Lenovo 1U Switched and Monitored Power Distribution Units User Guide
- June 3, 2024
- Lenovo
Table of Contents
1U Switched and Monitored Power Distribution Units
User Guide
Lenovo 1U Switched and Monitored Power Distribution Units
Product Guide (withdrawn product)
The 1U Switched and Monitored Power Distribution Units (PDUs) make it quick
and simple to deploy, protect, and manage your high-availability rack
environment. These space-efficient and power-dense PDUs come in two unique 1U
designs, either nine IEC-320-C19 (16A) and three IEC-320-C13 (10A) or 12
IEC-320-C13 (10A), with single-phase 30A, 32A, 60A, 63A, and three-phase 32A
and 60A solutions available to meet the requirements of your most power-
demanding systems.
The receptacles on these PDUs are switched for additional intelligent power
management capabilities. They provide on-and-off functionality to allow for
power sequencing and to help prevent unintended overloading. The PDUs are
shown in Figure 1.
Figure 1. 1U Switched and Monitored PDUs (left: model with C19 outlets,
right: with C13 outlets)
Did you know?
These PDUs also combine receptacle density with advanced intelligent power
management capabilities that can be remotely monitored and managed via a web
interface. Switched and Monitored PDU models don’t just monitor the incoming
power of the PDU, but also provide a more granular and precise view of power
usage at the individual receptacle level.
Click here to check for updates
Lenovo 1U Switched and Monitored Power Distribution Units (withdrawn
product)
Part number information
Table 1 lists the four available switched and monitored PDUs.
Two require that a separate line cord be ordered from Table 2, and two have a
line cord permanently attached.
Table 1. Ordering part numbers and feature codes
Part number | Feature code | Description | Line cord |
---|---|---|---|
46M4002 | 5896 | 1U 9 C19/3 C13 Switched and Monitored DPI PDU | Detachable – see |
Table 2
46M4003| 5897| 1U 9 C19/3 C13 Switched and Monitored 60A 3-phase PDU| Fixed –
IEC 309 3P+Gnd
46M4004| 5894| 1U 12 C13 Switched and Monitored DPI PDU| Detachable – see
Table 2
46M4005| 5895| 1U 12 C13 Switched and Monitored 60A 3-phase PDU| Fixed – IEC
309 3P+Gnd
The line cords that are available for the PDUs with part numbers 46M4002 and
46M4004 are listed in Table 2.
Table 2. Line cord part numbers and feature codes
Part number| Feature code| Description| Maximum input
current (Amps)
---|---|---|---
40K9611| 6504| DPI 32a Line Cord (IEC 309 3P+N+G)| 32 A
40K9612| 6502| DPI 32a Line Cord (IEC 309 P+N+G)| 32 A
40K9613| 6503| DPI 63a Cord (IEC 309 P+N+G)| 63 A
40K9614| 6500| DPI 30a Line Cord (NEMA L6-30P)| 24 A (30 A derated)
40K9615| 6501| DPI 60a Cord (IEC 309 2P+G)| 48 A (60 A derated)
40K9617| 6505| DPI Australian/NZ 3112 Line Cord| 32 A
40K9618| 6506| DPI Korean 8305 Line Cord| 30 A
The detachable line cords, with the exception of the IEC 309 3P+N+G power cable, are shown below in Figure 2.
Figure 2. Line cords
The part numbers for the 1U Switched and Monitored PDUs are shipped with the
following items:
- 1 power distribution unit
- Environmental Monitoring Probe kit – sensor, CAT5 cable, mounting hardware
- Mounting rails for supported System x racks – horizontal and vertical mounting
- 1 blank 1U filler panel
- RS232 to RJ45 serial cable
- Miscellaneous hardware kit
Introduction to PDUs
A power distribution unit (PDU) is a highly reliable, multiple outlet power
strip designed to consolidate line cords within the rack and distribute
conditioned power from a UPS or utility power to servers and other IT
equipment. The PDU efficiently distributes power within the rack and provides
fault-tolerant power redundancy for high availability requirements.
There are three types of PDUs available from Lenovo: basic, monitored and
switched monitors. The PDUs covered in this document is of the switched and
monitored type.
- Basic: The simplest and most cost-effective power distribution. Available with various outlet configurations and line cord options to support differing systems and load requirements.
- Monitored (also known as PDU+): Provides the same benefits as a Basic PDU, but adds additional advanced PDU power monitoring down to the load group. This enables businesses to have a cross-platform rack-level power and thermal view for trending analysis to improve power management.
- Switched and Monitored: These are next-generation advanced power management solutions, providing power monitoring at the outlet level, with increased accuracy at low amperages, for more precise views of power consumption down to the individual component/server level instead of at the consolidated load group. These PDUs also offer management via a web-based interface which includes individual outlet switching (on/off). Outlet switching allows for remote power sequencing and helps prevent unintended PDU overloading.
Features
The following table compares the major features of the PDUs.
Table 3. Feature comparison
Feature| 1U 9 C19/3 C13 Switched and Monitored DPI PDU| 1U 9
C19/3 C13 Switched and Monitored 60A 3 Phase PDU| 1U 12 C13 Switched
and Monitored DPI PDU| 1U 12 C13 Switched and Monitored 60A 3 PhasePDU
---|---|---|---|---
Part number| 46M4002| 46M4003| 46M4004| 46M4005
Line cord| Order Separately| Permanently attached| Order Separately|
Permanently attached
Line cord connector| Varies – see Table 2| IEC 309 3P+Gnd| Varies – see Table
2| IEC 309 3P+Gnd
Input current maximum| Varies – see Table 2| 48 A (60 A derated)
(27.7 A/phase)| Varies – see Table 2| 48 A (60 A derated)
(27.7 A/phase)
Number of phases| Single or 3 phase wye| 3-phase power delta| Single or 3
phase wye| 3-phase power delta
Number of C13 outlets| 3 (on the rear of the unit)| 3 (on the rear of the
unit)| 12| 12
Number of C19 outlets| 9| 9| 0| 0
Circuit breakers| 9 double-pole branch-rated circuit breakers rated at 20amps|
9 double-pole branch-rated circuit breakers rated at 20 amps| 6 double-pole
branch-rated circuit breakers rated at 20amps| 6 double-pole branch-rated
circuit breakers rated at 20 amps
The 1U Switched and Monitored PDUs have the following features:
- 1U Rack Dense design with input cable connection, primary outlets, communication connections, and breakers on one face to improve usability and cable management
- Hardware included mounting in either EIA space or the side pocket of the rack
- Easily accessible individual breakers per receptacle for high availability environments
- Switched Receptacles with on and off functionality to allow for power sequencing and to prevent unintended overloading
- Monitored power draw at the receptacle level Advanced remote monitoring capability
- Detailed data logging for statistical analysis and diagnostics
- Management using SNMPv3 An Environmental Monitoring Probe (EMP) included providing both temperature and humidity values
Outlet ratings:
The power outlets for C19 models (46M4002 and 46M4003) have the following
ratings:
- 9 IEC320 -C19 outlets rated at 16 amps
- 3 IEC320-C13 outlets rated at 10 amps
The power outlets for C13 models (46M4004 and 46M4005) have the following ratings:
- 12 IEC320-C13 outlets rated at 10 amps
Environmental Monitoring Probe:
The Environmental Monitoring Probe (EMP) is shown in Figure 3 and is used to
report local temperature and humidity values and make that information
available to the web interface of the PDU.
Figure 3. The Environmental Monitoring Probe (EMP)
The EMP is attached to the PDU as shown in Figure 4.
Figure 4. Attaching the Environmental Monitoring Probe
The Environmental Monitoring Probe has the following features:
- The temperature and humidity sensor enables you to remotely monitor the temperature and humidity and status of two contact devices in the rack
- Hot-swap feature simplifies installation by enabling you to install the probe safely without turning off power to the PDU or to the loads that are connected to it
- Measures temperatures between 0 and 80°C (32 and 176°F) with an accuracy of ±1°C
- Measures relative humidity between 10 and 90% with an accuracy of ±5%
- Can be located away from the PDU with a CAT5 network cable up to 20 m (65.6 ft)
- User-selectable alarm thresholds enable you to define acceptable temperature or humidity limits
- E-mail notification through SMTP
Management methods:
The Switched and Monitored DPI PDUs can be managed by any of the following
methods:
- Web browser
- Telnet
- SNMP
- Serial connection
Connectors
The two 1U 9 C19/3 C13 Switched and Monitored DPI PDUs have the following
connectors on the front of the unit (Figure 5).
Figure 5. 1U 9 C19/3 C13 Switched and Monitored DPI PDU (front)
Figure 6 shows the rear of the 1U 9 C19/3 C13 Switched and Monitored DPI PDUs
where the three C13 outlets are located.
Figure 6. 1U 9 C19/3 C13 Switched and Monitored DPI PDU (rear)
The two 1U 12 C13 Switched and Monitored DPI PDUs have the following
connectors (Figure 7). There are no additional connectors on the rear of the
unit.
Figure 7. 1U 12 C13 Switched and Monitored DPI PDUs (front)
Physical specifications
1U Switched and Monitored PDUs have the following dimensions:
- Approximate height: 43.9 mm (1.73 in.)
- Approximate width: 447 mm (17.6 in.)
- Approximate depth: 350 mm (13.78 in.)
- Approximate weight: (not including power cord) 6.3 kg (13.8 lb)
- Weight of power cord (approximate, varies by PDU model) 5.4 kg (11.8 lb)
- Additional clearance 25 mm (0.98 in.) for circuit breakers and 3 mm (0.12 in.) for outlets
Operating environment
The 1U Switched and Monitored PDUs operate in the following environment:
- Temperature: 10 to 60 °C (50 to 140 °F)
- Relative humidity: 8% to 80% (non-condensing)
Electrical specifications
The following tables list the specific rated voltage, rated current, and
maximum power rating for each combination of PDU and line cord.
Table 4. Rated input power source for the 1U 9 C19/3 C13 Switched and
Monitored DPI PDU with all line cord combinations
Description of PDU + Line cord| PDU part number| Line cord
part number| Rated voltage, rated current| Max power rating
---|---|---|---|---
DPI 32 amp / 250 V three-phase 1U 9 C19 / 3 C13 switched and monitored DPI PDU
with IEC 309 3P+N+Gnd connector| 46M4002| 40K9611| 220-240 V, 50-60 Hz,32 A,
three-phase Wye| 23040 VA
DPI 32 amp / 250 V single-phase 1U 9 C19 / 3 C13 switched and monitored DPI
PDU with IEC 309 P+N+Gnd connector| 46M4002| 40K9612| 220-240 V, 50-60 Hz,32
A, single-phase| 7680 VA
DPI 63 amp / 250 V single-phase 1U 9 C19 / 3 C13 switched and monitored DPI
PDU with IEC 309 P+N+Gnd connector| 46M4002| 40K9613| 220-240 V, 50-60 Hz,63
A, single-phase| 15120 VA
DPI 30 amp / 208 V single-phase 1U 9 C19 / 3 C13 switched and monitored DPI
PDU with NEMA L6-30P (2P+Gnd) connector| 46M4002| 40K9614| 200-208 V, 50-60
Hz,24 A, single-phase| 4992 VA
DPI 60 amp / 208 V single-phase 1U 9 C19 / 3 C13 switched and monitored DPI
PDU with IEC 309 2P+Gnd connector| 46M4002| 40K9615| 200-208 V, 50-60 Hz,48 A,
single-phase| 9984 VA
DPI 32 amp / 250 V single-phase 1U 9 C19 / 3 C13 switched and monitored DPI
PDU with special connector for Australia and New Zealand (not IEC 309)|
46M4002| 40K9617| 220-240 V, 50-60 Hz,32 A, single-phase| 7680 VA
DPI 30 amp / 250 V single-phase 1U 9 C19 / 3 C13 switched and monitored DPI
PDU with special Korea connector – P+N+Gnd connector| 46M4002| 40K9618|
220-240 V, 50-60 Hz,30 A, single-phase| 7200 VA
Table 5. Rated input power source for the 1U 9 C19/3 C13 Switched and Monitored 60A 3-phase PDU
Description of PDU + Line cord| PDU part number| Line cord part
number| Rated voltage, rated current| Max power rating
---|---|---|---|---
DPI 60 amp / 208 V three-phase 1U 9 C19 / 3 C13 switched and monitored PDU
with fixed IEC 309 3P+Gnd connector| 46M4003| fixed| 200-208 V, 50-60 Hz,48 A,
three-phase Delta| 17292 VA
Table 6. Rated input power source for the 1U 12 C13 Switched and Monitored DPI PDU with all cord combinations
Description of PDU + Line cord| PDU part number| Line cord
part number| Rated voltage, rated current| Max power rating
---|---|---|---|---
DPI 32 amp / 250 V three-phase 1U 12 C13 switched and monitored DPI PDU with
IEC 309 3P+N+Gnd connector| 46M4004| 40K9611| 220-240 V, 50-60 Hz,32 A, three-
phase Wye| 23040 VA
DPI 32 amp / 250 V single-phase 1U 12 C13 switched and monitored DPI PDU with
IEC 309 P+N+Gnd connector| 46M4004| 40K9612| 220-240 V, 50-60 Hz,32 A, single-
phase| 7680 VA
DPI 63 amp / 250 V single-phase 1U 12 C13 switched and monitored DPI PDU with
IEC 309 P+N+Gnd connector| 46M4004| 40K9613| 220-240 V, 50-60 Hz,63 A, single-
phase| 15120 VA
DPI 30 amp / 208 V single-phase 1U 12 C13 switched and monitored DPI PDU with
NEMA L6-30P (2P+Gnd) connector| 46M4004| 40K9614| 200-208 V, 50-60 Hz,24 A,
single-phase| 4992 VA
DPI 60 amp / 208 V single-phase 1U 12 C13 switched and monitored DPI PDU with
IEC 309 2P+Gnd connector| 46M4004| 40K9615| 200-208 V, 50-60 Hz,48 A, single-
phase| 9984 VA
DPI 32 amp / 250 V single-phase 1U 12 C13 switched and monitored DPI PDU with
a special connector for Australia and New Zealand (not IEC 309)| 46M4004|
40K9617| 220-240 V, 50-60 Hz,32 A, single-phase| 7680 VA
Table 7. Rated input power source for 1U 12 C13 Switched and Monitored 60A 3-phase PDU
Description of PDU + Line cord| PDU part number| Line cord part
number| Rated voltage, rated current| Max power rating
---|---|---|---|---
DPI 60 amp / 208 V three-phase 1U 12 C13 switched and monitored PDU with fixed
IEC 309 3P+Gnd connector| 46M4005| fixed| 200-208 V, 50-60 Hz,
48 A, three-phase Delta
| 17292 VA
Warranty
These switched and monitored PDUs are offered a three-year, limited warranty.
Supported rack cabinets
The 1U Switched and Monitored PDUs can be installed in all 19-inch rack
cabinets including the following:
- iDataPlex Rack Cabinet (7825)
- S2 42U Standard Rack Cabinet (Types 9307 and 9956)
- Enterprise Rack Cabinet (Types 1410 and 9308)
Installation can be either vertically inside pockets of the rack or
horizontally in a 1U space. The PDU part numbers include the necessary rack
installation hardware for either configuration.
Related publications and links
For more information refer to these documents:
- Rack & Power Infrastructure Options page https://lenovopress.com/lp0766-rack-power-infrastructure-options
- User Manual http://systemx.lenovofiles.com/help/topic/com.lenovo.sysx.racks.doc/ch_1Uc19c13swmonpdus.html?cp=0_5_1_1_1
- Lenovo PDU Quick Reference Guide – North America http://lenovopress.com/redp5266-pdu-quick-reference-north-america
- Lenovo PDU Quick Reference Guide International http://lenovopress.com/redp5267-pdu-quick-reference-international
- PDU and UPS Technical Reference Guides: http://support.lenovo.com/documents/LNVO-POWINF
- Power Configurator tool: http://support.lenovo.com/documents/LNVO-PWRCONF
Related product families
Product families related to this document are the following:
Power Distribution Units
Notices
Lenovo may not offer the products, services, or features discussed in this
document in all countries. Consult your local Lenovo representative for
information on the products and services currently available in your area. Any
reference to a Lenovo product, program, or service is not intended to state or
imply that only the Lenovo product, program, or service may be used. Any
functionally equivalent product, program, or service that does not infringe
any Lenovo intellectual property right may be used instead. However, it is the
user’s responsibility to evaluate and verify the operation of any other
product, program, or service. Lenovo may have patents or pending patent
applications covering the subject matter described in this document. The
furnishing of this document does not give you any license to these patents.
You can send license inquiries, in writing, to:
Lenovo (United States), Inc.
8001 Development Drive
Morrisville, NC 27560
The U.S.A.
Attention: Lenovo Director of Licensing
LENOVO PROVIDES THIS PUBLICATION “AS IS” WITHOUT WARRANTY OF ANY KIND, EITHER
EXPRESS OR IMPLIED, INCLUDING, BUT NOT LIMITED TO, THE IMPLIED WARRANTIES OF
NON-INFRINGEMENT, MERCHANTABILITY, OR FITNESS FOR A PARTICULAR PURPOSE. Some
jurisdictions do not allow disclaimers of express or implied warranties in
certain transactions, therefore, this statement may not apply to you.
This information could include technical inaccuracies or typographical errors.
Changes are periodically made to the information herein; these changes will be
incorporated in new editions of the publication. Lenovo may make improvements
and/or changes in the product(s) and/or the program(s) described in this
publication at any time without notice.
The products described in this document are not intended for use in
implantation or other life support applications where malfunction may result
in injury or death to persons. The information contained in this document does
not affect or change Lenovo product specifications or warranties. Nothing in
this document shall operate as an express or implied license or indemnity
under the intellectual property rights of Lenovo or third parties. All
information contained in this document was obtained in specific environments
and is presented as an illustration. The result obtained in other operating
environments may vary. Lenovo may use or distribute any of the information you
supply in any way it believes appropriate without incurring any obligation to
you.
Any references in this publication to non-Lenovo Web sites are provided for
convenience only and do not in any manner serve as an endorsement of those Web
sites. The materials at those Web sites are not part of the materials for this
Lenovo product, and use of those Web sites is at your own risk. Any
performance data contained herein was determined in a controlled environment.
Therefore, the result obtained in other operating environments may vary
significantly. Some measurements may have been made on development-level
systems and there is no guarantee that these measurements will be the same on
generally available systems. Furthermore, some measurements may have been
estimated through extrapolation. Actual results may vary. Users of this
document should verify the applicable data for their specific environment.
© Copyright Lenovo 2022. All rights reserved.
This document, TIPS0775, was created or updated on January 24, 2022.
Send us your comments in one of the following ways:
Use the online Contact us review form found at:
https://lenovopress.com/TIPS0775
Send your comments in an e-mail to:
comments@lenovopress.com
This document is available online at https://lenovopress.com/TIPS0775.
Trademarks
Lenovo and the Lenovo logo are trademarks or registered trademarks of Lenovo
in the United States, other countries, or both. A current list of Lenovo
trademarks is available on the Web at
https://www.lenovo.com/us/en/legal/copytrade/.
The following terms are trademarks of Lenovo in the United States, other
countries, or both: Lenovo® System x® iDataPlex®
Other company, product, or service names may be trademarks or service marks of
others.
References
- Lenovo PDU Quick Reference Guide - North America > Lenovo Press
- Lenovo PDU Quick Reference Guide – International > Lenovo Press
- Lenovo Enterprise Systems Data Center Planning Portal - Lenovo Support US
- Lenovo Enterprise Systems Data Center Planning Portal - Lenovo Support US
- 1U C19 and C13 Switched and Monitored PDUs
- 1U C19 and C13 Switched and Monitored PDUs
- Rack & Power Infrastructure Options > Lenovo Press
- Lenovo 1U Switched and Monitored Power Distribution Units Product Guide (withdrawn product) > Lenovo Press
- Copyright and Trademark Information | Lenovo US | Lenovo US
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>