LENNOX Commercial Rooftop Unit User Guide

June 12, 2024
Lennox

LENNOX Commercial Rooftop Unit User Guide
LENNOX Commercial Rooftop Unit

Siemens Setup and Configuration Guide

Applies to Lennox Rooftop using a Siemens Climatix ECO Economizer Controller

Follow the steps below to setup the siemens controller manually.

  1. From the default HMI screen, press and hold Enter + Up. The 5CONFIG STATE screen displays.

  2. Press enter, and then confirm the switch by pressing enter again. Blocks can be changed by pressing and holding Enter + Up or Down. Parameters can be changed by pressing enter and using the arrows to adjust. Confirm the switch by pressing enter again.

  3. Configure I/Os. See below for notable parameters.
    Parameter| Configure As| Description
    ---|---|---
    6OCC| Always/T-stat| Occupancy comes from controller or OC terminal
    6OAT SIG| NTC10K| Configures signal type of OAT sensor
    6OAH SIG| 0-10V| Configures signal type of OAH sensor
    6RAH SIG| 0-10V| Configures signal type of RAH sensor
    6MAT SIG| NTC10K| Configures signal type of MAT or LAT

  4. If configurations are done, press and hold Enter + Up or Down to switch to the 8RUN STATE screen, then press Enter twice to go back to Running State. The 1FREECOOL screen displays.

    Apps
    Apps
    Apps

  5. Verify status parameters. See below for notable parameters.
    Parameter| Description
    ---|---
    1FREECOOL| Indicates if the system can use outdoor air for free cooling
    1ECON ENAB| Indicates if outdoor air is being used for the 1st stage of cooling
    1OCCUPIED| Indicates if the space is occupied- Controller needs to be in the occupied state
    1Y1-IN| Y1-In call from thermostat for Cooling Stage 1
    1Y1-OUT| Y1-Out signal to compressor for Cooling Stage

  6. Configure basic settings. See below for notable parameters.
    Parameter| Configure As| Description
    ---|---|---
    2TEMP OFF| 55°F (12.8°C)| Temperature shutoff setpoint
    2ENTH OFF| 22 Btu/lbm| Enthalpy shutoff setpoint
    2FAN L ACT| 2.8V| Minimum position at low speed
    2FAN H ACT| 3.6V| Minimum position at high speed

Damper Position – 2V = 0% 6V = 50% 10V = 100%

  1. Configure advanced settings. See below for notable parameters.
    Parameter| Configure As| Description
    ---|---|---
    3FREEZE POS| CLO| Anti-freeze protection damper position
    3MAT SET| 53°F (11.7°C)| Setpoint of MAT or LAT sensor
    3FRZ PROT| 45°F (7.2°C)| Anti-freeze protection setpoint of MAT sensor
    3OAT LOCK| 32°F (0°C)| OAT lockout setpoint for anti-freeze
  2. To enter test functions. See below for notable parameters.
    From the default HMI screen, press and hold Enter + Up. The 5CONFIG STATE screen displays. Press enter, and then confirm the switch by pressing enter again.
Parameter Description
7DAMPER MIN POS Drives damper to minimum position
7DAMPER CLOSE Drives damper 100% closed
7DAMPER OPEN Drives damper 100% open

If configurations are done, press and hold Enter + Up or Down to switch to the 8RUN STATE screen, then press Enter twice to go back to Running State. The 1FREECOOL screen displays.