Installation Instructions:

  1. Install fixture into ceiling cavity using universal mounting bracket which has slot openings for C-Channel, flat bar, wood joist bar hanger (ordered separately) and 1/2” EMT (by others). Secure to joist or grid using fasteners or wire. C-Channel hangers are recommended for T-Bar ceilings, install with notches facing down to engage T-Bar grid.

  2. Mounting bracket includes a wing nut to adjust fixture to accommodate different ceiling thickness or ceiling construction .

  3. Remove junction box cover plate. Remove desired knockout, the junction box will accept metal conduit or non-metallic cable.

  4. Connect black wire from fixture to black (HOT) supply wire, white wire from fixture to white (NEUTRAL) supply wire and connect the ground from fixture to green (GROUND) supply wire. Use UL listed connectors or wire nuts to make the connections (not included).

  5. Make connections in junction box and replace cover plate.

  6. Squeeze torsion springs on trim and insert into bracket in housing.

  7. Once all fixtures have been installed, power at the breaker can be restored.

Wiring & Dimming Compatibility:

This product can be used with all Intense Lighting products with supported dimming options. Please check the configuration of the product for the correct dimming protocol. The product is compatible with a variety of dimmers from different manufacturers. Consult the dimming manufacturer for installation instructions.
Phase Dimming or Lutron® LTEA2W Hi-Lume 2-Wire

  • 120V Only
  • Forward 1% / Reverse 5%

Compatible Dimmers:

Product         Part Number(s )           Type

Leviton        IPE04                        Reverse

Leviton        IPI06-1LZ                Forward

Leviton        6633-P                     Forward

Lutron         DVELV300P           Reverse

Lutron         DVCL-153P             Forward

Lutron         S600P                      Forward

Cooper        DLC03P                   Forward

Cooper        DAL06P                     ForwardIntense Lighting IHOL-6DS
Gravity High Lumen Square Downlight 5

0-10V Dimming

  • 120V or 277V
  • Dims down to 1% or 0.1% light output
  • Consult dimming manufacturer for installation instructions and power packs

Compatible Dimmers:

Manufacturer Part Number(s)
HUNT PS-010-IV-120V, PS-010-WH-120V, PS-010-3W-IV-120,

PS-010-3W-WH-120V, PS-010-IV-277V, PS-010-WH-277V,
PS-010-3W-IV-277V, PS-010-3W-WH-277V, FD-010: PS-IFC-010-IV,
PS-IFC-010-WH-120/277V, FD-010: PS-IFC-010-3W-IV,
PS-IFC-010-3W-WH-120/277V, FD-010-120V, FD-010-277V
Leviton| Centura Fluorescent Control System, IllumaTechTM IP7 Series,
DPSPE-212
Lightolier| ZP600FAM120, MP1500FAM120, V2000FAMU
Lithonia| LEQ BC, LEQ LVBC, SLD LVBC, SQ1DC
Lutron| DVTV, NTFTV
Synergy| ISD BC 120/277

Intense Lighting IHOL-6DS Gravity High Lumen Square Downlight
6

Lutron® LDE1 Hi-Lume EcoSystem

  • 120V or 277V
  • Dims down to 1%
  • Consult dimming manufacturer for installation instructions

Compatible Dimmers:

Product                       Part Number(s )

EcoSystem                CS-1L-WM, CS-2L-WM, CS-1L-CM, CS-2L-CM, EcoSystem ESN, Grafik Eye QS with EcoSystem, Quantum
Intense Lighting IHOL-6DS Gravity High Lumen Square Downlight
7
DMX512 RDM (Downlights with RJ45)

  • 120V or 277V
  • Dims Down to 0.1% Light Output
  • RDM Channel ProgrammableIntense Lighting IHOL-6DS Gravity High Lumen Square Downlight 8

DMX512 RDM (Cylinders without RJ45)

  • 120V or 277V
  • Dims Down to 0.1% Light Output
  • RDM Channel ProgrammableIntense Lighting IHOL-6DS Gravity High Lumen Square Downlight 9

0-10V With Dynamic Beam

  • 120V or 277V
  • Dims down to 1% or 0.1% light output
  • Consult dimming manufacturer for installation instructions and power packs

Compatible Dimmers:

Manufacturer Part Number(s)
HUNT PS-010-IV-120V, PS-010-WH-120V, PS-010-3W-IV-120,

PS-010-3W-WH-120V, PS-010-IV-277V, PS-010-WH-277V,
PS-010-3W-IV-277V, PS-010-3W-WH-277V, FD-010: PS-IFC-010-IV,
PS-IFC-010-WH-120/277V, FD-010: PS-IFC-010-3W-IV,
PS-IFC-010-3W-WH-120/277V, FD-010-120V, FD-010-277V
Leviton| Centura Fluorescent Control System, IllumaTechTM IP7 Series,
DPSPE-212
Lightolier| ZP600FAM120, MP1500FAM120, V2000FAMU
Lithonia| LEQ BC, LEQ LVBC, SLD LVBC, SQ1DC
Lutron| DVTV, NTFTV
Synergy| ISD BC 120/277

Intense Lighting IHOL-6DS Gravity High Lumen Square Downlight
10

0-10V With Tunable White

  • 120V or 277V
  • Dims down to 1% or 0.1% light output
  • Consult dimming manufacturer for installation instructions and power packs

Compatible Dimmers:

Manufacturer Part Number(s)
HUNT PS-010-IV-120V, PS-010-WH-120V, PS-010-3W-IV-120,

PS-010-3W-WH-120V, PS-010-IV-277V, PS-010-WH-277V,
PS-010-3W-IV-277V, PS-010-3W-WH-277V, FD-010: PS-IFC-010-IV,
PS-IFC-010-WH-120/277V, FD-010: PS-IFC-010-3W-IV,
PS-IFC-010-3W-WH-120/277V, FD-010-120V, FD-010-277V
Leviton| Centura Fluorescent Control System, IllumaTechTM IP7 Series,
DPSPE-212
Lightolier| ZP600FAM120, MP1500FAM120, V2000FAMU
Lithonia| LEQ BC, LEQ LVBC, SLD LVBC, SQ1DC
Lutron| DVTV, NTFTV
Synergy| ISD BC 120/277

Intense Lighting IHOL-6DS Gravity High Lumen Square Downlight
11

DALI With Tunable White

  • 120V or 277V
  • Dims down to 0.1%Intense Lighting IHOL-6DS Gravity High Lumen Square Downlight 12

IMPORTANT SAFETY INSTRUCTIONS

  • Read all installation instructions before installing. It is important to save these instructions.
  • Observe and follow all label information and instructions regarding dry, damp and wet location listings, proper Intense LED module, warnings of installation near combustible materials and/or insulation.
  • Turn off power at circuit breaker before attempting to install or perform maintenance on the fixtures.
  • Be sure to connect ground wire to prevent electric shock or other potential hazards.
  • The product must be installed in a manner consistent with the intended use and in compliance with the national electrical codes and local codes.
  • Do not block the trim aperture as this may cause unsafe operating conditions.
  • WARNING: RISK OF FIRE. Non-IC fixture requires that insulation must be kept at least 3” away from all sides of the fixture. Minimum of 90°C supply conductors. Consult a qualified electrician before installation.

WARNING: Use only Intense Lighting trims listed for use with this fixture. Use of trims other than those listed by Intense Lighting is a violation of N.E.C 110-3(B) and voids all warranties. INSTALLATION INSTRUCTIONS
INTENSE LIGHTING | 3340 E La Palma Ave, Anaheim, CA 92806
tel 714 630-9877
fax 714 630-9883
For Intense Lighting’s limited product warranty, go to www.intenselighting.com. For a printed copy of the warranty, you may call 800 961-5321. © 2022 Intense Lighting, LLC. All rights reserved. Note: This document is subject to change without notice.

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals