TERACOM TSM400-1-TH Temperature and Humidity Sensor User Manual
- June 12, 2024
- TERACOM
Table of Contents
TSM400-1-TH Temperature and Humidity Sensor
User Manual
TSM400-1-TH Temperature and Humidity Sensor
Short description
TSM400-1-TH is a temperature and humidity sensor that supports the 1-Wire
protocol. A unique capacitive element is used for measuring relative humidity
while the temperature is measured by a band gap sensor. Both sensors are
seamlessly coupled to a 12-bit analog to digital converter. This results in
superior signal quality.
The TSM400-4-TH sensor is housed in a slim plastic enclosure. The bottom part
of the enclosure is suitable for installation on standard flush-mounted/cavity
wall boxes ø68mm, with installation openings on 61 mm.
Features
- LED indicator for status of communication
- Excellent long-term stability
- Firmware update with Turaco controller via the 1-Wire interface
Applications
- Environmental quality monitoring and assessment for offices.
- Humidity and temperature monitoring in building management systems.
- Smart ventilation systems.
Specifications
-
Physical characteristics
Dimensions: 81 x 81 x 30 mm
Weight: 66 g -
Environmental limits
Operating temperature range: -20 to 60°C
Operating relative humidity range: 5 to 95% (non-condensing)
Storage temperature range: -20 to 60°C
Storage relative humidity range: 5 to 95% (non-condensing)
Ingress protection: IP20 -
Power requirements
Operating voltage range (including -15/+20% according to IEC 62368-1): 4.5 to 26 VDC
Current consumption: 10 mA@5VDC -
Humidity measurements
Accuracy (min): ±3.0 %RH (in 20 to 80 %RH range)
Accuracy (max): ±5.0 %RH (in 5 to 95 %RH range)
Resolution: 0.1 %RH
Recommended operating range is 20% to 80% RH (non-condensing) over –10 °C to 60 °C
Prolonged operation beyond these ranges may result in a shift of sensor reading, with slow recovery time. -
Temperature measurements
Accuracy (min): ±0.4 °C (in -10 to +60°C range)
Accuracy (max): ±0.6 °C (in -20 to +60°C range)
Resolution: 0.1 °C -
Warranty
Warranty period: 3 years
Pinout
| Pin| Description| UTP wires color
---|---|---|---
1-W| 1-Wire data| Green
+5÷30V| Positive power supply| Orange
GND| Ground (negative) supply| Green/White tracer Orange/White Tracer
A+| Not used|
B-| Not used|
TERM| Not used|
Installation
It is strongly recommended to use UTP/FTP cables and daisy-chained (linear) topology for multiple sensors and keep the total cable length up to 30 meters.
“Star” topology can be used only as a last resort for up to 4 sensors and a total cable length of up to 10 meters.
Status indicator
The status of the device is shown by a single LED, located inside the box:
- If the LED blinks for a period of 1 second, the sensor works properly;
- If the LED blinks for a period of 3 seconds, there isn‘t communication with the controller;
- If the LED doesn’t blink, there isn’t a power supply.
Installation tips
The location and the mounting position of sensors have a direct effect on the accuracy of the measurements. The tips below will ensure good measuring results:
- The sensor shall be installed about 1.2-1.4 m above the floor;
- To avoid solar radiation, the sensor should not be installed next to windows or directly in the sunlight;
- The sensors shall be installed in a place with sufficient air circulation.
1-Wire is a registered trademark of Maxim Integrated Products, Inc. It is
strongly recommended to read Maxim’s 1-Wire tips at
https://teracomsystems.com/wp-content/uploads/AN148.pdf .
TSM400-1-TH sensor is intended for installation on a cavity wall box with 68mm
diameter and 61 mm screw spacing.
9. Firmware update
The firmware of the sensor can be updated with any Turaco controller which supports a 1-Wire interface. For more details ask your dealer.
Recycling
Recycle all applicable material.
Do not dispose of regular household refuse.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>