
DO NOT BYPASS SAFETY DEVICES
SAFETY INSTRUCTIONS
To The Installer
Before installing this unit, please read this manual to familiarize yourself
on the specific items which must be adhered to, including maximum external
static pressure to unit, air temperature rise and minimum or maximum CFM.
Keep this literature in a safe place for future reference.
WARNING
To avoid property damage, personal injury or death, do not use this unit if
any part has been under water. Immediately call a qualified service technician
to inspect the furnace and to replace any part of the control system and any
gas control having been under water
CAUTION
Sheet metal parts, screws, clips and similar items inherently have shart
edges, and it is necessary that the installer and servicer personnel exercise
caution.
WARNING
Do not connect to or use any device that is not design certified by the
manufacturer for use with this unit. Serious property damage, personal injury,
reduced unit performance and/or hazardous conditions may result from the use
of such non-approved devices.
WARNING
This unit must not be used as a “construction heater” during the finishing
phases of construction on a new structure. This type of use may result in
premature failure of the unit due to extremely low reurn air temperatures and
exposure to corrosive or very dirty atmospheres.
WARNING
HIGH VOLTAGE
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER
SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL
INJURY OR DEATH.
WARNING
To prevent the risk of property damage, personal injury or death, do not store
combustible materials or use gasoline or other flammable liquids or vapors in
the vicinity of this appliance.
REPLACEMENT PARTS
Ordering Parts
When reporting shortages or damages, or ordering repair parts, give the
complete unit model and serial numbers as stamped on the unit’s nameplate.
Replacement parts for this appliance are available through your contractor or
local distributor. Your nearest distributor can be located online at
www.daikinac.com or by contacting:
EQUIPMENT SUPPORT
DAIKIN NORTH AMERICA LLC
19001 KERMIER ROAD
WALLER, TEXAS 77484
855-DAIKIN-1
GENERAL INFORMATION
For complete information and installation instructions for models with DDC
controls, see manual DK-DDC-TGD-XXX.
WARNING
To prevent property damage, personal injury or death due to fire, explosions,
smoke, soot, condensation, electric shock or carbon monoxide, this unit must
be properly installed, repaired, operated and maintained.
This unit is approved for outdoor installation ONLY. Rated performance is
achieved after 20 hours of operation. Rated performance is delivered at the
specified airflow. See outdoor unit specification sheet for split system
models or product specification sheet for packaged and light commercial
models. Specification sheets can be found at
www.daikinac.com for Daikin brand products. Within
the website, please select the residential or commercial products menu and
then select the submenu for the type of product to be installed, such as air
conditioners or heat pumps, to access a list of product pages that each
contain links to that model’s specification sheet.
To assure that your unit operates safely and efficiently, it must be
installed, operated, and maintained in accordance with these installation and
operating instructions, all local building codes and ordinances.
EPA Regulations
Important: The United States Environmental Protection Agency (EPA) has issued various regulations regarding the introduction and disposal of refrigerants in thisunit. Failure to follow these regulations may harmthe environment and can lead to the imposition ofsubstantial fines. Because regulations may vary due to passage of new laws, we suggest a certified technician perform any work done on this unit. Should you have any questions please contact the local office of the EPA.
National Codes
This product is designed and manufactured to permit installation in accordance
with National Codes. It is the installer’s responsibility to install the
product in accordance with National Codes and/or prevailing local codes and
regulations.
The heating and cooling capacities of the unit should be greater than or equal
to the design heating and cooling loads of the area to be conditioned. The
loads should be calculated by an approved method or in accordance with ASHRAE
Guide or Manual J – Load Calculations published by the Air Conditioning
Contractors of America.
Obtain from:
American National Standards Institute
25 West 43rd Street, 4th Floor
New York, NY 10036
System design and installation should also, where applicable, follow
information presented in accepted industry guides such as the ASHRAE
Handbooks. The manufacturer assumes no responsibility for equipment installed
in violation of any code or regulation. The mechanical installation of the
packaged roof top units consists of making final connections between the unit
and building services; supply and return duct connections; and drain
connections (if required). The internal systems of the unit are completely
factory-installed and tested prior to shipment.
Units are generally installed on a steel roof mounting curb assemblywhich has
been shipped to the job site for installation on the roof structure prior to
the arrival of the unit. The model number shownon the unit’s identification
plate identifies the various componentsof the unit such as refrigeration
tonnage, heating input and voltage. Verify that the Voltage listed on the unit
id plate matches the voltage supplied from the site.
Carefully inspect the unit for damage including damage to the cabinetry. Any
bolts or screws which may have loosened in transit must be re-tightened. In
the event of damage, the receiver should:
- Make notation on delivery receipt of any visible damage to shipment or container.
- Notify carrier promptly and request an inspection.
- In case of concealed damage, carrier should be notified as soon as possible-preferably within 5 days.
- File the claim with the following supporting documents:
a. Original Bill of Lading, certified copy, or indemnity bond.
b. Original paid freight bill or indemnity in lieu thereof.
c. Original invoice or certified copy thereof, showing trade and other discounts or reductions.
d. Copy of the inspection report issued by the carrier representative at the time damage is reported to the carrier. The carrier is responsible for making prompt inspection of damage and for a thorough investigation of each claim. The distributor or manufacturer will not accept claims from dealers for transportation damage.
NOTE: When inspecting the unit for transportation damage, remove all packaging materials. Recycle or dispose of the packaging material according to local codes.
Pre-Installation Checks
Carefully read all instructions for the installation prior to installing unit.
Ensure each step or procedure is understood and any special considerations are
taken into account before starting installation. Assemble all tools, hardware
and supplies needed to complete the installation. Some items may need to be
purchased locally.
UNIT LOCATION
WARNING
To prevent possible equipment damage, property damage, personal injury or
death, the following must be observed when installing the unit.
IMPORTANT NOTE: Remove wood shipping rails prior to installation of the
unit. See important note under Roof Curb Installation Only.
All Installations:
Important Note: Unit should be energized 24 hours prior to compressor
start up to ensure crankcase heater has sufficiently warmed the compressors.
Compressor damage may occur if this step is not followed.
NOTE: Units are vertical supply and return only.
Proper installation of the unit ensures trouble-free operation. Improper
installation can result in problems ranging from noisy operation to property
or equipment damages, dangerous conditions that could result in injury or
personal property damage. Damage or repairs due to improper installation are
not covered under the warranty. Give this booklet to the user and explain it’s
provisions. The user should retain these instructions for future reference.
- For proper operation and condensate drainage, the unit must be mounted level.
- The flue outlet hood must be at least three feet above any forced air inlet located within ten feet. The economizer/ manual fresh air intake/motorized fresh air intake and combustion air inlet mounted on the unit are not affected by this restriction.
- Do not locate the unit in an area where the outdoor air (i.e. combustion air for the unit) will be frequently contaminated by compounds containing chlorine or fluorine. Common sources of such compounds include swimming pool chemicals and chlorine bleaches, paint stripper, adhesives, paints, varnishes, sealers, waxes (which are not yet dried) and solvents used during construction and remodeling. Various commercial and industrial processes may also be sources of chlorine/ fluorine compounds.
- To avoid possible illness or death of the building occupants, do NOT locate outside air intake device (economizer, manual fresh air intake, motorized fresh air intake) too close to an exhaust outlet, gas vent termination, or plumbing vent outlet. For specific distances required, consult local codes or in their absence, with the latest edition of the National Fuel Gas Code latest edition of the National Fuel Gas Code NFPA54/ANSI Z223.1 and National Standard of Canada CAN/CSA B149 Installation Codes.
- Allow minimum clearances from the enclosure for fire protection, proper operation, and service access (see unit clearances). These clearances must be permanently maintained.
- If used, do not allow the economizer/manual fresh air damper/ motorized fresh air damper to become blocked by snow or debris. In some climates or locations, it may be necessary to elevate the unit to avoid these problems. For proper operation and condensate drainage, the unit must be mounted level.
- When the unit is heating, the temperature of the return air entering the unit must be between 50° F and 100° F.
Ground Level Installations Only:
- When the unit is installed on the ground adjacent to the building, a level concrete (or equal) base is recommended. Prepare a base that is 3” larger than the package unit footprint and a minimum of 3” thick.
- The base should also be located where no runoff of water from higher ground can collect in the unit.
Roof top Installations Only:
- To avoid possible property damage or personal injury, the roof must have sufficient structural strength to carry the weight of the unit(s) and snow or water loads as required by local codes. Consult a structural engineer to determine the weight capabilities of the roof.
- The unit may be installed directly on wood floors or on Class A, Class B, or Class C roof covering material.
- To avoid possible personal injury, a safe, flat surface for service personnel should be provided.
- As indicated on the unit data plate, a minimum clearance of 36” to any combustible material is required on the furnace access side of the unit. All combustible materials must be kept out of this area.
- This 36” clearance must also be maintained to insure proper combustion air and flue gas flow. The combustion air intake and furnace flue discharge must not be blocked for any reason, including blockage by snow.
- Adequate clearances from the unit to any adjacent public walkways, adjacent buildings, building openings or openable windows must be maintained in accordance with national codes. National Fuel Gas Code NFPA54/ANSI Z223.1 and National Standard of Canada CAN/CSA B149 Installation Codes.
Unit Precautions
- Do not stand or walk on the unit.
- Do not drill holes anywhere in panels or in the base frame of the unit (except where indicated). Unit access panels provide structural support.
- Do not remove any access panels until unit has been installed on roof curb or field supplied structure.
- Do not roll unit across finished roof without prior approval of owner or architect.
- Do not skid or slide on any surface as this may damage unit base. The unit must be stored on a flat, level surface. Protect the condenser coil because it is easily damaged.
Roof Curb Installations Only:
Before installing this unit…
IMPORTANT NOTE: This unit has been equipped with a shipping brace under
the compressor section that MUST BE REMOVED before installing the unit on
a roof curb.
Please follow the instructions below to remove brace.
**CAUTION
** When unit is suspended, boards and shipping brace will drop when screws are
removed. To prevent personal injury, STAND CLEAR. Remove fork hole brackets,
boards and shipping brace from bottom of unit before placing units onto curb.
- Remove wooden struts and shipping brace per installation instructions. The struts are located in the fork holes and are used to protect the unit from damage while lifting with forks. The shipping brace is located under the unit (under compressor). Also remove the fork hole brackets as shown in the following figure.
- Locate and remove the end brackets as shown in the following figure.
- Lift unit per the “Rigging Details” section of this manual, observing all warnings and cautions. When unit is lifted, boards and shipping brace will drop if screws have been removed. To avoid injury, STAND CLEAR.
- Dispose of the boards and brace appropriately.
Curb installations must comply with local codes and should be done in
accordance with the established guidelines of the National Roofing Contractors
Association.
Proper unit installation requires that the roof curb be firmly and permanently
attached to the roof structure. Check for adequate fastening method prior to
setting the unit on the curb.
Full perimeter roof curbs are available from the factory and are shipped
unassembled. Field assembly, squaring, leveling and mounting on the roof
structure are the responsibility of the installing contractor.
All required hardware necessary for the assembly of the sheet metal curb is
included in the curb accessory.
WARNING
To prevent possible equipment damage, property damage, personal injury or
death, the following bullet points must be observed when installing the unit.
- Sufficient structural support must be determined prior to locating and mounting the curb and package unit.
- Ductwork must be constructed using industry guidelines. The duct work must be placed into the roof curb before mounting the package unit. Our full perimeter curbs include duct connection frames to be assembled with the curb. Cantilevered type curbs are not available from the factory.
- Curb insulation, cant strips, flashing and general roofing material are furnished by the contractor.
The curbs must be supported on parallel sides by roof members.
The roof members must not penetrate supply and return duct opening areas as
damage to the unit might occur.
NOTE: The unit and curb accessories are designed to allow vertical duct
installation before unit placement. Duct installation after unit placement is
not recommended.
CAUTION
All curbs look similar. To avoid incorrect curb positioning, check job plans
carefully and verify markings on curb assembly. Instructions may vary in curb
styles and supercede information shown.
See the manual shipped with the roof curb for assembly and installation
instructions.
CLEARANCES *In situations that have multiple units, a 48” minimum clearance is required between the condenser coils.
UNIT CLEARANCES
Adequate clearance around the unit should be kept for safety, service, maintenance, and proper unit operation. A 75” clearance on the non-service side of the unit is required to facilitate possi- ble blower assembly, shaft, wheel replacement and coil removal. *DFG ONLY – A 75” clearance on the service is required for removal of the gas heat exchanger. This unit must not be installed beneath any obstruction. This unit should be installed remote from all building exhausts to inhibit ingestion of exhaust air into the unit’s fresh air intake. ROOF CURB INSTALLATION
ROOF CURB POST-INSTALLATION CHECKS
After installation, check the top of the curb, duct connection frame and
duct flanges to make sure gasket has been applied properly.
Gasket should be firmly applied to the top of the curb perimeter, duct flanges
and any exposed duct connection frame. If gasket is loose, re-apply using
strong weather resistant adhesive.
Protrusion
Inspect curb to ensure that none of the utility services (electric) routed
through the curb protrude above the curb.
**CAUTION**
If protrusions exist, do not attempt to set unit on curb. Information shown.
ROOF TOP DUCT CONNECTIONS
Install duct connections on the roof curb before placing the unit on the
rooftop.
NOTE: If duct is to be fasten to the roof curb the fasteners need to be
installed horizontally to allow the unit to be set flat on the curb.
RIGGING DETAILS
WARNING
To prevent property damage, the unit should remain in an upright position
during all rigging and moving operations.
To facilitate lifting and moving when a crane is used, place the unit in an
adequate cable sling.
CAUTION
Do not lift units two at a time. Provisions for forks have been included in
the unit base fram. Minimum fork length is 72” to prevent damage to the unit.
Provisions for forks have been included in the unit base frame. No other fork
locations are approved.
WARNING
To prevent possible equipment damage, property damage, personal injury or
death, the following bullet points must be observed when installing the unit.
- Unit must be lifted by the four lifting holes located at the base frame corners.
- Lifting cables should be attached to the unit with shackles.
- The distance between the crane hook and the top of the unit must not be less than 60”.
- Two spreader bars must span over the unit to prevent damage to the cabinet by the lift cables. Spreader bars must be of sufficient length so that cables do not come in contact with the unit during transport. Remove wood struts mounted beneath unit base frame before setting unit on roof curb. These struts are intended to protect unit base frame from fork lift damage. Removal is accomplished by extracting the sheet metal retainers and pulling the struts through the base of the unit. Refer to rigging label on the unit.
Important: If using bottom discharge with roof curb, ductwork should be
attached to the curb prior to installing the unit. Ductwork dimensions are
shown in Roof Curb Installation Instructions.
Refer to the Roof Curb Installation Instructions for proper curb installation.
Curbing must be installed in compliance with the National Roofing Contractors
Association Manual.
Lower unit carefully onto roof mounting curb. While rigging unit, center of
gravity will cause condenser end to be lower than supply air end. CAUTION
When unit is suspended, boards and shipping brace will drop when screws are
removed. To prevent personal injury, STAND CLEAR. Remove fork hole brackets,
boards and shipping brace from bottom of unit before placing units onto curb.
To assist in determining rigging requirements, unit weights are shown as
follows: CORNER & CENTER OF GRAVITY LOCATIONS
DATA | DFC Weights (lbs) |
---|---|
15T | 20T |
Corner Weight – A | 486 |
Corner Weight – B | 410 |
Corner Weight – C | 395 |
Corner Weight – D | 433 |
Unit Shipping Weight | 1839 |
Unit Operating Weight | 1724 |
X (Inches) | 69.31 |
Y (Inches) | 43.09 |
NOTE: These weights are without accessories installed.
CAUTION
To prevent severe damage to the bottom of the unit, do not fork lift unit
after wood struts have been removed.
Bring condenser end of unit into alignment with the curb. With condenser end
of the unit resting on curb member and using curb as a fulcrum, lower opposite
end of the unit until entire unit is seated on the curb. When a rectangular
cantilever curb is used, care should be taken to center the unit. Check for
proper alignment and orientation of supply and return openings with duct.
Rigging Removal
CAUTION
To prevent damage to the unit, do not allow crane hooks and spreader bars to
rest on the roof of the unit.
Remove spreader bars, lifting cables and other rigging equipment.
ELECTRICAL WIRING
WARNING
HIGH VOLTAGE
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER
SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL
INJURY OR DEATH.
WARNING
HIGH VOLTAGE
TO AVOID PROPERTY DAMAGE, PERSONAL INJURY OR DEATH DUE TO ELECTRICAL SHOCK, DO
NOT TAMPER WITH FACTORY WIRING. THE INTERNAL POWER AND CONTROL WIRING OF THESE
UNITS ARE FACTORY-INSTALLED AND HAVE BEEN THROUGHLY TESTED PRIOR TO SHIPMENT.
CONTACT YOUR LOCAL REPRESENTATIVE IF ASSISTANCE IS REQUIRED.
CAUTION
To prevent damage to the wiring, protect wiring from sharp edges. Follow
national electrical code and all local codes and ordinances. Do not route
wires through removable access panels.
CAUTION
Conduit and fittings must be weather-tight to prevent water entry into the
building.
For unit protection, use a fuse or HACR circuit breaker that is in excess of
the circuit ampacity, but less than or equal to the maximum overcurrent
protection device. DO NOT EXCEED THE MAXIMUM OVERCURRENT DEVICE SIZE SHOWN ON
UNIT DATA PLATE.
All line voltage connections must be made through weatherproof fittings. All
exterior power supply and ground wiring must be in approved weatherproof
conduit.
The main power supply wiring to the unit and low voltage wiring to accessory
controls must be done in accordance with these instructions, the latest
edition of the National Electrical Code (ANSI/ NFPA 70), and all local codes
and ordinances.
The main power supply shall be three-phase, three wire. The unit is factory
wired for the voltage shown on the unit’s data plate.
NOTE: If supply voltage is 208V, all leads on primary of transformer(s)
must be moved from the 230V to the 208V tap.
Main power wiring should be sized for the minimum circuit ampacity shown on
the unit’s data plate. Size wires in accordance with the ampacity tables in
Article 310 of the National Electrical Code. If long wires are required, it
may be necessary to increase the wire size to prevent excessive voltage drop.
Wires should be sized for a maximum of 3% voltage drop.
CAUTION
To avoid property damage or personal injury due to fire, use only copper
conductors.
CAUTION
To prevent improper and dangerous operation due to wiring errors, label all
wires prior to disconnection when servicing controls. Verify proper operation
after servicing.
NOTE: A weather-tight disconnect switch, properly sized for the unit
total load must be installed. An external field supplied disconnect may be
mounted on the exterior panel.
Ensure the data plate is not covered by the field-supplied disconnect switch.
- Some disconnect switches are not fused. Protect the power leads at the point of distribution in accordance with the unit data plate.
- The unit must be electrically grounded in accordance with local codes or, in the absence of local codes, with the latest edition of the National Electrical Code (ANSI-NFPA 70). A ground lug is provided for this purpose. Size grounding conductor in accordance with Table 250-95 of the National Electrical Code. Do not use the ground lug for connecting a neutral conductor.
- Connect power wiring to the middle contactor within the main control box or power block, if equipped.
|
---|---
15-25 TON TSTAT POWER AND LOW VOLTAGE TERMINAL LOCATIONS| 15-25 TON DDC POWER
AND LOW VOLTAGE TERMINAL LOCATIONS
NOTE: Depending on the options installed, the location of the components
may vary in some models.
WARNING
ailure of unit due to operation on improper line voltage or with excessive
phase unbalance constitues product abuse and is not covered by the warranty.
It may cause severe damage to the unit electrical components.
Areas Without Convenience Outlet
It is recommended that an independent 115V power source be brought to the
vicinity of the roof top unit for portable lights and tools used by the
service mechanic.
NOTE: Refer to local codes for requirements. These outlets can also be
factory installed.
Units installed on Roof Tops
Main power and low voltage wiring may enter the unit through the side or
through the roof curb. Install conduit connectors at the desired entrance
locations. External connectors must be weatherproof. All holes in the unit
base must be sealed (including those around conduit nuts) to prevent water
leakage into building. All required conduit and fittings are to be field
supplied. For wiring and/or gas connections entering through roof curb, the
through the base kit would be required (TTBCK03).
Supply voltage to roof top unit must not vary by more than 10% of the value
indicated on the unit data plate. Phase voltage unbalance must not exceed 2%.
Contact your local power company for correction of improper voltage or phase
unbalance. ELECTRICAL
ENTRANCE LOCATIONS
Unit is equipped with a Low Voltage Terminal Block and has Single Point wiring
to the contactor.
Low Voltage Control Wiring
NOTE: For models equipped with the DDC controls option, refer to the
supplemental DDC literature supplied with the unit for additional information.
- A 24V thermostat must be installed for unit operation. It may be purchased with the unit or field -supplied. Thermostats may be programmable or electromechanical as required.
- Locate thermostat or remote sensor in the conditioned space where it will sense average temperature. Do not locate the device where it may be directly exposed to supply air, sunlight or other sources of heat. Follow installation instructions packaged with the thermostat.
- Use #18 AWG wire for 24V control wiring runs not exceeding 75 feet. Use #16 AWG wire for 24V control wiring runs not exceeding 125 feet. Use #14 AWG wire for 24V control wiring runs not exceeding 200 feet. Low voltage wiring may be National Electrical Code (NEC) Class 2 where permitted by local codes.
- Route thermostat wires from sub-base terminals to the unit. Control wiring should enter through the duct panel (dimple marks entrance location) or through the specified through the base connection points through the base pan. Connect thermostat and any accessory wiring to low voltage terminal block TB1 in the main control box.
NOTE: Field-supplied conduit may need to be installed depending on
unit/curb configuration. Use #18 AWG solid conductor wire whenever connecting
thermostat wires to terminals on sub-base. DO NOT use larger than #18 AWG
wire. A transition to #18 AWG wire may be required before entering thermostat
sub-base.
NOTE: Refer to unit wiring diagrams for thermostat hookups.
CIRCULATING AIR AND FILTERS
Ductwork
The supply duct from the unit through a wall may be installed without
clearance. However, minimum unit clearances must be maintained (see
“Clearances” section). The supply duct should be provided with an access panel
large enough to inspect the air chamber downstream of the heat exchanger. A
cover should be tightly attached to prevent air leaks.
Ductwork dimensions are shown in the roof curb installation manual.
If desired, supply and return duct connections to the unit may be made with
flexible connections to reduce possible unit operating sound transmission.
CONDENSATE DRAIN CONNECTION
Condensate Drain Connection
A 1” female NPT drain connection is supplied on the end of the condensate pan,
with an alternative connection on the bottom of the pan. An extrnal trap must
be installed for proper condensate drainage. NOTE: Trap should be deep enough to offset
maximum unit static difference. A minimum 4” trap is recommended.
DRAIN CONNECTION
Install condensate drain trap as shown. Use 1” drain line and fittings or
larger. Do not operate without trap.
NOTE: All threaded connection use pipe sealer.
Horizontal Drain
Drainage of condensate directly onto the roof may be acceptable; (refer to
local code). It is recommended that a small drip pad of either stone, mortar,
wood or metal be provided to prevent any possible damage to the roof. When
using the horizontal drain connection, check the drain plug in bottom
connection to ensure it is tight.
Cleaning
Due to the fact that drain pans in any air conditioning unit will have some
moisture in them, algae and fungus will grow due to airborne bacteria and
spores. Periodic cleaning is necessary to prevent this build-up from plugging
the drain.
STARTUP, ADJUSTMENTS, AND CHECKS
WARNING
HIGH VOLTAGE
To avoid personal injury or death due to electrical shock, bond the frame of
this unit to the building electrical ground by use of the grounding terminal
provided or other acceptable means. Disconnect all power before servicing or
installing this unit.
CAUTION
To prevent property damage or personal injury, Do not start the unit until all
necessary pre-checks and test have been performed.
WARNING
MOVING MACHINERY HAZARD!
To prevent possible personal injury or death, disconnect power to the unit and
padlock in the “OFF” position before servicing fans.
Heating Startup
On new installations, or if a major component has been replaced, the operation
of the unit must be checked.
Check unit operation as outlined in the following instructions. If any
sparking, odors, or unusual sounds are encountered, shut off electrical power
and recheck for wiring errors, or obstructions in or near the blower motors.
The Startup, Adjustments, and Checks procedure provides a stepby-step sequence
which, if followed, will assure the proper startup of the equipment in the
minimum amount of time. Air balancing of duct system is not considered part of
this procedure. However, it is an important phase of any air conditioning
system startup and should be performed upon completion of the Startup,
Adjustments, and Checks procedure. The Startup, Adjustments, and
Checksprocedure at outside ambients below 55°F should be limited to a
readiness check of the refrigeration system with the required final check and
calibration left to be completed when the outside ambient rises above 55°F.
Temporary Heating Or Cooling
If the unit is to be used for temporary heating or cooling, a “Startup,
Adjustments, and Checks” must first be performed in accordance with this
manual. Damage or repairs due to failure to comply with these requirements are
not covered under the warranty. After the machines are used for temporary
heating or cooling, inspect the coils, fans, and motors for unacceptable
levels of construction dust and dirt and install new filters.
Contractor Responsibility
The installing contractor must be certain that:
- All supply and return air ductwork is in place, properly sealed, and corresponds with installation instructions.
- All thermostats are mounted and wired in accordance with installation instructions.
- All electric power, all gas, hot water or steam line connections, and the condensate drain installation have been made to each unit on the job. These main supply lines must be functional and capable of operating all units simultaneously.
- Clean Air filters are in place.
Roof Curb Installation Check
Inspect the roof curb for correct installation. The unit and curb assembly
should be level. Inspect the flashing of the roof mounting curb to the roof,
especially at the corners, for good workmanship. Also check for leaks around
gaskets. Note any deficiencies in a separate report and forward to the
contractor.
Obstructions, Fan Clearance and Wiring
Remove any extraneous construction and shipping materials that may be found
during this procedure. Rotate all fans manually to check for proper clearances
and that they rotate freely. Check for bolts and screws that may have jarred
loose during shipment to the job site. Retighten if necessary. Re-tighten all
electrical connections.
Field Duct Connections
Verify that all duct connections are tight and that there is no air bypass
between supply and return.
Filter Section Check
Remove filter section access panels and check that filters are properly
installed. Note airflow arrows on filter frames.
Pre-startup Precautions
It is important to your safety that the unit has been properly grounded during
installation. Check ground lug connection in main control box for tightness
prior to closing circuit breaker or disconnect switch. Verify that supply
voltage on line side of disconnect agrees with voltage on unit identification
plate and is within the utilization voltage range as indicated in Appendix C
Electrical Data.
System Voltage – That nominal voltage value assigned to a circuit or
system for the purpose of designating its voltage class.
Nameplate Voltage – That voltage assigned to a piece of equipment for the
purpose of designating its voltage class and for the purpose of defining the
minimum and maximum voltage at which the equipment will operate.
Utilization Voltage – The voltage of the line terminals of the equipment
at which the equipment must give fully satisfactory performance. Once it is
established that supply voltage will be maintained within the utilization
range under all system conditions, check and calculate if an unbalanced
condition exists between phases. Calculate percent voltage unbalance as
follows:
Three Phase Models
- PERCENT VOLTAGE UNBALANCE HOW TO USE THE FORMULA :
EXAMPLE: With voltage of 220, 216, and 213
- Average Voltage = 220+216+213=649 / 3 = 216
- Maximum Voltage Deviations from Average Voltage = 220 – 216 = 4
- Percent Voltage Unbalance
Percent voltage unbalance MUST NOT exceed 2%.
AIR FLOW ADJUSTMENTS
When the final adjustments are complete, the current draw of the motor should
be checked and compared to the full load current rating of the motor. The
amperage must not exceed the service factor stamped on the motor nameplate.
The total airflow must not be less than that required for operation of the
electric heaters or the furnace.
If an economizer is installed, check the unit operating balance with the
economizer at full outside air and at minimum outside air.
NOTE: High Stage Airflow setting below 300 CFM/Ton is not recommended, as
evaporator freezing or poor unit performance is possible.
- The unit has one set of taps for cooling (T1-T5) and a second set of taps for heating (T6-T10).
- When Heat is called TB1-W1 will also call TB1-DH activating the second set of taps T6-T10.
- If cooling and heating is called at the same time heating will take priority and T6-T10 will be chosen by default.
- Taps T1 and T2 are for low cool operation (cooling stage 1) and Taps T3 to T5 are for high cool operation (cooling stage 2).
- Taps T6 and T7 are for low heat operation (heating stage 1) and taps T8 to T10 are for high heat operation (heating stage 2).
Taps are selected by changing the position of the low voltage leads on the
terminal block TB1. Refer to Appendix A for blower performance at each speed
tap.
Fan speed for G (GR) is fixed at TB1-T1 and cannot be moved.
Low Cool Y1, Yellow (YL) is movable and set to TB1-T1.
Low Heat W1, White (WH) is movable and set to TB1-T6.
High Cool Y2, Purple (PU) is movable and set to TB1-T3.
High Heat W2, Brown (BR) is movable and set to TB1-T8.
These wires can be moved together or separately and placed on any unoccupied
terminal.
Note: YL can be moved to tap T3 as long as YL does not share the tap with
PU. WH can be moved to tap T7 as long as WH does not share the tap with BR.
If high cool operation is set at Tap T4 or T5, low cool operation must be set
at T2.
If high heat operation is set at T9 or T10, low heat operation must be set at
T7.
Note: On units with DDC controls installed, air flow adjustments are made
through settings in the DDC controller and speed tap adjustments are not
required. Refer to the DDC User Manual for details on making airflow
adjustments. Individual settings are available for Fan Only, Low Stage
Cooling, High Stage Cooling, Low Stage Heating, and High Stage Heating which
can be adjusted as needed to meet airflow requirements. ** TB1-DH is energized when the unit is in
heat mode. When TB1-DH is energized, the blower motor operates at a new group
of programmed speeds, T6-T10, in place of T1-T5.
-
Move YELLOW (YL) wire from TB1-T1 to T2 to change blower speed during cooling stage 1 operation.
(Do not move wires YL and PU to the same taps) -
Move WHITE (WH) wire from TB1-T6 to T7 to change blower speed during heating stage 1 operation.
(Do not move wires WH and BR to the same taps) -
Move PURPLE (PU) wire from TB1-T3 to T4 or T5 to change blower speed during cooling stage 2 operation.
(Do not move wires YL and PU to the same taps) -
Move BROWN (BR) wire from TB1-T8 to T9 or T10 to change blower speed during heating stage 2 operation.
(Do not move wires WH and BR to the same taps)
DFC/DFG OPERATION and WIRE RANGE CHART X= 24V Signal
= Range of AVAILABLE TAPS
For wire color information and placement, view DFC/DFG Model Wiring
Electrical Input Check
Make preliminary check of evaporator fan ampere draw and verify that motor
nameplate amps are not exceeded. A final check of amp draw should be made upon
completion of air balancing of the duct system (see Appendix B).
Refrigeration System
The unit is equipped with a thermal expansion valve as a metering device.
Ensure the hold-down bolts on the compressor are secure and have not vibrated
loose during shipment. Check that vibration grommets have been installed.
Visually check all piping for damage and leaks; repair if necessary. The
entire system has been factory charged and tested, making it unnecessary to
field charge. Factory charges are shown on the unit’s nameplate. To confirm
charge levels or, if a leak occurs and charge needs to be added to the system,
it is recommended to evacuate the system and recharge refrigerant to unit
nameplate specifications. This unit has been rated in the cooling mode at the
AHRI rated conditions of: Indoor (80°db / 67°wb) and outdoor (95°db).
While operating at this condition, the superheat and subcool for each circuit
for each unit should fall within the values listed in the table below. The
superheat is measured at the suction service port located near the compressor.
The subcool is measured at the liquid line service port.
SUPERHEAT AND SUBCOOLING
Checking Subcooling
NOTE: Units with a TXV should be charged to Subcooling only.
Make sure the air flow is correct before making any adjustments.
EXAMPLE:
a. Liquid Line Pressure = 417 PSI
b. Corresponding Temp. = 120°F
c. Thermometer on Liquid line = 109°F.
To obtain the amount of subcooling, subtract 109°F from 120°F. The difference
is 11° subcooling. See the specification sheet or technical information manual
for the design subcooling range for your unit.
SUBCOOLING FORMULA = SATURATED LIQUID LINE TEMPERATURE – LIQUID LINE
TEMPERATURE
Checking Superheat
EXAMPLE:
a. Suction Pressure = 143 PSI
b. Corresponding Temp. = 50°F
c. Thermometer on Suction Line = 59°F
To obtain the degrees temperature of superheat, subtract 50.0 from 59.0°F. The
difference is 9° Superheat. The 9° Superheat would fall in the ± range of
allowable superheat.
SUPERHEAT = SUCTION LINE TEMP – SAT. SUCTION TEMP.
Superheat Adjustment
NOTE: Superheat adjustments should not be made until indoor ambient
conditions have stabilized. This could take up to 24 hours depending on indoor
temperature and humidity. Before checking superheat, run the unit in cooling
for 15-20 minutes or until refrigerant pressures stabilize. Use the following
guidelines and methods to check unit operation and ensure that the refrigerant
charge is within limits.
For TXV systems, to adjust superheat, unscrew the cover from the expansion
valve, locate the adjustment screw, and turn it clockwise (in) to increase
superheat or counterclockwise (out) to decrease superheat. It is recommended
to make small adjustments at a time, 1/8-1/4 turn increments. Replace
adjustment cap. Wait a minimum of 15 minutes between adjustments to allow time
for the TXV and pressures to stabilize.
Refrigerant Charge Check
NOTE : For optimal performance, follow charging instructions below.
Units with Fixed Orifice Devices
All package units with fixed orifice devices are charged using the superheat
method at the compressor suction line. To increase super heat, remove charge
and to decrease super heat, add charge. After superheat is adjusted, it is
recommended to check unit subcooling at the condenser coil liquid line. See
Figure 14: DESIGN SUPERHEAT AND SUBCOOLING table for targets on each model.
Units with Expansion valve (TXV)
Single Stage Cooling Application: Refer to the Design Superheat & Subcooling
table
Two-Stage Cooling Application: Run unit on Low Stage cooling and refer to
Design Superheat & Subcooling table.
-
Purge gauge lines. Connect service gauge manifold to access fittings. Run system at least 10 minutes to allow pressure to stabilize.
-
Temporarily install thermometer on liquid (small) line near liquid line access fitting with adequate contact and insulate for best possible reading.
-
Check subcooling and superheat. System should have a subcooling and superheat within the range listed on the Design Superheat and Subcooling table.
a. If subcooling and superheat are low, adjust TXV superheat, then check subcooling.
NOTE: To adjust superheat, turn the valve stem clockwise to increase and counterclockwise to decrease. If an under charge is suspected, recover the charge, re-evacuate the system and recharge per data plate. No adjustments should be made if suspecting a charge issue.
b. If subcooling is low and superheat is high, add charge to raise subcooling then check superheat.
c. If subcooling and superheat are high, adjust TXV valve superheat, then check subcooling.
d. If subcooling is high and superheat is low, adjust TXV valve superheat and remove charge to lower the subcooling.
NOTE: Do NOT adjust the charge based on suction pressure unless there is a gross undercharge. -
Disconnect manifold set, installation is complete.
Design Superheat & Subcooling
Model| Circuit| Superheat 2°F| Subcooling ± 1°F| Expansion Device| Outdoor
Ambent (°F)
DFG180| 1| 8| 14| TXV| 95
DFG180| 2| 8| 12| TXV| 95
DFG240| 1| 8| 9| TXV| 95
DFG240| 2| 8| 6| TXV| 95
DFG300| 1| 10| 7| TXV| 95
DFG300| 2| 10| 7| TXV| 95
NORMAL SEQUENCE OF OPERATION – COOLING
Refrigeration Sequence Check
With the disconnect switch open, remove the field connected thermostat wire
from terminal R on TB1 terminal block. Place a jumper across terminals R and
G, and across R and Y on TB1 terminal block. Close the disconnect switch. The
following operational sequence should be observed.
-
Current through primary winding of transformer TRANS1 energizes the 24-volt control circuit.
-
To simulate a mechanical call for cooling from the wall thermostat, place a jumper across terminals R and Y1 of terminal block TB1.
-
UNIT WITH ECONOMIZER OPTION: The compressor circuit is interlocked through terminals 3 and 4 of the economizer module. If the outdoor air enthalpy (temperature and humidity) is not suitable for cooling, the economizer terminals will be closed permitting compressor to be energized.
-
The blower contactor closes its contacts L1, L2 and L3 to T1, T2 and T3 to provide power to the supply fan motor.
-
Compressor contactor closes its contacts L1, L2 and L3 to T1, T2 and T3 to provide power to the compressor motor COMP 1; COMP 2, if conditions are correct. In addition, contactor C1 closes its contact L3 to T3 , energizing the condenser fan motor.
WARNING
BURN HAZARD!
DO NOT TOUCH! DISCHARGE LINE MAY BE HOT! -
Check that each compressor is operating correctly. The scroll compressors in these units MUST operate in the proper rotation. To ensure the compressors are operating in the correct direction, check the compressor discharge line pressure or temperature after each compressor is started. The discharge pressure and discharge line temperature should increase. If this does not occur and the compressor is producing an exceptional amount of noise, perform the following checks.
• Ensure all compressors are operating in the proper direction. If a single motor is operating backwards, check the power wiring for that motor and correct any leads that have been interchanged at the contactor or at the motor. -
With all safety devices closed, the system will continue cooling operation until the thermostat is satisfied.
-
Disconnecting the jumper wire between R and Y1 and Y2 and between R and G on TB1 terminal block will simulate a satisfied thermostat. The compressors will cycle off and IIC (pin 12) will initiate its time delay cycle. The compressor and the supply fan will cycle off.
-
After a time delay of approximately 3 minutes, the compressor control circuits will be ready to respond to a subsequent call for cooling from the wall thermostat.
-
Open disconnect switch. Reconnect the field thermostat wire at terminal R on terminal block TB1.
MAINTENANCE
WARNING
HIGH VOLTAGE
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER
SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL
INJURY OR DEATH.
WARNING
To prevent personal injury or death due to improper installation, adjustment,
alteration, service or maintenance, refer to this manual. For additional
assistance or information, consult a qualified installer, service agency or
the gas supplier.
CAUTION
This unit must be ISOLATED from the gas supply piping system by closing its
individual manual shutoff valve during any pressure testing equal to or less
than 1/2 psig.
Preventive maintenance is the best way to avoid unnecessary expense and
inconvenience. Have this system inspected at regular intervals by qualified
service personnel, at least twice a year. Routine maintenance should cover the
following items:
- Tighten, set screws, and wire connections.
- Clean evaporator mechanically or with cold water, if necessary. Usually any fouling is only matted on the entering air face of the coil and can be removed by brushing.
- Replace filters as needed (see below).
- Check for blockage of condensate drain.
- Check power and control voltages.
- Check running amperage.
- Check operating temperatures and pressures.
- Check and adjust temperature and pressure controls.
- Check and adjust damper linkages.
- Check operation of all safety controls.
- Examine gas furnaces (see below and the User’s Information Manual).
- Check condenser fans and tighten set screws.
Filters
CAUTION
TO PREVENT PROPERTY DAMAGE DUE TO FIRE AND LOSS OF EQUIPMENT EFFICIENCY OR
EQUIPMENT DAMAGE DUE TO DUST AND LINT BUILD UP ON INTERNAL PARTS, NEVER
OPERATE UNIT WITHOUT AN AIR FILTER INSTALLED IN THE RETURN AIR SYSTEM
Every application may require a different frequency of replacement of dirty
filters. Filters must be replaced at least every three (3) months during
operating seasons.
Dirty filters are the most common cause of inadequate heating or cooling
performance. Filter inspection should be made at least every two months; more
often if necessary because of local conditions and usage.
Dirty throwaway filters should be discarded and replaced with a new, clean
filter.
Disposable return air filters are supplied with this unit. See the unit
Specification Sheet or Technical Manual for the correct size and part number.
To remove the filters, remove the filter access panel on return side of the
unit.
Cabinet Finish Maintenance
Use a fine grade automotive wax on the cabinet finish to maintain the finish’s
original high luster. This is especially important in installations with
extended periods of direct sunlight.
Clean Outside Coil (Qualified Servicer Only)
The coil with the outside air flowing over it should be inspected annually and
cleaned as frequently as necessary to keep the finned areas free of lint, hair
and debris.
NOTE: Clean the opposite direction of air flow.
Maintenance of MicroChannel Heat Exchangers (MCHE)
Frequent servicing is essential to maintaining the required MCHE performance.
For every installed Danfoss MCHE, service records must be documented.
CAUTION
Prior to servicing MCHE, be sure to disconnect the power supply and use lock-
out methods to prevent the power from accidentally being turned on.
Shut Down Periods
During periods when the MCHE is not operated for longer than a week, the MCHE
must be completely cleaned following the cleaning procedure. This practice
must also be performed during short shut-down periods where corrosive deposits
accumulate on the MCHE.
Cleaning Procedure
Relative to tube & fin heat exchangers, MicroChannel heat exchanger coils tend
to accumulate more dirt on the surface of the coil and less dirt inside the
coil, making them easier to clean. Follow the steps below for proper cleaning:
STEP 1: Remove Surface Debris
Remove surface dirt, leaves, fibers, etc. with a vacuum cleaner (preferably
with a brush or other soft attachment rather than a metal tube), compressed
air blown from the inside out, and/or a soft bristle (not wire!) brush. Do not
impact or scrape the coil with the vacuum tube, air nozzle, etc.
STEP 2: Rinse
Rinse the coil by following procedure:
1. Rinse the coil by approved MCHE cleaner first, or rinsing by water
directly;
2. Waiting for 5 minutes;
3. Wash the coil by water;
Adjust the angle of gimbaled nozzle and insert it through fans. Using an
extension rod if the nozzle cannot reach the bottom side. Preferably cleaning
the coils from the insideout and top to bottom (see figure 1), running the
water through every fin passage until it comes out clean. The fins of
MicroChannel coils are stronger than traditional tube & fin coil fins but
still need to be handled with care. Do not hit the coil with the hose. We
recommend placing your thumb over the end of the hose to obtain a gentler
spray and reduce the possibility of impact damage. Please PAY MORE ATTENTION
when using a pressure cleaning equipment to prevent damage. Highest pressure
of cleaning equipment shall not exceed 15 bar, and tentatively move the
cleaning equipment from far to near to prevent damage.
- KEEP the outlet of washer away from coil for at least 4in (see figure 2);
- KEEP the water gun perpendicular to the coil surface and the angle error shall less than 20°, or ±40° if the distance from washer to coil is more than 12in (see figure 2);
- Water outlet angle for high pressure cleaning equipment shall over 15° (see figure 3).
Warranty claims related to cleaning damage, especially for incorrect pressure washing operation, or corrosion resulting from applying non-recommended cleaners, will NOT be honored.
STEP 3: Remove Surface Debris
Depending on the installation and fin geometry, MicroChannel heat exchangers
could possibly retain more water compared to traditional tube & fin coils. It
is advised to blow off or vacuum out the residual water from the coil to speed
up drying and prevent pooling. Daikin recommends a quarterly cleaning of the
coils, as the minimum. The cleaning frequency should be increased depending on
the level of dirt/dust accumulation and the environment (e.g., coastal areas
with chlorides and salts) or industrial areas with aggressive substances.
WARNING
Field applied coatings are not recommended for brazed aluminum MicroChannel
heat exchangers. MicroChannel heat exchangers must NOT be coated using any
other coating, Coating of a coil using a supplier or coating process is not
approved and voids the product warranty. It may also reduce the lifetime
and/or the performance of the MicroChannel heat exchanger.
Condenser Fans
Bearings on the condenser fan motors are permanently lubricated.
No additional oiling is required.
Functional Parts
Refer to the unit Parts Catalog for a list of functional parts. Parts are
available from your distributor.
APPENDIX A BLOWER PERFORMANCE DATA
DIRECT DRIVE – STANDARD
DFC1803D Standard Static
Speed Tap| Static| Airflow| RPM 1| RPM 2| BHP 1| BHP 2
T1| 0.2| 3198| 422| 434| 0.19| 0.20
0.4| 2752| 503| 498| 0.23| 0.22
0.6| 2055| 609| 564| 0.27| 0.25
0.8| 1372| 674| 648| 0.30| 0.29
1| –| –| –| –| –
1.2| –| –| –| –| –
T2| 0.2| 4368| 496| 509| 0.35| 0.35
0.4| 3945| 567| 568| 0.39| 0.40
0.6| 3374| 654| 626| 0.46| 0.44
0.8| 3899| 714| 696| 0.50| 0.48
1| 2318| 761| 751| 0.53| 0.52
1.2| 1766| 791| 826| 0.55| 0.57
T3| 0.2| 5124| 544| 558| 0.50| 0.51
0.4| 4716| 609| 613| 0.56| 0.56
0.6| 4222| 685| 667| 0.63| 0.61
0.8| 3643| 741| 728| 0.68| 0.67
1| 3264| 788| 778| 0.72| 0.71
1.2| 2756| 827| 845| 0.76| 0.77
T4| 0.2| 7370| 685| 705| 1.33| 1.37
0.4| 7008| 733| 750| 1.43| 1.46
0.6| 6703| 779| 791| 1.52| 1.54
0.8| 6574| 826| 829| 1.61| 1.61
1| 6021| 873| 868| 1.70| 1.69
1.2| 5643| 928| 911| 1.80| 1.77
T5| 0.2| 7626| 702| 722| 1.27| 1.31
0.4| 7265| 749| 766| 1.36| 1.39
0.6| 6970| 793| 806| 1.44| 1.46
0.8| 4105| 837| 843| 1.51| 1.53
1| 6316| 882| 881| 1.60| 1.59
1.2| 5955| 936| 922| 1.69| 1.67
T6| 0.2| 7227| 677| 695| 1.11| 1.14
0.4| 6858| 726| 741| 1.19| 1.22
0.6| 6540| 774| 783| 1.27| 1.29
0.8| 6188| 820| 823| 1.35| 1.35
1| –| –| –| –| –
1.2| –| –| –| –| –
T7| 0.2| 7431| 690| 709| 1.19| 1.22
0.4| 7065| 738| 754| 1.27| 1.30
0.6| 6760| 784| 795| 1.35| 1.37
0.8| 6423| 829| 833| 1.43| 1.44
1| 6084| 875| 872| 1.51| 1.51
1.2| –| –| –| –| –
T8| 0.2| 7669| 705| 724| 1.29| 1.32
0.4| 7308| 751| 769| 1.37| 1.41
0.6| 7016| 795| 809| 1.45| 1.48
0.8| 6696| 839| 846| 1.53| 1.55
1| 6366| 884| 883| 1.62| 1.61
1.2| 6007| 938| 923| 1.71| 1.69
T9| 0.2| 7783| 712| 732| 1.34| 1.38
0.4| 7424| 758| 776| 1.42| 1.46
0.6| 7138| 800| 815| 1.50| 1.53
0.8| 6826| 843| 851| 1.59| 1.60
1| 6501| 888| 888| 1.67| 1.67
1.2| 6149| 942| 928| 1.77| 1.74
T10| 0.2| 7885| 719| 739| 1.38| 1.42
0.4| 7527| 764| 782| 1.47| 1.51
0.6| 7247| 805| 821| 1.55| 1.58
0.8| 6941| 848| 857| 1.63| 1.65
1| 6620| 892| 893| 1.72| 1.72
1.2| 6275| 946| 932| 1.82| 1.79
DFC2403D Standard Static
Speed Tap| Static| Airflow| RPM 1| RPM 2| BHP 1| BHP 2
T1| 0.2| 4426| 504| 521| 0.29| 0.30
0.4| 4019| 574| 579| 0.33| 0.33
0.6| 3466| 660| 636| 0.38| 0.37
0.8| 2911| 717| 701| 0.41| 0.40
1| 2424| 772| 756| 0.44| 0.43
1.2| 1881| 809| 825| 0.47| 0.47
T2| 0.2| 5830| 591| 608| 0.62| 0.64
0.4| 5453| 649| 659| 0.68| 0.69
0.6| 5056| 711| 707| 0.75| 0.74
0.8| 4597| 771| 757| 0.81| 0.80
1| 4141| 832| 803| 0.88| 0.85
1.2| 3702| 867| 861| 0.91| 0.91
T3| 0.2| 6929| 659| 677| 0.98| 1.00
0.4| 6571| 709| 724| 1.05| 1.07
0.6| 6269| 756| 765| 1.12| 1.13
0.8| 5883| 815| 806| 1.21| 1.19
1| 5461| 876| 845| 1.30| 1.25
1.2| 5096| 910| 895| 1.35| 1.32
T4| 0.2| 9133| 798| 821| 2.08| 2.14
0.4| 8793| 837| 860| 2.19| 2.25
0.6| 8538| 871| 895| 2.28| 2.34
0.8| 8286| 912| 929| 2.38| 2.43
1| 7991| 947| 960| 2.48| 2.51
1.2| 7739| 984| 992| 2.57| 2.59
T5| 0.2| 9371| 813| 837| 2.26| 2.33
0.4| 9030| 852| 875| 2.37| 2.43
0.6| 8756| 888| 912| 2.47| 2.53
0.8| 8516| 924| 946| 2.57| 2.63
1| 8245| 953| 977| 2.65| 2.71
1.2| 8000| 990| 1007| 2.75| 2.80
T6| 0.2| 7986| 725| 745| 1.42| 1.46
0.4| 7641| 769| 787| 1.51| 1.54
0.6| 7394| 805| 824| 1.58| 1.61
0.8| 7076| 860| 859| 1.68| 1.68
1| –| –| –| –| –
1.2| –| –| –| –| –
T7| 0.2| 8329| 746| 767| 1.59| 1.64
0.4| 7987| 789| 808| 1.68| 1.73
0.6| 7748| 823| 844| 1.76| 1.80
0.8| 7450| 875| 878| 1.87| 1.87
1| 7096| 925| 911| 1.98| 1.95
1.2| –| –| –| –| –
T8| 0.2| 8663| 768| 789| 1.78| 1.83
0.4| 8323| 808| 829| 1.88| 1.92
0.6| 8083| 842| 865| 1.95| 2.01
0.8| 7806| 890| 898| 2.06| 2.08
1| 7473| 935| 930| 2.17| 2.16
1.2| 7204| 970| 966| 2.25| 2.24
T9| 0.2| 9133| 798| 821| 2.08| 2.14
0.4| 8793| 837| 860| 2.19| 2.25
0.6| 8538| 871| 895| 2.28| 2.34
0.8| 8286| 912| 929| 2.38| 2.43
1| 7991| 947| 960| 2.48| 2.51
1.2| 7739| 984| 992| 2.57| 2.59
T10| 0.2| 9371| 813| 837| 2.26| 2.33
0.4| 9030| 852| 875| 2.37| 2.43
0.6| 8756| 888| 912| 2.47| 2.53
0.8| 8516| 924| 946| 2.57| 2.63
1| 8245| 953| 977| 2.65| 2.71
1.2| 8000| 990| 1007| 2.75| 2.80
DFC3003D Standard Static
Speed Tap| Static| Airflow| RPM 1| RPM 2| BHP 1| BHP 2
T1| 0.2| 5835| 605| 594| 0.57| 0.56
0.4| 5496| 659| 654| 0.63| 0.62
0.6| 5095| 706| 736| 0.67| 0.70
0.8| 4723| 757| 785| 0.72| 0.75
1| 4182| 836| 848| 0.79| 0.81
1.2| 3784| 874| 884| 0.83| 0.84
T2| 0.2| 7123| 669| 647| 0.91| 0.88
0.4| 6801| 717| 701| 0.97| 0.95
0.6| 6439| 761| 761| 1.03| 1.03
0.8| 6144| 808| 813| 1.10| 1.10
1| 5766| 864| 877| 1.17| 1.19
1.2| 5416| 902| 921| 1.22| 1.25
T3| 0.2| 8988| 809| 767| 1.66| 1.58
0.4| 8693| 847| 810| 1.74| 1.67
0.6| 8401| 885| 843| 1.82| 1.73
0.8| 8197| 923| 892| 1.90| 1.83
1| 7998| 954| 951| 1.96| 1.96
1.2| 7722| 988| 1000| 2.03| 2.06
T4| 0.2| 10778| 1051| 980| 3.13| 2.92
0.4| 10516| 1077| 1007| 3.21| 3.00
0.6| 10323| 1106| 1027| 3.30| 3.06
0.8| 10162| 1132| 1061| 3.37| 3.16
1| 10002| 1152| 1097| 3.44| 3.27
1.2| 9806| 1179| 1132| 3.52| 3.38
T5| 0.2| 10958| 1088| 1013| 3.38| 3.15
0.4| 10701| 1112| 1038| 3.45| 3.22
0.6| 10521| 1140| 1058| 3.54| 3.29
0.8| 10359| 1164| 1089| 3.61| 3.38
1| 10187| 1186| 1120| 3.68| 3.48
1.2| 10000| 1211| 1152| 3.76| 3.58
T6| 0.2| 9218| 832| 787| 1.79| 1.70
0.4| 8927| 869| 828| 1.87| 1.79
0.6| –| –| –| –| –
0.8| –| –| –| –| –
1| –| –| –| –| –
1.2| –| –| –| –| –
T7| 0.2| 9642| 879| 828| 2.07| 1.95
0.4| 9358| 913| 866| 2.15| 2.04
0.6| 9096| 949| 893| 2.23| 2.10
0.8| 8916| 983| 938| 2.31| 2.21
1| 8754| 1008| 991| 2.37| 2.33
1.2| –| –| –| –| –
T8| 0.2| 9934| 1083| 971| 2.68| 2.40
0.4| 9735| 1110| 999| 2.75| 2.47
0.6| 9559| 1138| 1027| 2.82| 2.54
0.8| 9379| 1162| 1056| 2.88| 2.61
1| 9201| 1187| 1086| 2.94| 2.69
1.2| 9006| 1212| 1120| 3.00| 2.77
T9| 0.2| 10398| 1123| 1008| 3.04| 2.73
0.4| 10203| 1149| 1034| 3.11| 2.80
0.6| 10034| 1176| 1060| 3.18| 2.87
0.8| 9863| 1199| 1087| 3.24| 2.94
1| 9698| 1222| 1116| 3.30| 3.02
1.2| 9516| 1245| 1147| 3.37| 3.10
T10| 0.2| 10958| 1088| 1013| 3.38| 3.15
0.4| 10701| 1112| 1038| 3.45| 3.22
0.6| 10521| 1140| 1058| 3.54| 3.29
0.8| 10359| 1164| 1089| 3.61| 3.38
1| 10187| 1186| 1120| 3.68| 3.48
1.2| 10000| 1211| 1152| 3.76| 3.58
NOTES:
High static airflow requires installation of high static kit.
Air flow tables represent dry coil with filters installed; SCFM correction
factor for wet coil is 4%.
DIRECT DRIVE – HIGH STATIC
DFC1803D High Static
Speed Tap | Static | Airflow | RPM 1 | RPM 2 | BHP 1 | BHP 2 |
---|---|---|---|---|---|---|
T1 | 0.2 | 6622 | 626 | 626 | 0.25 | 0.25 |
0.4 | 6195 | 666 | 667 | 0.27 | 0.27 | |
0.6 | 5791 | 709 | 706 | 0.28 | 0.28 | |
0.8 | 5392 | 749 | 748 | 0.30 | 0.30 | |
1 | 4960 | 789 | 792 | 0.31 | 0.32 | |
1.2 | 4503 | 836 | 836 | 0.33 | 0.33 | |
1.4 | 3515 | 956 | 911 | 0.38 | 0.36 | |
1.6 | 2887 | 998 | 978 | 0.40 | 0.39 | |
1.8 | 2360 | 1047 | 1020 | 0.42 | 0.41 | |
2 | 1807 | 1082 | 1067 | 0.43 | 0.43 | |
2.2 | 1305 | 1109 | 1103 | 0.44 | 0.44 | |
T2 | 0.2 | 6622 | 626 | 626 | 0.25 | 0.25 |
0.4 | 6195 | 666 | 667 | 0.27 | 0.27 | |
0.6 | 5791 | 709 | 706 | 0.28 | 0.28 | |
0.8 | 5392 | 749 | 748 | 0.30 | 0.30 | |
1 | 4960 | 789 | 792 | 0.31 | 0.32 | |
1.2 | 4503 | 836 | 836 | 0.33 | 0.33 | |
1.4 | 3515 | 956 | 911 | 0.38 | 0.36 | |
1.6 | 2887 | 998 | 978 | 0.40 | 0.39 | |
1.8 | 2360 | 1047 | 1020 | 0.42 | 0.41 | |
2 | 1807 | 1082 | 1067 | 0.43 | 0.43 | |
2.2 | 1305 | 1109 | 1103 | 0.44 | 0.44 | |
T3 | 0.2 | 8201 | 738 | 736 | 0.84 | 0.84 |
0.4 | 7841 | 776 | 774 | 0.89 | 0.88 | |
0.6 | 7516 | 814 | 811 | 0.93 | 0.93 | |
0.8 | 7185 | 852 | 849 | 0.97 | 0.97 | |
1 | 6864 | 887 | 885 | 1.01 | 1.01 | |
1.2 | 6517 | 926 | 923 | 1.06 | 1.05 | |
1.4 | 5970 | 991 | 973 | 1.13 | 1.11 | |
1.6 | 5502 | 1033 | 1020 | 1.18 | 1.16 | |
1.8 | 5050 | 1082 | 1059 | 1.24 | 1.21 | |
2 | 4609 | 1122 | 1101 | 1.28 | 1.26 | |
2.2 | 4136 | 1164 | 1141 | 1.33 | 1.30 | |
T4 | 0.2 | 8778 | 780 | 776 | 1.12 | 1.12 |
0.4 | 8441 | 816 | 813 | 1.17 | 1.17 | |
0.6 | 8141 | 852 | 850 | 1.23 | 1.22 | |
0.8 | 7832 | 889 | 887 | 1.28 | 1.28 | |
1 | 7543 | 924 | 921 | 1.33 | 1.32 | |
1.2 | 7231 | 960 | 957 | 1.38 | 1.38 | |
1.4 | 6814 | 1009 | 998 | 1.45 | 1.44 | |
1.6 | 6401 | 1051 | 1039 | 1.51 | 1.50 | |
1.8 | 5980 | 1098 | 1077 | 1.58 | 1.55 | |
2 | 5580 | 1139 | 1117 | 1.64 | 1.61 | |
2.2 | 5126 | 1184 | 1157 | 1.70 | 1.67 | |
T5 | 0.2 | 9286 | 816 | 811 | 1.40 | 1.39 |
0.4 | 8969 | 851 | 848 | 1.46 | 1.46 | |
0.6 | 8688 | 886 | 884 | 1.52 | 1.52 | |
0.8 | 8398 | 923 | 920 | 1.58 | 1.58 | |
1 | 8132 | 956 | 952 | 1.64 | 1.63 | |
1.2 | 7849 | 990 | 987 | 1.70 | 1.69 | |
1.4 | 7530 | 1028 | 1022 | 1.76 | 1.75 | |
1.6 | 7162 | 1068 | 1059 | 1.83 | 1.82 | |
1.8 | 6771 | 1114 | 1096 | 1.91 | 1.88 | |
2 | 6407 | 1155 | 1134 | 1.98 | 1.95 | |
2.2 | 5974 | 1201 | 1173 | 2.06 | 2.01 | |
Speed Tap | Static | Airflow | RPM 1 | RPM 2 | BHP 1 | BHP 2 |
--- | --- | --- | --- | --- | --- | --- |
T6 | 0.2 | 8163 | 925 | 854 | 1.33 | 1.23 |
0.4 | 7902 | 953 | 880 | 1.37 | 1.27 | |
0.6 | 7642 | 979 | 913 | 1.41 | 1.31 | |
0.8 | 7399 | 1006 | 944 | 1.45 | 1.36 | |
1 | 7146 | 1033 | 976 | 1.49 | 1.41 | |
1.2 | 6893 | 1061 | 1010 | 1.53 | 1.45 | |
1.4 | 6626 | 1090 | 1047 | 1.57 | 1.51 | |
1.6 | 6349 | 1122 | 1082 | 1.61 | 1.56 | |
1.8 | 6035 | 1154 | 1118 | 1.66 | 1.61 | |
2 | 5765 | 1184 | 1148 | 1.70 | 1.65 | |
2.2 | 5401 | 1215 | 1189 | 1.75 | 1.71 | |
T7 | 0.2 | 9129 | 805 | 800 | 2.63 | 1.63 |
0.4 | 8806 | 840 | 837 | 2.75 | 1.71 | |
0.6 | 8519 | 876 | 873 | 2.86 | 1.78 | |
0.8 | 8224 | 912 | 910 | 2.98 | 1.86 | |
1 | 7951 | 946 | 942 | 3.09 | 1.92 | |
1.2 | 7659 | 981 | 977 | 3.21 | 1.99 | |
1.4 | 7312 | 1022 | 1015 | 3.34 | 2.07 | |
1.6 | 6930 | 1063 | 1053 | 3.47 | 2.15 | |
1.8 | 6530 | 1109 | 1090 | 3.62 | 2.22 | |
2 | 6154 | 1150 | 1128 | 3.76 | 2.30 | |
2.2 | 5715 | 1196 | 1168 | 3.91 | 2.38 | |
T8 | 0.2 | 9286 | 816 | 811 | 2.67 | 1.65 |
0.4 | 8969 | 851 | 848 | 2.78 | 1.73 | |
0.6 | 8688 | 886 | 884 | 2.90 | 1.80 | |
0.8 | 8398 | 923 | 920 | 3.02 | 1.88 | |
1 | 8132 | 956 | 952 | 3.12 | 1.94 | |
1.2 | 7849 | 990 | 987 | 3.24 | 2.01 | |
1.4 | 7530 | 1028 | 1022 | 3.36 | 2.08 | |
1.6 | 7162 | 1068 | 1059 | 3.49 | 2.16 | |
1.8 | 6771 | 1114 | 1096 | 3.64 | 2.23 | |
2 | 6407 | 1155 | 1134 | 3.78 | 2.31 | |
2.2 | 5974 | 1201 | 1173 | 3.93 | 2.39 | |
T9 | 0.2 | 9405 | 825 | 820 | 2.70 | 1.67 |
0.4 | 9091 | 860 | 856 | 2.81 | 1.75 | |
0.6 | 8815 | 894 | 892 | 2.92 | 1.82 | |
0.8 | 8529 | 930 | 928 | 3.04 | 1.89 | |
1 | 8268 | 963 | 960 | 3.15 | 1.96 | |
1.2 | 7991 | 997 | 994 | 3.26 | 2.03 | |
1.4 | 7692 | 1033 | 1028 | 3.38 | 2.10 | |
1.6 | 7334 | 1073 | 1064 | 3.51 | 2.17 | |
1.8 | 6951 | 1118 | 1100 | 3.65 | 2.24 | |
2 | 6595 | 1159 | 1138 | 3.79 | 2.32 | |
2.2 | 6168 | 1205 | 1177 | 3.94 | 2.40 | |
T10 | 0.2 | 9495 | 831 | 826 | 2.72 | 1.68 |
0.4 | 9185 | 866 | 862 | 2.83 | 1.76 | |
0.6 | 8911 | 901 | 898 | 2.94 | 1.83 | |
0.8 | 8629 | 936 | 934 | 3.06 | 1.90 | |
1 | 8371 | 969 | 965 | 3.17 | 1.97 | |
1.2 | 8098 | 1003 | 999 | 3.28 | 2.04 | |
1.4 | 7814 | 1037 | 1033 | 3.39 | 2.11 | |
1.6 | 7464 | 1076 | 1068 | 3.52 | 2.18 | |
1.8 | 7086 | 1121 | 1104 | 3.66 | 2.25 | |
2 | 6737 | 1162 | 1141 | 3.80 | 2.33 | |
2.2 | 6314 | 1208 | 1180 | 3.95 | 2.41 |
DFC2403D High Static
Speed Tap | Static | Airflow | RPM 1 | RPM 2 | BHP 1 | BHP 2 |
---|---|---|---|---|---|---|
T1 | 0.2 | 6412 | 631 | 616 | 0.71 | 0.69 |
0.4 | 6081 | 683 | 673 | 0.77 | 0.76 | |
0.6 | 5697 | 729 | 745 | 0.82 | 0.84 | |
0.8 | 5360 | 778 | 796 | 0.88 | 0.90 | |
1 | 4895 | 846 | 859 | 0.95 | 0.97 | |
1.2 | 4519 | 884 | 900 | 1.00 | 1.01 | |
1.4 | 4139 | 927 | 948 | 1.04 | 1.07 | |
1.6 | 3635 | 987 | 981 | 1.11 | 1.10 | |
1.8 | 3278 | 1034 | 1012 | 1.16 | 1.14 | |
2 | 2968 | 1070 | 1043 | 1.21 | 1.18 | |
2.2 | 2662 | 1098 | 1083 | 1.24 | 1.22 | |
T2 | 0.2 | 6797 | 651 | 632 | 0.81 | 0.79 |
0.4 | 6471 | 700 | 688 | 0.88 | 0.86 | |
0.6 | 6099 | 746 | 753 | 0.93 | 0.94 | |
0.8 | 5784 | 793 | 804 | 0.99 | 1.00 | |
1 | 5368 | 855 | 868 | 1.07 | 1.08 | |
1.2 | 5006 | 893 | 911 | 1.12 | 1.14 | |
1.4 | 4638 | 934 | 962 | 1.17 | 1.20 | |
1.6 | 4160 | 992 | 997 | 1.24 | 1.25 | |
1.8 | 3810 | 1039 | 1029 | 1.30 | 1.29 | |
2 | 3510 | 1076 | 1060 | 1.34 | 1.33 | |
2.2 | 3192 | 1106 | 1099 | 1.38 | 1.37 | |
T3 | 0.2 | 9468 | 859 | 811 | 1.95 | 1.84 |
0.4 | 9181 | 894 | 850 | 2.03 | 1.93 | |
0.6 | 8911 | 930 | 878 | 2.11 | 1.99 | |
0.8 | 8724 | 966 | 925 | 2.19 | 2.10 | |
1 | 8554 | 992 | 980 | 2.25 | 2.22 | |
1.2 | 8298 | 1025 | 1027 | 2.33 | 2.33 | |
1.4 | 8015 | 1054 | 1082 | 2.39 | 2.45 | |
1.6 | 7718 | 1094 | 1128 | 2.48 | 2.56 | |
1.8 | 7441 | 1133 | 1158 | 2.57 | 2.63 | |
2 | 7210 | 1171 | 1189 | 2.66 | 2.70 | |
2.2 | 6884 | 1209 | 1218 | 2.74 | 2.76 | |
T4 | 0.2 | 9881 | 909 | 854 | 2.24 | 2.11 |
0.4 | 9602 | 941 | 890 | 2.32 | 2.20 | |
0.6 | 9353 | 976 | 915 | 2.41 | 2.26 | |
0.8 | 9179 | 1008 | 959 | 2.49 | 2.37 | |
1 | 9025 | 1032 | 1009 | 2.55 | 2.49 | |
1.2 | 8787 | 1063 | 1055 | 2.62 | 2.60 | |
1.4 | 8519 | 1090 | 1107 | 2.69 | 2.73 | |
1.6 | 8248 | 1127 | 1151 | 2.78 | 2.84 | |
1.8 | 7989 | 1163 | 1181 | 2.87 | 2.92 | |
2 | 7770 | 1199 | 1211 | 2.96 | 2.99 | |
2.2 | 7460 | 1237 | 1239 | 3.05 | 3.06 | |
T5 | 0.2 | 10268 | 963 | 902 | 2.58 | 2.41 |
0.4 | 9996 | 993 | 935 | 2.66 | 2.50 | |
0.6 | 9769 | 1025 | 957 | 2.74 | 2.56 | |
0.8 | 9604 | 1055 | 997 | 2.82 | 2.67 | |
1 | 9456 | 1077 | 1042 | 2.88 | 2.79 | |
1.2 | 9235 | 1106 | 1084 | 2.96 | 2.90 | |
1.4 | 8983 | 1132 | 1133 | 3.03 | 3.03 | |
1.6 | 8736 | 1164 | 1175 | 3.11 | 3.14 | |
1.8 | 8496 | 1197 | 1204 | 3.20 | 3.22 | |
2 | 8288 | 1232 | 1233 | 3.29 | 3.30 | |
2.2 | 8001 | 1267 | 1259 | 3.39 | 3.37 |
DFC3003D High Static
Speed Tap | Static | Airflow | RPM 1 | RPM 2 | BHP 1 | BHP 2 |
---|---|---|---|---|---|---|
T1 | 0.2 | 7629 | 701 | 674 | 1.07 | 1.03 |
0.4 | 7314 | 746 | 725 | 1.14 | 1.11 | |
0.6 | 6969 | 789 | 777 | 1.21 | 1.19 | |
0.8 | 6701 | 833 | 829 | 1.28 | 1.27 | |
1 | 6380 | 882 | 892 | 1.35 | 1.37 | |
1.2 | 6049 | 919 | 939 | 1.41 | 1.44 | |
1.4 | 5706 | 956 | 994 | 1.46 | 1.52 | |
1.6 | 5285 | 1010 | 1035 | 1.55 | 1.58 | |
1.8 | 4952 | 1055 | 1066 | 1.62 | 1.63 | |
2 | 4673 | 1094 | 1098 | 1.68 | 1.68 | |
2.2 | 4339 | 1128 | 1134 | 1.73 | 1.74 | |
T2 | 0.2 | 7900 | 719 | 690 | 1.17 | 1.12 |
0.4 | 7588 | 763 | 739 | 1.24 | 1.20 | |
0.6 | 7253 | 805 | 787 | 1.31 | 1.28 | |
0.8 | 6999 | 848 | 839 | 1.38 | 1.37 | |
1 | 6706 | 893 | 902 | 1.45 | 1.47 | |
1.2 | 6386 | 929 | 949 | 1.51 | 1.55 | |
1.4 | 6051 | 966 | 1005 | 1.57 | 1.64 | |
1.6 | 5649 | 1018 | 1048 | 1.66 | 1.71 | |
1.8 | 5322 | 1063 | 1079 | 1.73 | 1.76 | |
2 | 5050 | 1102 | 1111 | 1.79 | 1.81 | |
2.2 | 4712 | 1137 | 1146 | 1.85 | 1.87 | |
T3 | 0.2 | 9468 | 859 | 811 | 1.95 | 1.84 |
0.4 | 9181 | 894 | 850 | 2.03 | 1.93 | |
0.6 | 8911 | 930 | 878 | 2.11 | 1.99 | |
0.8 | 8724 | 966 | 925 | 2.19 | 2.10 | |
1 | 8554 | 992 | 980 | 2.25 | 2.22 | |
1.2 | 8298 | 1025 | 1027 | 2.33 | 2.33 | |
1.4 | 8015 | 1054 | 1082 | 2.39 | 2.45 | |
1.6 | 7718 | 1094 | 1128 | 2.48 | 2.56 | |
1.8 | 7441 | 1133 | 1158 | 2.57 | 2.63 | |
2 | 7210 | 1171 | 1189 | 2.66 | 2.70 | |
2.2 | 6884 | 1209 | 1218 | 2.74 | 2.76 | |
T4 | 0.2 | 9881 | 909 | 854 | 2.24 | 2.11 |
0.4 | 9602 | 941 | 890 | 2.32 | 2.20 | |
0.6 | 9353 | 976 | 915 | 2.41 | 2.26 | |
0.8 | 9179 | 1008 | 959 | 2.49 | 2.37 | |
1 | 9025 | 1032 | 1009 | 2.55 | 2.49 | |
1.2 | 8787 | 1063 | 1055 | 2.62 | 2.60 | |
1.4 | 8519 | 1090 | 1107 | 2.69 | 2.73 | |
1.6 | 8248 | 1127 | 1151 | 2.78 | 2.84 | |
1.8 | 7989 | 1163 | 1181 | 2.87 | 2.92 | |
2 | 7770 | 1199 | 1211 | 2.96 | 2.99 | |
2.2 | 7460 | 1237 | 1239 | 3.05 | 3.06 | |
T5 | 0.2 | 10259 | 962 | 901 | 2.57 | 2.41 |
0.4 | 9987 | 992 | 934 | 2.65 | 2.49 | |
0.6 | 9759 | 1024 | 956 | 2.73 | 2.55 | |
0.8 | 9594 | 1054 | 996 | 2.81 | 2.66 | |
1 | 9446 | 1075 | 1041 | 2.87 | 2.78 | |
1.2 | 9224 | 1105 | 1084 | 2.95 | 2.89 | |
1.4 | 8972 | 1131 | 1132 | 3.02 | 3.02 | |
1.6 | 8724 | 1163 | 1175 | 3.11 | 3.14 | |
1.8 | 8484 | 1196 | 1203 | 3.19 | 3.21 | |
2 | 8276 | 1231 | 1233 | 3.29 | 3.29 | |
2.2 | 7988 | 1267 | 1259 | 3.38 | 3.36 | |
Speed Tap | Static | Airflow | RPM 1 | RPM 2 | BHP 1 | BHP 2 |
--- | --- | --- | --- | --- | --- | --- |
T6 | 0.2 | 10268 | 963 | 902 | 2.58 | 2.41 |
0.4 | 9996 | 993 | 935 | 2.66 | 2.50 | |
0.6 | 9769 | 1025 | 957 | 2.74 | 2.56 | |
0.8 | 9604 | 1055 | 997 | 2.82 | 2.67 | |
1 | 9456 | 1077 | 1042 | 2.88 | 2.79 | |
1.2 | 9235 | 1106 | 1084 | 2.96 | 2.90 | |
1.4 | 8983 | 1132 | 1133 | 3.03 | 3.03 | |
1.6 | 8736 | 1164 | 1175 | 3.11 | 3.14 | |
1.8 | 8496 | 1197 | 1204 | 3.20 | 3.22 | |
2 | 8288 | 1232 | 1233 | 3.29 | 3.30 | |
2.2 | 8001 | 1267 | 1259 | 3.39 | 3.37 | |
T7 | 0.2 | 10626 | 1022 | 955 | 2.95 | 2.75 |
0.4 | 10361 | 1049 | 984 | 3.03 | 2.84 | |
0.6 | 10156 | 1080 | 1004 | 3.11 | 2.90 | |
0.8 | 9995 | 1107 | 1040 | 3.19 | 3.00 | |
1 | 9842 | 1127 | 1079 | 3.25 | 3.11 | |
1.2 | 9638 | 1155 | 1117 | 3.33 | 3.22 | |
1.4 | 9402 | 1179 | 1160 | 3.40 | 3.35 | |
1.6 | 9176 | 1207 | 1199 | 3.48 | 3.46 | |
1.8 | 8958 | 1236 | 1227 | 3.57 | 3.54 | |
2 | 8760 | 1269 | 1255 | 3.66 | 3.62 | |
2.2 | 8502 | 1302 | 1280 | 3.76 | 3.69 | |
T8 | 0.2 | 10979 | 1092 | 1017 | 3.41 | 3.17 |
0.4 | 10723 | 1116 | 1042 | 3.48 | 3.25 | |
0.6 | 10544 | 1144 | 1062 | 3.57 | 3.31 | |
0.8 | 10382 | 1168 | 1093 | 3.65 | 3.41 | |
1 | 10209 | 1190 | 1123 | 3.71 | 3.51 | |
1.2 | 10023 | 1216 | 1155 | 3.79 | 3.60 | |
1.4 | 9804 | 1237 | 1191 | 3.86 | 3.72 | |
1.6 | 9598 | 1261 | 1225 | 3.93 | 3.82 | |
1.8 | 9406 | 1285 | 1252 | 4.01 | 3.91 | |
2 | 9218 | 1314 | 1278 | 4.10 | 3.99 | |
2.2 | 9000 | 1344 | 1301 | 4.19 | 4.06 | |
T9 | 0.2 | 11348 | 1185 | 1101 | 4.05 | 3.76 |
0.4 | 11101 | 1206 | 1120 | 4.11 | 3.82 | |
0.6 | 10956 | 1230 | 1142 | 4.20 | 3.90 | |
0.8 | 10785 | 1250 | 1165 | 4.27 | 3.97 | |
1 | 10567 | 1275 | 1183 | 4.35 | 4.04 | |
1.2 | 10402 | 1298 | 1205 | 4.43 | 4.11 | |
1.4 | 10203 | 1317 | 1230 | 4.49 | 4.20 | |
1.6 | 10015 | 1335 | 1257 | 4.56 | 4.29 | |
1.8 | 9858 | 1353 | 1281 | 4.62 | 4.37 | |
2 | 9682 | 1376 | 1305 | 4.70 | 4.45 | |
2.2 | 9524 | 1400 | 1326 | 4.78 | 4.52 | |
T10 | 0.2 | 11679 | 1301 | 1205 | 4.88 | 4.52 |
0.4 | 11444 | 1317 | 1219 | 4.94 | 4.57 | |
0.6 | 11337 | 1338 | 1246 | 5.02 | 4.67 | |
0.8 | 11145 | 1353 | 1257 | 5.07 | 4.71 | |
1 | 10847 | 1386 | 1260 | 5.20 | 4.72 | |
1.2 | 10703 | 1405 | 1267 | 5.27 | 4.75 | |
1.4 | 10526 | 1421 | 1277 | 5.33 | 4.79 | |
1.6 | 10353 | 1432 | 1291 | 5.37 | 4.84 | |
1.8 | 10238 | 1441 | 1313 | 5.40 | 4.93 | |
2 | 10074 | 1457 | 1333 | 5.47 | 5.00 | |
2.2 | 10002 | 1473 | 1353 | 5.52 | 5.07 |
NOTES:
High static airflow requires installation of high static kit.
Air flow tables represent dry coil with filters installed; SCFM correction
factor for wet coil is 4%.
APPENDIX A BLOWER PERFORMANCE DATA
MODELS: DFG1803WL, DFG1804WL, DFG1807WL STANDARD STATIC TO 3.5HP (0.2 ~1.2
ESP)MODELS: DFG1803WL, DFG1804WL, DFG1807WL
HIGH STATIC TO 5HP (0.8 ~2.2 ESP)MODELS: DFG1803DM, DFG1803DH,
DFG1804DM, DFG1804DH, DFG1807DM, DFG1807DH
STANDARD STATIC TO 3.5HP (0.2 ~1.2 ESP)MODELS: DFG1803WM,
DFG1803WH, DFG1804WM, DFG1804WH, DFG1807WM, DFG1807WH
HIGH STATIC TO 5HP (0.8 ~2.2 ESP)MODELS: DFC1803D, DFC1804D,
DFC1807D
STANDARD STATIC TO 3.5HP (0.2 ~1.2 ESP)MODELS: DFC1803W,
DFC1804W, DFC1807W
HIGH STATIC TO 5HP (0.8 ~2.2 ESP)MODELS: DFG2403WL, DFG2404WL,
DFG2407WL
STANDARD STATIC TO 3.5HP (0.2 ~1.2 ESP)MODELS: DFG2403WL,
DFG2404WL, DFG2407WL
HIGH STATIC TO 5HP (0.8 ~2.2 ESP)MODELS: DFG2403DM, DFG2403DH,
DFG2404DM, DFG2404DH, DFG2407DM, DFG2407DH
STANDARD STATIC TO 3.5HP (0.2 ~1.2 ESP)MODELS: DFG2403WM,
DFG2403WH, DFG2404WM, DFG2404WH, DFG2407WM, DFG2407WH
HIGH STATIC TO 5HP (0.8 ~2.2 ESP)MODELS: DFC2403D, DFC2404D,
DFC2407D
STANDARD STATIC TO 3.5HP (0.2 ~1.2 ESP)MODELS: DFC2403W,
DFC2404W, DFC2407W
HIGH STATIC TO 5HP (0.8 ~2.2 ESP) APPENDIX A ECONOMIZER
PRESSURE DROP
Airflow Pressure Drop of Downflow Economizer for 15 to 25 Ton Rooftop Units (100% Return Air)
SCFM| 4500| 5000| 5500| 6000| 6500| 7000| 7500| 8000| 8500| 9000| 9500| 10000
(In WG)| 0.15| 0.18| 0.22| 0.27| 0.32| 0.37| 0.42| 0.48| 0.55| 0.61| 0.69|
0.76
APPENDIX B ELECTRICAL DATA
APPENDIX C UNIT DIMENSIONS
Model | A | B | C | D |
---|---|---|---|---|
15 Ton | 133 – 7/8” | 88 – 1/2” | 51 – 11/16” | 5 – 5/32” |
20 Ton
25 Ton| 133 – 7/8”| 88 – 1/2”| 51| 5 – 5/32”
NOTE: 15 ton models
have 3 fans.
20 ton models have 4 fans
25 ton models have 5 fans
WIRING DIAGRAMS
NOTES
-
REPLACEMENT WIRE MUST BE SAME SIZE AND TYPE OF INSULATION AS ORIGINAL (AT LEAST 105° C). USE COPPER CONDUCTORS ONLY.
USE N.E.C. CLASS 2 WIRE FOR ALL LOW VOLTAGE FIELD CONNECTIONS.IF OPTIONAL ECONOMIZER IS INSTALLED REMOVE ECON PLM JUMPER AND PLUG IN NEW HARNESS FROM ECONOMIZER KIT. -
IF OPTIONAL ELECTRIC HEAT IS INSTALLED PLUG IN NEW HARNESS FROM ELECTRIC HEATER KIT.
-
IF OPTIONAL OEM SAFETY EQUIPMENT SUCH AS PHASE MONITOR, FLOAT SWITCH OR SMOKE DETECTOR ARE INSTALLED, UNPLUG JUMPER PLUG AND PLUG IN SAFETY DEVICE.
-
A. IF MULTIPLE SAFETIES ARE INSTALLED, PLUG IN THE ADDITIONAL DEVICES IN SERIES. PLUG IN JUMPER PLUG AT THE LAST SAFETY DEVICE INSTALLED.
B. IF A THIRD PARTY SAFETY DEVICE IS FIELD INSTALLED, CUT WIRE ON THE JUMPER PLUG AND WIRE IT IN SERIES WITH THE SAFETY CIRCUIT. -
FOR HIGHER TORQUE, “YL” AND/OR “WH” CAN BE MOVED TO T2 ON TB1. SEE IO MANUAL FOR ADDITIONAL INFORMATION.
-
FOR HIGHER TORQUE, “PU” AND/OR “BR” CAN BE MOVED TO T4 – T5 ON TB1. SEE IO MANUAL FOR ADDITIONAL INFORMATION.
-
REMOVE YELLOW AND PURPLE JUMPER WIRES IF OPTIONAL FREEZESTATS ARE INSTALLED.
COMPONENT LEGEND
BC | BLOWER CONTACTOR |
---|---|
BM | BLOWER MOTOR |
BR | BLOWER RELAY |
CB | CIRCUIT BREAKER |
CC | COMPRESSOR CONTACTOR |
CCR | COMPRESSOR CONTACTOR RELAY |
CM | CONDENSER MOTOR |
ECON | ECONOMIZER |
EHK | ELECTRIC HEATER KIT |
ES | EMERGENCY SHUTDOWN |
FPS | FREEZE PROTECTION SWITCH |
GND | EQUIPMENT GROUND |
HPS | HIGH PRESSURE SWITCH |
LPS | LOW PRESSURE SWITCH |
PLF | FEMALE PLUG/CONNECTOR |
PLM | MALE PLUG/CONNECTOR |
TB | TERMINAL BLOCK |
TR | TRANSFORMER |
WIRE CODE
BK | BLACK |
---|---|
BL | BLUE |
BL/PK | BLUE WITH PINK STRIPE |
BR | BROWN |
GR | GREEN |
GY | GRAY |
OR | ORANGE |
PK | PINK |
PU | PURPLE |
RD | RED |
TN | TAN |
WH | WHITE |
YL | YELLOW |
YL/PK | YELLOW WITH PINK STRIPE |
CONTROLS WIRING DIAGRAM
DFC(180-240)**
LINE VOLTAGE:
208-230/460/575V/3PH/60HZ NOTES
-
REPLACEMENT WIRE MUST BE SAME SIZE AND TYPE OF INSULATION AS ORIGINAL (AT LEAST 105° C). USE COPPER CONDUCTORS ONLY.
USE N.E.C. CLASS 2 WIRE FOR ALL LOW VOLTAGE FIELD CONNECTIONS.
TR1 PRIMARY (HIGH VOLTAGE) CONNECTIONS: RED WIRES CONNECTED TO 240/460/575V TAP AT THE FACTORY AND BLACK WIRES TO -
COM TERMINAL. FOR 208V SUPPLY POWER, MOVE RED WIRES FROM 240V TAP TO THE 208V TAP.
-
SEE CONTROL DIAGRAM FOR CONTROL TRANSFORMER LOW VOLTAGE CONNECTIONS
-
OPTIONAL FACTORY INSTALLED EQUIPMENT
COMPONENT LEGEND
BC | BLOWER CONTACTOR |
---|---|
BM | BLOWER MOTOR |
CB | CIRCUIT BREAKER |
CC | COMPRESSOR CONTACTOR |
CCH | CRANKCASE HEATER |
CCX | COMPRESSOR CONTACTOR AUXILIARY SWITCH |
CF HVTB | CONDENSER FAN HIGH VOLTAGE TERMINAL BLOCK |
CM | CONDENSER MOTOR |
COMP | COMPRESSOR |
F | FUSE |
FB | FUSE BLOCK |
FC | FAN CAPACITOR |
GND | EQUIPMENT GROUND |
PB | POWER DISTRIBUTION BLOCK |
PLF | FEMALE PLUG/CONNECTOR |
PLM | MALE PLUG/CONNECTOR |
TR | TRANSFORMER |
WIRE CODE
BK | BLACK |
---|---|
BL | BLUE |
BL/PK | BLUE WITH PINK STRIPE |
BR | BROWN |
GR | GREEN |
GY | GRAY |
OR | ORANGE |
PK | PINK |
PU | PURPLE |
RD | RED |
TN | TAN |
WH | WHITE |
YL | YELLOW |
YL/PK | YELLOW WITH PINK STRIPE |
NOTES
-
REPLACEMENT WIRE MUST BE SAME SIZE AND TYPE OF INSULATION AS ORIGINAL (AT LEAST 105° C). USE COPPER CONDUCTORS ONLY.
USE N.E.C. CLASS 2 WIRE FOR ALL LOW VOLTAGE FIELD CONNECTIONS. -
IF OPTIONAL ECONOMIZER IS INSTALLED REMOVE ECON PLM JUMPER AND PLUG IN NEW HARNESS FROM ECONOMIZER KIT.
-
IF OPTIONAL ELECTRIC HEAT IS INSTALLED PLUG IN NEW HARNESS FROM ELECTRIC HEATER KIT.
-
A. IF OPTIONAL OEM SAFETY EQUIPMENT SUCH AS PHASE MONITOR, FLOAT SWITCH OR SMOKE DETECTOR ARE INSTALLED, UNPLUG JUMPER PLUG AND PLUG IN SAFETY DEVICE.
IF MULTIPLE SAFETIES ARE INSTALLED, PLUG IN THE ADDITIONAL DEVICES IN SERIES. PLUG IN JUMPER PLUG AT THE LAST SAFETY DEVICE INSTALLED.
B. IF A THIRD PARTY SAFETY DEVICE IS FIELD INSTALLED, CUT WIRE ON THE JUMPER PLUG AND WIRE IT IN SERIES WITH THE SAFETY CIRCUIT. -
FOR HIGHER TORQUE, “YL” AND/OR “WH” CAN BE MOVED TO T2 ON TB1. SEE IO MANUAL FOR ADDITIONAL INFORMATION.
-
FOR HIGHER TORQUE, “PU” AND/OR “BR” CAN BE MOVED TO T4 – T5 ON TB1. SEE IO MANUAL FOR ADDITIONAL INFORMATION.
-
REMOVE YELLOW AND PURPLE JUMPER WIRES IF OPTIONAL FREEZESTATS ARE INSTALLED.
COMPONENT LEGEND
BC | BLOWER CONTACTOR |
---|---|
BM | BLOWER MOTOR |
BR | BLOWER RELAY |
CB | CIRCUIT BREAKER |
CC | COMPRESSOR CONTACTOR |
CCR | COMPRESSOR CONTACTOR RELAY |
CM | CONDENSER MOTOR |
ECON | ECONOMIZER |
EHK | ELECTRIC HEATER KIT |
ES | EMERGENCY SHUTDOWN |
FPS | FREEZE PROTECTION SWITCH |
GND | EQUIPMENT GROUND |
HPS | HIGH PRESSURE SWITCH |
LPS | LOW PRESSURE SWITCH |
PLF | FEMALE PLUG/CONNECTOR |
PLM | MALE PLUG/CONNECTOR |
TB | TERMINAL BLOCK |
TR | TRANSFORMER |
WIRE CODE
BK | BLACK |
---|---|
BL | BLUE |
BL/PK | BLUE WITH PINK STRIPE |
BR | BROWN |
GR | GREEN |
GY | GRAY |
OR | ORANGE |
PK | PINK |
PU | PURPLE |
RD | RED |
TN | TAN |
WH | WHITE |
YL | YELLOW |
YL/PK | YELLOW WITH PINK STRIPE |
NOTES
-
REPLACEMENT WIRE MUST BE SAME SIZE AND TYPE OF INSULATION AS ORIGINAL (AT LEAST 105° C). USE COPPER CONDUCTORS ONLY.
USE N.E.C. CLASS 2 WIRE FOR ALL LOW VOLTAGE FIELD CONNECTIONS. -
TR1 PRIMARY (HIGH VOLTAGE) CONNECTIONS: RED WIRES CONNECTED TO 240/460/575V TAP AT THE FACTORY AND BLACK WIRES TO
COM TERMINAL. FOR 208V SUPPLY POWER, MOVE RED WIRES FROM 240V TAP TO THE 208V TAP ON BOTH TRANSFORMERS. -
SEE CONTROL DIAGRAM FOR CONTROL TRANSFORMER LOW VOLTAGE CONNECTIONS
-
FUSE BLOCKS ARE OPTIONAL
COMPONENT LEGEND
BC | BLOWER CONTACTOR |
---|---|
BM | BLOWER MOTOR |
CB | CIRCUIT BREAKER |
CC | COMPRESSOR CONTACTOR |
CCAS | COMPRESSOR CONTACTOR AUXILIARY SWITCH |
CCH | CRANKCASE HEATER |
CCX | COMPRESSOR CONTACTOR AUXILIARY SWITCH |
CF HVTB | CONDENSER FAN HIGH VOLTAGE TERMINAL BLOCK |
CM | CONDENSER MOTOR |
CMC | CONDENSER MOTOR CONTACTOR |
COMP | COMPRESSOR |
F | FUSE |
FC | FAN CAPACITOR |
GND | EQUIPMENT GROUND |
LAK | LOW AMBIENT KIT |
PB | POWER DISTRIBUTION BLOCK |
PLF | FEMALE PLUG/CONNECTOR |
PLM | MALE PLUG/CONNECTOR |
RLY | RELAY |
TR | TRANSFORMER |
VM | VENT MOTOR |
VMC | VENT MOTOR CONTACTOR |
WIRE CODE
BK | BLACK |
---|---|
BL | BLUE |
BL/PK | BLUE WITH PINK STRIPE |
BR | BROWN |
GR | GREEN |
GY | GRAY |
OR | ORANGE |
PK | PINK |
PU | PURPLE |
RD | RED |
TN | TAN |
WH | WHITE |
YL | YELLOW |
YL/PK | YELLOW WITH PINK STRIPE |
NOTES
-
REPLACEMENT WIRE MUST BE SAME SIZE AND TYPE OF INSULATION AS ORIGINAL (AT LEAST 105° C). USE COPPER CONDUCTORS ONLY.
USE N.E.C. CLASS 2 WIRE FOR ALL LOW VOLTAGE FIELD CONNECTIONS. -
IF OPTIONAL ECONOMIZER IS INSTALLED REMOVE ECON PLM JUMPER AND PLUG IN NEW HARNESS FROM ECONOMIZER KIT.
-
IF OPTIONAL ELECTRIC HEAT IS INSTALLED PLUG IN NEW HARNESS FROM ELECTRIC HEATER KIT.
-
A. IF OPTIONAL OEM SAFETY EQUIPMENT SUCH AS PHASE MONITOR, FLOAT SWITCH OR SMOKE DETECTOR ARE INSTALLED, UNPLUG JUMPER PLUG AND PLUG IN SAFETY DEVICE.
IF MULTIPLE SAFETIES ARE INSTALLED, PLUG IN THE ADDITIONAL DEVICES IN SERIES. PLUG IN JUMPER PLUG AT THE LAST SAFETY DEVICE INSTALLED.
B. IF A THIRD PARTY SAFETY DEVICE IS FIELD INSTALLED, CUT WIRE ON THE JUMPER PLUG AND WIRE IT IN SERIES WITH THE SAFETY CIRCUIT. -
FOR HIGHER TORQUE, “YL” AND/OR “WH” CAN BE MOVED TO T2 ON TB1. SEE IO MANUAL FOR ADDITIONAL INFORMATION.
-
FOR HIGHER TORQUE, “PU” AND/OR “BR” CAN BE MOVED TO T4 – T5 ON TB1. SEE IO MANUAL FOR ADDITIONAL INFORMATION.
-
REMOVE YELLOW AND PURPLE JUMPER WIRES IF OPTIONAL FREEZESTATS ARE INSTALLED.
COMPONENT LEGEND
BC | BLOWER CONTACTOR |
---|---|
BM | BLOWER MOTOR |
BR | BLOWER RELAY |
CB | CIRCUIT BREAKER |
CC | COMPRESSOR CONTACTOR |
CCR | COMPRESSOR CONTACTOR RELAY |
CM | CONDENSER MOTOR |
CMC | CONDENSER MOTOR CONTACTOR |
ECON | ECONOMIZER |
EHK | ELECTRIC HEATER KIT |
ES | EMERGENCY SHUTDOWN |
FPS | FREEZE PROTECTION SWITCH |
GND | EQUIPMENT GROUND |
HPS | HIGH PRESSURE SWITCH |
LPS | LOW PRESSURE SWITCH |
PLF | FEMALE PLUG/CONNECTOR |
PLM | MALE PLUG/CONNECTOR |
TB | TERMINAL BLOCK |
TR | TRANSFORMER |
WIRE CODE
BK | BLACK |
---|---|
BL | BLUE |
BL/PK | BLUE WITH PINK STRIPE |
BR | BROWN |
GR | GREEN |
GY | GRAY |
OR | ORANGE |
PK | PINK |
PU | PURPLE |
RD | RED |
TN | TAN |
WH | WHITE |
YL | YELLOW |
YL/PK | YELLOW WITH PINK STRIPE |
NOTES
-
REPLACEMENT WIRE MUST BE SAME SIZE AND TYPE OF INSULATION AS ORIGINAL (AT LEAST 105° C). USE COPPER CONDUCTORS ONLY.
USE N.E.C. CLASS 2 WIRE FOR ALL LOW VOLTAGE FIELD CONNECTIONS. -
TR1 PRIMARY (HIGH VOLTAGE) CONNECTIONS: RED WIRES CONNECTED TO 240/460/575V TAP AT THE FACTORY AND BLACK WIRES TO
COM TERMINAL. FOR 208V SUPPLY POWER, MOVE RED WIRES FROM 240V TAP TO THE 208V TAP ON BOTH TRANSFORMERS. -
SEE CONTROL DIAGRAM FOR CONTROL TRANSFORMER LOW VOLTAGE CONNECTIONS
-
FUSE BLOCKS ARE OPTIONAL
COMPONENT LEGEND
BC | BLOWER CONTACTOR |
---|---|
BM | BLOWER MOTOR |
CB | CIRCUIT BREAKER |
CC | COMPRESSOR CONTACTOR |
CCAS | COMPRESSOR CONTACTOR AUXILIARY SWITCH |
CCH | CRANKCASE HEATER |
CCX | COMPRESSOR CONTACTOR AUXILIARY SWITCH |
CF HVTB | CONDENSER FAN HIGH VOLTAGE TERMINAL |
BLOCK
CM| CONDENSER MOTOR
CMC| CONDENSER MOTOR CONTACTOR
COMP| COMPRESSOR
F| FUSE
FC| FAN CAPACITOR
GND| EQUIPMENT GROUND
LAK| LOW AMBIENT KIT
PB| POWER DISTRIBUTION BLOCK
PLF| FEMALE PLUG/CONNECTOR
PLM| MALE PLUG/CONNECTOR
RLY| RELAY
TR| TRANSFORMER
VM| VENT MOTOR
VMC| VENT MOTOR CONTACTOR
WIRE CODE
BK | BLACK |
---|---|
BL | BLUE |
BL/PK | BLUE WITH PINK STRIPE |
BR | BROWN |
GR | GREEN |
GY | GRAY |
OR | ORANGE |
PK | PINK |
PU | PURPLE |
RD | RED |
TN | TAN |
WH | WHITE |
YL | YELLOW |
YL/PK | YELLOW WITH PINK STRIPE |
NOTES
-
REPLACEMENT WIRE MUST BE SAME SIZE AND TYPE OF INSULATION AS ORIGINAL (AT
LEAST 105° C). USE COPPER CONDUCTORS ONLY.
USE N.E.C. CLASS 2 WIRE FOR ALL LOW VOLTAGE FIELD CONNECTIONS. -
IF OPTIONAL ECONOMIZER IS INSTALLED, INSERT PLM PLUG PROVIDED BY THE ECONOMIZER KIT.
-
IF ELECTRIC HEAT IS INSTALLED, CONNECT EHK EXT PLF TO ACCESSORY HEAT PLUG IN HEAT COMPARTMENT
-
FIELD WIRE BACNET MS/TP TO J25. SEE USER IO MANUAL FOR ADDITIONAL INFORMATION.
-
A. IF OPTIONAL OEM SAFETY EQUIPMENT SUCH AS PHASE MONITOR, FLOAT SWITCH OR SMOKE DETECTOR ARE INSTALLED, UNPLUG JUMPER PLUG AND PLUG IN SAFETY DEVICE.
IF MULTIPLE SAFETIES ARE INSTALLED, PLUG IN THE ADDITIONAL DEVICES IN SERIES.
PLUG IN JUMPER PLUG AT THE LAST SAFETY DEVICE INSTALLED. -
IF A THIRD PARTY SAFETY DEVICE IS FIELD INSTALLED, CUT THE RED WIRE ON THE JUMPER PLUG AND WIRE A NORMALLY CLOSED DRY CONTACT IN SERIES WITH THE CUT WIRE
-
OPTIONAL FACTORY INSTALLED EQUIPMENT.
-
REMOVE YELLOW AND PURPLE JUMPER WIRES IF OPTIONAL FREEZESTATS ARE INSTALLED.
-
SEE POWER WIRING DIAGRAM FOR TRANSFORMER LINE VOLTAGE CONNECTIONS.
COMPONENT LEGEND
ALM | ALARM |
---|---|
BC | BLOWER CONTACTOR |
BM | BLOWER MOTOR |
BPS | BLOWER PROVING SWITCH |
CB | CIRCUIT BREAKER |
CC | COMPRESSOR CONTACTOR |
CFS | CLOGGED FILTER SWITCH |
CO2 | CARBON DIOXIDE SENSOR |
DAT | DISCHARGE AIR TEMPERATURE |
DDC | DIRECT DIGITAL CONTROL |
ECON | ECONOMIZER |
EHK | ELECTRIC HEATER KIT |
ES | EMERGENCY SHUTDOWN |
FPS | FREEZE PROTECTION SWITCH |
GND | EQUIPMENT GROUND |
HPS | HIGH PRESSURE SWITCH |
IAH | INDOOR AIR HUMIDITY |
LDS | LOAD SHEDDING |
LPS | LOW PRESSURE SWITCH |
OAT | OUTDOOR AIR TEMPERATURE |
OAH | OUTDOOR AIR HUMIDITY |
PLF | FEMALE PLUG/CONNECTOR |
PLM | MALE PLUG/CONNECTOR |
PS | PRESSURE SWITCH |
RSS | REMOTE START/STOP |
SPA | SETPOINT ADJUST |
SPT | SPACE TEMPERATURE |
TB | TERMINAL BLOCK |
TR | TRANSFORMER |
XS | TRAMSFORMER POWER |
WIRE CODE
BK | BLACK |
---|---|
BL | BLUE |
BL/PK | BLUE WITH PINK STRIPE |
BR | BROWN |
GR | GREEN |
GY | GRAY |
OR | ORANGE |
PK | PINK |
PU | PURPLE |
RD | RED |
TN | TAN |
WH | WHITE |
YL | YELLOW |
YL/PK | YELLOW WITH PINK STRIPE |
NOTES
-
REPLACEMENT WIRE MUST BE SAME SIZE AND TYPE OF INSULATION AS ORIGINAL (AT LEAST 105° C). USE COPPER CONDUCTORS ONLY.
USE N.E.C. CLASS 2 WIRE FOR ALL LOW VOLTAGE FIELD CONNECTIONS. -
TR1 & TR2 PRIMARY (HIGH VOLTAGE) CONNECTIONS: ORANGE WIRES CONNECTED TO 240/460/575V TAP AT THE FACTORY AND BLACK WIRES TO COM TERMINAL. FOR 208V SUPPLY POWER, MOVE ORANGE WIRES FROM 240V TAP TO THE 208V TAP.
-
SEE CONTROL DIAGRAM FOR CONTROL TRANSFORMER LOW VOLTAGE CONNECTIONS
-
OPTIONAL FACTORY INSTALLED EQUIPMENT
COMPONENT LEGEND
BC | BLOWER CONTACTOR |
---|---|
BM | BLOWER MOTOR |
CB | CIRCUIT BREAKER |
CC | COMPRESSOR CONTACTOR |
CCH | CRANKCASE HEATER |
CCX | COMPRESSOR CONTACTOR AUXILIARY SWITCH |
CF HVTB | CONDENSER FAN HIGH VOLTAGE TERMINAL BLOCK |
CM | CONDENSER MOTOR |
COMP | COMPRESSOR |
F | FUSE |
FB | FUSE BLOCK |
FC | FAN CAPACITOR |
GND | EQUIPMENT GROUND |
PB | POWER DISTRIBUTION BLOCK |
PLF | FEMALE PLUG/CONNECTOR |
PLM | MALE PLUG/CONNECTOR |
TR | TRANSFORMER |
WIRE CODE
BK | BLACK |
---|---|
BL | BLUE |
BL/PK | BLUE WITH PINK STRIPE |
BR | BROWN |
GR | GREEN |
GY | GRAY |
OR | ORANGE |
PK | PINK |
PU | PURPLE |
RD | RED |
TN | TAN |
WH | WHITE |
YL | YELLOW |
YL/PK | YELLOW WITH PINK STRIPE |
NOTES
-
REPLACEMENT WIRE MUST BE SAME SIZE AND TYPE OF INSULATION AS ORIGINAL (AT LEAST 105° C). USE COPPER CONDUCTORS ONLY.
USE N.E.C. CLASS 2 WIRE FOR ALL LOW VOLTAGE FIELD CONNECTIONS. -
IF OPTIONAL ECONOMIZER IS INSTALLED, INSERT PLM PLUG PROVIDED BY THE ECONOMIZER KIT.
-
IF ELECTRIC HEAT IS INSTALLED, CONNECT EHK EXT PLF TO ACCESSORY HEAT PLUG IN HEAT COMPARTMENT
-
FIELD WIRE BACNET MS/TP TO J25. SEE USER IO MANUAL FOR ADDITIONAL INFORMATION.
-
A. IF OPTIONAL OEM SAFETY EQUIPMENT SUCH AS PHASE MONITOR, FLOAT SWITCH OR SMOKE DETECTOR ARE INSTALLED, UNPLUG JUMPER PLUG AND PLUG IN SAFETY DEVICE.
B. IF MULTIPLE SAFETIES ARE INSTALLED, PLUG IN THE ADDITIONAL DEVICES IN SERIES.
PLUG IN JUMPER PLUG AT THE LAST SAFETY DEVICE INSTALLED.
IF A THIRD PARTY SAFETY DEVICE IS FIELD INSTALLED, CUT THE RED WIRE ON THE JUMPER PLUG AND WIRE A NORMALLY CLOSED DRY CONTACT IN SERIES WITH THE CUT WIRE OPTIONAL FACTORY INSTALLED EQUIPMENT. -
REMOVE YELLOW AND PURPLE JUMPER WIRES IF OPTIONAL FREEZESTATS ARE INSTALLED.
-
SEE POWER WIRING DIAGRAM FOR TRANSFORMER LINE VOLTAGE CONNECTIONS.
NOTES
-
REPLACEMENT WIRE MUST BE SAME SIZE AND TYPE OF INSULATION AS ORIGINAL (AT LEAST 105° C). USE COPPER CONDUCTORS ONLY.
USE N.E.C. CLASS 2 WIRE FOR ALL LOW VOLTAGE FIELD CONNECTIONS. -
TR1 & TR2 PRIMARY (HIGH VOLTAGE) CONNECTIONS: ORANGE WIRES CONNECTED TO 240/460/575V TAP AT THE FACTORY AND BLACK WIRES TO COM TERMINAL. FOR 208V SUPPLY POWER, MOVE ORANGE WIRES FROM 240V TAP TO THE 208V TAP ON BOTH TRANSFORMERS.
-
SEE CONTROL DIAGRAM FOR CONTROL TRANSFORMER LOW VOLTAGE CONNECTIONS
-
FUSE BLOCKS ARE OPTIONAL FACTORY INSTALLED EQUIPMENT
NOTES
-
REPLACEMENT WIRE MUST BE SAME SIZE AND TYPE OF INSULATION AS ORIGINAL (AT LEAST 105° C). USE COPPER CONDUCTORS ONLY. USE N.E.C. CLASS 2 WIRE FOR ALL LOW VOLTAGE FIELD CONNECTIONS.
-
IF OPTIONAL ECONOMIZER IS INSTALLED, INSERT PLM PLUG PROVIDED WITH THE ECONOMIZER KIT.
-
FIELD WIRE BACNET MS/TP TO J25. SEE USER IO MANUAL FOR ADDITIONAL INFORMATION.
-
A. IF OPTIONAL OEM SAFETY EQUIPMENT SUCH AS PHASE MONITOR, FLOAT SWITCH OR SMOKE DETECTOR ARE INSTALLED, UNPLUG JUMPER PLUG AND PLUG IN SAFETY DEVICE. IF MULTIPLE SAFETIES ARE INSTALLED, PLUG IN THE ADDITIONAL DEVICES IN SERIES. PLUG IN JUMPER PLUG AT THE LAST SAFETY DEVICE INSTALLED.
B. IF A THIRD PARTY SAFETY DEVICE IS FIELD INSTALLED, CUT THE RED WIRE ON THE JUMPER PLUG AND WIRE A NORMALLY CLOSED DRY CONTACT IN SERIES WITH THE CUT WIRE -
OPTIONAL FACTORY INSTALLED EQUIPMENT.
-
REMOVE YELLOW AND PURPLE JUMPER WIRES IF OPTIONAL FREEZESTATS ARE INSTALLED.
-
SEE POWER WIRING DIAGRAM FOR TRANSFORMER LINE VOLTAGE CONNECTIONS.
NOTES
-
REPLACEMENT WIRE MUST BE SAME SIZE AND TYPE OF INSULATION AS ORIGINAL (AT LEAST 105° C). USE COPPER CONDUCTORS ONLY.
USE N.E.C. CLASS 2 WIRE FOR ALL LOW VOLTAGE FIELD CONNECTIONS. -
TR1 & TR2 PRIMARY (HIGH VOLTAGE) CONNECTIONS: ORANGE WIRES CONNECTED TO 240/460/575V TAP AT THE FACTORY AND BLACK WIRES TO COM TERMINAL. FOR 208V SUPPLY POWER, MOVE ORANGE WIRES FROM 240V TAP TO THE 208V TAP ON BOTH TRANSFORMERS.
-
SEE CONTROL DIAGRAM FOR CONTROL TRANSFORMER LOW VOLTAGE CONNECTIONS
-
FUSE BLOCKS ARE OPTIONAL
Start-up Checklist
*Store in job file
Date: ———–
Location: ———–
Model Number: ———–
Serial Number: ———–
Technician: Unit 4: ———–
Pre Start-Up
(Check each item as completed)
- Verify all packaging material has been removed.
- Remove all shipping brackets per installation instructions.
- Verify the job site voltage agrees with the unit serial plate.
- Verify condensate connection is installed per installation instructions.
- Verify proper clearance around the unit for safety, service, maintenance and proper unit operation.
- Verify proper weatherproofing of all ductwork, roof curbs and electrical connections.
- Check that the flue screen is in place.
- Check gas piping for leaks.
- Verify gas pressure to the unit is within the range specified on the serial plate.
- Check for proper beit tension and alignment per installation instructions.
- Check refrigerant piping for rubbing and leaks. Repair if necessary.
- Check unit wiring to ensure it is not in contact with refrigerant piping or sharp metal edges.
- Check all electrical connections and terminals. Tighten as needed.
- Verify that the crankcase heaters have been energized for 24 hours.
- Verify the scroll compressor(s) are rotating in the right direction.
- Verify all accessories are installed and operating correctly.
- Check filters and replace if necessary.
- Verify the installation of the thermostat.
CUSTOMER FEEDBACK
Daikin is very interested in all product comments.
Please fill out the feedback form on the following
link:https://daikincomfort.com/contact-us
You can also scan the QR code on the right to be directed to the feedback
page.
Our continuing commitment to quality products may mean a change in
specifications without notice.
©2022 DAIKIN COMFORT TECHNOLOGIES MANUFACTURING, L.P.
19001 Kermier Rd. Waller, TX 77484
www.daikincomfort.com
References
- Mini-split AC systems, heat pumps, VRV multi-zone systems for residential and commercial HVAC | Daikin AC
- Daikin Comfort - Perfecting The Air We Share
- Daikin Comfort - Perfecting The Air We Share
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>