ABB MO165 Motor Starter Instruction Manual

June 12, 2024
ABB

ABB MO165 Motor Starter

Product Information

Product Usage Instructions

  1. Warning: Hazardous voltage! Refer to operating instructions.
  2. Disconnect and lock out power before working on this device.
  3. Installation should only be performed by persons with electrotechnical expertise.
  4. Refer to the English text in case of doubt.

Note: For detailed installation instructions and safety precautions, please refer to the product manual.

Installation instructions

Warning: Hazardous voltage!
Refer to operating instructions. Disconnect and lock out power before working on this device.

Attention! Installation by a person with electrotechnical expertise only. The English text applies in case of doubt.ABB-MO165-Motor-Starter-
FIG-1

INSTALLATION INSTRUCTION

ABB-MO165-Motor-Starter-FIG-2 ABB-MO165-Motor-
Starter-FIG-3 ABB-MO165-Motor-Starter-
FIG-4 ABB-MO165-Motor-Starter-FIG-5 ABB-MO165-Motor-
Starter-FIG-6 ABB-MO165-Motor-Starter-
FIG-7 ABB-MO165-Motor-Starter-FIG-8 ABB-MO165-Motor-
Starter-FIG-9 ABB-MO165-Motor-Starter-
FIG-10 ABB-MO165-Motor-Starter-FIG-11

WARNING
When an overload or a fault current interruption occurs, circuits must be checked to determine the cause of the interruption. When a fault condition exists, the current-carrying components should be examined and replaced when damaged, and the integral current sensors must be replaced to reduce the risk of fire or electric shock. To maintain overcurrent, short-circuit, and ground- fault protection, the manufacturer’s instructions for selection of overload and short-circuit protection must be followed to reduce the risk of fire or electric shock. Suitable for installation in an enclosure with minimum dimemsions of 290 x 130 x 190 mm

When used with PS2-xx-125 busbars, suitable for installation in an enclosure with minimum dimensions:

Type Height (mm) Width (mm) Depth (mm)
PS2-2-0-125 280 165 195
PS2-3-0-125 280 248 195
PS2-4-0-125 280 330 195
PS2-2-2-125 280 219 195
PS2-3-2-125 280 329 195
PS2-4-2-125 280 438 195

Combination motor controller Type F, when used with AF contactor series and overload relays EF or TF series and optional connector BEAxx”

Combination Motor Controller Type F

Type 1 Coordination


Type| 480Y/277V

[kA]

| OL Relay| Contactor| 600Y/347V

[kA]

| OL Relay| Contactor
MO165-16| 65| EF19-18.9| AF09…AF38| 50| EF19-18.9| AF09…AF38
MO165-20| 65| EF45-30| AF26…AF38| 50| EF45-30| AF26…AF38
MO165-25| 65| EF45-30| AF26…AF38| 50| EF45-30| AF26…AF38
MO165-32| 65| EF45-45| AF26…AF38| 50| EF45-45| AF26…AF38
MO165-42| 65| EF65| AF40…AF65| 30| EF65| AF40…AF65
MO165-54| 65| EF65| AF40…AF65| 30| EF65| AF40…AF65
MO165-65| 65| EF65| AF40…AF65| 30| EF65| AF40…AF65
MO165-73| 50| EF96| AF80…AF96| –| –| –
MO165-80| 50| EF96| AF80…AF96| –| –| –

Combination Motor Controller Type F

Type 1 Coordination

Type| 480Y/277V

[kA]

| OL Relay| Contactor| 600Y/347V

[kA]

| OL Relay| Contactor
MO165-16| 65| TF42| AF09…AF38| 30| TF42| AF09…AF38
MO165-20| 65| TF42| AF26…AF38| 30| TF42| AF09…AF38
MO165-25| 65| TF42| AF26…AF38| 50| TF42| AF26…AF38
MO165-32| 65| TF42| AF26…AF38| 50| TF42| AF26…AF38
MO165-42| 65| TF65| AF40…AF65| 30| TF65| AF40…AF65
MO165-54| 65| TF65| AF40…AF65| 30| TF65| AF40…AF65
MO165-65| 65| TF65| AF40…AF65| 30| TF65| AF40…AF65
MO165-73| 50| TF96| AF80…AF96| –| –| –
MO165-80| 50| TF96| AF80…AF96| –| –| –

Combination Motor Controller Type F

Type 2 Coordination

Type| 480Y/277V

[kA]

| OL Relay| Contactor| 600Y/347V

[kA]

| OL Relay| Contactor
MO165-73| 50| EF96| AF80…AF96| –| –| –
MO165-80| 50| EF96| AF80…AF96| –| –| –

Combination Motor Controller Type F

Type 2 Coordination

Type| 480Y/277V

[kA]

| OL Relay| Contactor| 600Y/347V

[kA]

| OL Relay| Contactor
MO165-73| 50| TF96| AF80…AF96| –| –| –
MO165-80| 50| TF96| AF80…AF96| –| –| –

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>