NDZGG50V16 Mersen Electrical Power Fuses Surge
Product Information
The D fuse-links gG are low voltage IEC fuses used for theprotection of cables and power lines. They are part of the first generation of screw fuse-system in the German DIN standard. The D fuse range includes the sizes NDZ, DII, DIII, DIV, DV. These fuse-links limit and cut-off unacceptable overcurrents and short circuit currents up to their nominal breaking capacity. They also protect equipment and installations against dynamic effects of high short circuit currents.
The technical data overview for the D fuse-links gG is as follows:
- Voltage Range AC: 500V to 690VAC
- Voltage Range DC: 500VDC
- Ampere Range: 2A to 200A
- Speed/Characteristic: gG
- I.R. AC (IEC): 50kA
The D fuse-links gG conform to RoHS (chrome 6) standards.
Product Usage Instructions
The D fuse-links gG are designed for use in low voltage distribution units where non-trained persons are allowed to change the fuse-links. Follow the steps below to use the product:
- Identify the appropriate size of the D fuse-link (NDZ, DII, DIII, DIV, DV) based on your application requirements.
- Ensure that the voltage range (AC or DC) and ampere range of the fuse-link matches your system’s specifications.
- Select the desired color of the fuse-link based on your preference or coding system.
- Refer to the catalog number and item number for the specific product variant you need.
- Install the D fuse-link into the corresponding fuse-holder in your low voltage distribution unit.
- Make sure the fuse-link is securely connected and properly aligned.
- If a fuse-link needs to be replaced, follow the same steps to remove the old one and install a new D fuse-link.
For further assistance or if you have specific technical specifications and conditions, please contact Mersen for a solution tailored to your needs.
The D fuse-system is the first generation of screw fuse-system in the german
DIN standard. It is still used in many installations.
Applications are low voltage ditribution units, where non trained persons are
allowed to change the fuse-links.
The D fuse range comprises the sizes NDZ, DII, DIII, DIV, DV.
The range of applications for D fuse-links is the protection of cables and
power lines. They limit and cut-off unacceptable overcurrents and short
circuit currents up to their nominal breaking capacity. D fuse-links “gG” also
protect equipments and installations against dynamic effects of high short
circuit currents.
TECHNICAL DATA OVERVIEW
Voltage Range AC | 500 … 690 VAC |
---|---|
Voltage DC | 500 VDC |
Ampere Range (A) | 2 … 200 A |
Speed/Characteristic | gG |
I.R. AC (IEC) | 50 kA |
Product Size | NDZ to DV |
FEATURES & BENEFITS
- Insulated body suitable for high mechanical and thermal impacts
- Top and bottom contacts made of nickel plated copper alloy
- Safe cut-off short circuits and over currents due to special design of fuse element
- Clear indication of operation condi-tion due to coloured indicator on top contact
- Low power dissipation
- Optimized size
- Resistant to aging
- Free of lead, cadmium, mercury, chrome 6 (rohs conformity)
APPLICATIONS
- House incoming units
- Meter distribution units
- Distribution cabinets
- Installation cabinets
- Fuse boxes
STANDARDS
- DIN VDE 0636-301
PRODUCT RANGE
Size NDZ gG
Catalog number| Item number| Rated voltage AC (IEC)| Rated voltage DC (IEC)|
Rated current In
| ****
Colour
| ****
Package
| ****
Weight
---|---|---|---|---|---|---|---
NDZGG50V2| W212539| 500 V| 500 V| 2 A| pink| 25| 13.3 g
NDZGG50V4| G213055| 500 V| 500 V| 4 A| brown| 25| 13.3 g
NDZGG50V6| C213557| 500 V| 500 V| 6 A| green| 25| 13.3 g
NDZGG50V10| B214062| 500 V| 500 V| 10 A| red| 25| 13.3 g
NDZGG50V16| J214575| 500 V| 500 V| 16 A| grey| 25| 13.3 g
NDZGG50V20| Q215087| 500 V| 500 V| 20 A| blue| 25| 13.3 g
NDZGG50V25| Q215593| 500 V| 500 V| 25 A| yellow| 25| 13.3 g
Size DII gG
Catalog number| Item number| Rated voltage AC (IEC)| Rated voltage DC (IEC)| Rated current In| ****
Colour
| Power dissipation at In| ****
Package
| ****
Weight
---|---|---|---|---|---|---|---|---
DIIGG50V2| Z219718| 500 V| 500 V| 2 A| pink| 2.1 W| 25| 26.8 g
DIIGG50V4| G222163| 500 V| 500 V| 4 A| brown| 2 W| 25| 26.8 g
DIIGG50V6| B222917| 500 V| 500 V| 6 A| green| 1.2 W| 25| 26.8 g
DIIGG50V10| K200707| 500 V| 500 V| 10 A| red| 1.6 W| 25| 26.8 g
DIIGG50V16| K201765| 500 V| 500 V| 16 A| grey| 2.4 W| 25| 26.8 g
DIIGG50V20| A211508| 500 V| 500 V| 20 A| blue| 2.1 W| 25| 26.8 g
DIIGG50V25| X212540| 500 V| 500 V| 25 A| yellow| 3.5 W| 25| 26.8 g
Size DIII gG
Catalog number| Item number| Rated voltage AC (IEC)| Rated voltage DC (IEC)| Rated current In| ****
Colour
| Power dissipation at In| ****
Package
| ****
Weight
---|---|---|---|---|---|---|---|---
DIIIGG50V32| M229091| 500 V| 500 V| 32 A| black| –| 25| 51.6 g
DIIIGG50V35| C214063| 500 V| 500 V| 35 A| black| 3.7 W| 25| 51.6 g
DIIIGG50V50| K214576| 500 V| 500 V| 50 A| white| 5.2 W| 25| 51.6 g
DIIIGG50V63| R215088| 500 V| 500 V| 63 A| copper| 6 W| 25| 51.6 g
Size DIII gG 690VAC
Catalog number| Item number| Rated voltage AC (IEC)| ****
Rated current In
| ****
Colour
| Power dissipation at In| ****
Package
| ****
Weight
---|---|---|---|---|---|---|---
DIIIGG69V2| R215594| 690 V| 2 A| pink| –| 25| 73.58 g
DIIIGG69V4| Z216107| 690 V| 4 A| brown| 10 W| 25| 73.58 g
DIIIGG69V6| W216610| 690 V| 6 A| green| 12 W| 25| 73.58 g
DIIIGG69V10| H217127| 690 V| 10 A| red| 17 W| 25| 73.58 g
DIIIGG69V16| N217638| 690 V| 16 A| grey| 14 W| 25| 73.58 g
DIIIGG69V20| W218151| 690 V| 20 A| blue| 18 W| 25| 73.58 g
DIIIGG69V25| H218668| 690 V| 25 A| yellow| 20 W| 25| 73.58 g
DIIIGG69V35| X219187| 690 V| 35 A| black| 23 W| 25| 73.58 g
DIIIGG69V50| A219719| 690 V| 50 A| white| 36 W| 25| 73.58 g
DIIIGG69V63| H222164| 690 V| 63 A| copper| 55 W| 25| 73.58 g
Size DIV gG
Catalog number| Item number| Rated voltage AC (IEC)| Rated voltage DC (IEC)| Rated current In| ****
Colour
| Power dissipation at In| ****
Package
| ****
Weight
---|---|---|---|---|---|---|---|---
DIVGG50V80| V216609| 500 V| 500 V| 80 A| silver| 7.9 W| 10| 0.11 kg
DIVGG50V100| M217637| 500 V| 500 V| 100 A| red| 8.9 W| 10| 0.12 kg
Size DV gG
Catalog number| Item number| Rated voltage AC (IEC)| Rated voltage DC (IEC)| Rated current In| ****
Colour
| Power dissipation at In| ****
Package
| ****
Weight
---|---|---|---|---|---|---|---|---
DVGG50V125| V218150| 500 V| 500 V| 125 A| yellow| 10 W| 5| 0.20 kg
DVGG50V160| G218667| 500 V| 500 V| 160 A| copper| 16.5 W| 5| 0.20 kg
DVGG50V200| W219186| 500 V| 500 V| 200 A| blue| 18 W| 5| 0.20 kg
TIME CURRENT CHARACTERISTIC CURVES
NDZ 2A-50A
CUT-OFF CURRENT CHARACTERISTIC
NDZ 2A-25A
DIMENSIONS
D fuse-links
Size | a | bØ |
---|---|---|
NDZ | 50 | 12 |
DII | 50 | 22 |
DIII | 50 | 27 |
DIV | 63 | 37 |
DV | 63 | 45 |
Dimensions in mm
EP.MERSEN.COM
© 2021 Mersen. All rights reserved. Mersen reserves the right to change,
adapt, limit or discontinue its products. Therefore the data provided herein
are for information only and are not contractually binding. To ensure that
Mersen provides the best solution to your needs, please contact and provide
Mersen with all relevant technical specifications and conditions.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>