ABB MO165 Motor Starter
Product Information
- Product Model: MO165 / MO165-B
- Manufacturer: ABB STOTZ-KONTAKT GmbH
- Address: Eppelheimer Str. 82, 69123 Heidelberg, Germany
- Website: http://www.abb.com/lowvoltage
- Product Manual: Download
Product Usage Instructions
- Warning: Hazardous voltage! Refer to operating instructions.
- Disconnect and lock out power before working on this device.
- Installation should only be performed by persons with electrotechnical expertise.
- Refer to the English text in case of doubt.
Note: For detailed installation instructions and safety precautions, please refer to the product manual.
Installation instructions
Warning: Hazardous voltage!
Refer to operating instructions. Disconnect and lock out power before working
on this device.
Attention! Installation by a person with electrotechnical expertise only. The English text applies in case of doubt.
INSTALLATION INSTRUCTION
WARNING
When an overload or a fault current interruption occurs, circuits must be
checked to determine the cause of the interruption. When a fault condition
exists, the current-carrying components should be examined and replaced when
damaged, and the integral current sensors must be replaced to reduce the risk
of fire or electric shock. To maintain overcurrent, short-circuit, and ground-
fault protection, the manufacturer’s instructions for selection of overload
and short-circuit protection must be followed to reduce the risk of fire or
electric shock. Suitable for installation in an enclosure with minimum
dimemsions of 290 x 130 x 190 mm
When used with PS2-xx-125 busbars, suitable for installation in an enclosure with minimum dimensions:
Type | Height (mm) | Width (mm) | Depth (mm) |
---|---|---|---|
PS2-2-0-125 | 280 | 165 | 195 |
PS2-3-0-125 | 280 | 248 | 195 |
PS2-4-0-125 | 280 | 330 | 195 |
PS2-2-2-125 | 280 | 219 | 195 |
PS2-3-2-125 | 280 | 329 | 195 |
PS2-4-2-125 | 280 | 438 | 195 |
Combination motor controller Type F, when used with AF contactor series and overload relays EF or TF series and optional connector BEAxx”
Combination Motor Controller Type F
Type 1 Coordination
Type| 480Y/277V
[kA]
| OL Relay| Contactor| 600Y/347V
[kA]
| OL Relay| Contactor
MO165-16| 65| EF19-18.9| AF09…AF38| 50| EF19-18.9| AF09…AF38
MO165-20| 65| EF45-30| AF26…AF38| 50| EF45-30| AF26…AF38
MO165-25| 65| EF45-30| AF26…AF38| 50| EF45-30| AF26…AF38
MO165-32| 65| EF45-45| AF26…AF38| 50| EF45-45| AF26…AF38
MO165-42| 65| EF65| AF40…AF65| 30| EF65| AF40…AF65
MO165-54| 65| EF65| AF40…AF65| 30| EF65| AF40…AF65
MO165-65| 65| EF65| AF40…AF65| 30| EF65| AF40…AF65
MO165-73| 50| EF96| AF80…AF96| –| –| –
MO165-80| 50| EF96| AF80…AF96| –| –| –
Combination Motor Controller Type F
Type 1 Coordination
Type| 480Y/277V
[kA]
| OL Relay| Contactor| 600Y/347V
[kA]
| OL Relay| Contactor
MO165-16| 65| TF42| AF09…AF38| 30| TF42| AF09…AF38
MO165-20| 65| TF42| AF26…AF38| 30| TF42| AF09…AF38
MO165-25| 65| TF42| AF26…AF38| 50| TF42| AF26…AF38
MO165-32| 65| TF42| AF26…AF38| 50| TF42| AF26…AF38
MO165-42| 65| TF65| AF40…AF65| 30| TF65| AF40…AF65
MO165-54| 65| TF65| AF40…AF65| 30| TF65| AF40…AF65
MO165-65| 65| TF65| AF40…AF65| 30| TF65| AF40…AF65
MO165-73| 50| TF96| AF80…AF96| –| –| –
MO165-80| 50| TF96| AF80…AF96| –| –| –
Combination Motor Controller Type F
Type 2 Coordination
Type| 480Y/277V
[kA]
| OL Relay| Contactor| 600Y/347V
[kA]
| OL Relay| Contactor
MO165-73| 50| EF96| AF80…AF96| –| –| –
MO165-80| 50| EF96| AF80…AF96| –| –| –
Combination Motor Controller Type F
Type 2 Coordination
Type| 480Y/277V
[kA]
| OL Relay| Contactor| 600Y/347V
[kA]
| OL Relay| Contactor
MO165-73| 50| TF96| AF80…AF96| –| –| –
MO165-80| 50| TF96| AF80…AF96| –| –| –