Emerson 1F83C-11NP Non-Programmable Thermostats Operating Manual

October 30, 2023
Emerson

Emerson 1F83C-11NP Non-Programmable Thermostats

Emerson 1F83C-11NP Non-Programmable- Thermostats  -PRO

View all Emerson thermostat manual

SPECIFICATIONS

Electrical Rating:

  • Battery Power……………………………….. mV to 30 VAC, NEC Class II, 50/60 Hz
  • Input-Hardwire………………………………. 20 to 30 VAC, NEC Class II, 50/60 Hz
  • Terminal Load……………………………………. 1.0 A per terminal, 1.5A maximum all terminals combined
  • Setpoint Range………………………………….. 45° to 99° F (7° to 37° C)
  • Rated Differentials: Fast Med Slow
  • Heat (@ 6°F/ Hr)…………………………….. 0.5°F 0.75°F 1.9°F
  • Cool (@ 6°F/ Hr)…………………………….. 0.9°F 1.2°F 1.7°F
  • Operating Ambient…………………………….. 32°F to +105°F (0° to +41°C)
  • Display Temperature Range…………………… 32°F to +99°F (0 to 37°C)
  • Operating Humidity……………………………. 90% non-condensing max
  • Shipping Temperature Range……………….. -20°F to + 150°F (-29° to +65°C)
  • Thermostat Dimensions………………………. 3-3/4” H x 6” W x 1-1/8” D

MERCURY NOTICE : This product does not contain mercury. However, this product may replace a product that contains mercury. Mercury and products containing mercury must not be discarded in household trash. Refer to www .thermostat-recycle.org for information on disposing of products containing mercury.

Thermostat   Applications Maximum   Stages   Heat/Cool

Conventional Gas, Oil, Electric (mV and 24V), Heat Only, Cool Only or Heat/ Cool Systems| 1/1
Heat Pump (air source or geothermal) with no Aux. Heat| 1/1

THERMOSTAT INSTALLATION

WIRING
Refer to equipment manufacturer’s instructions for specific system wiring information. After wiring, see INSTALLER MENU for proper thermostat configuration. Wiring table shown are for typical systems and describe the thermostat terminal functions

Terminal   Designations Terminal   Function
RC* Power for Cooling
RH* Power for Heating
O/B Changeover Terminal-Energized in Heat (B) or Cool (O) for Heat Pump or

Damper Systems
Y| Cooling Relay
G| Fan Relay
W
| Heating Relay
C| Common wire for 24V (optional with batteries)

When both RC and RH wires are present, cut RC/RH jumper (see next page). For heat pump systems, add a jumper wire to connect terminals Y and WEmerson-
1F83C-11NP- Non-Programmable- Thermostats- 1

Precautions

  •  Do not exceed the specification ratings.
  •  All wiring must conform to local and national electrical codes and ordinances.
  •  This control is a precision instrument, and should be handled carefully. Rough handing or distorting components could cause the control to malfunction.

Emerson- 1F83C-11NP- Non-Programmable- Thermostats- 2

Gas/Elec Switch
If the system is a heat pump or electric furnace, the GAS/ELEC Switch must be set to Elec. If your system is a gas or oil furnace, the switch must be set to Gas.

O/B Terminal Switch
The O/B switch on this thermostat is factory set to the O position. This will accommodate the majority of heat pump applications, which require the changeover relay to be energized in Cool. If the heat pump being installed requires a B terminal, to energize the changeover relay in Heat, the O/B switch must be moved to the B position.

RC/RH Jumper Wire
This thermostat electrically connects the RC and RH terminals so a jumper wire is not required. If the application provides a separate wire for RC and RH, clip the RC/RH jumper. This will isolate both terminals so they can be independently used

INSTALLER MENU

To prevent changes that may affect system performance, this thermostat has an INSTALLER’S MENU and an USER MENU. The INSTALLER’S MENU provides access to every option, while the USER MENU provides access to items that will not affect system performance. To access the INSTALLER’S MENU press the Menu button for 8 seconds. The display will show item 30 in the table below. Use Next and Back to navigate through menu items. Press or to change a menu setting.

Installer’s Menu # (Hold Menu 8 Seconds)| Description| Default Setting (flashing icons)| Settings ( Press   )
---|---|---|---
30| Heat   Cycle   Rate  (how often the heat will turn on)| MEd| SLO – slow MEd – medium FAS – fast
35| Cool Cycle Rate (how often the cooling will turn on)| MEd| SLO – slow MEd – medium FAS – fast
50| Compressor Lockout (protects the compressor from short cycling)| OFF| On – 5 minute display OFF – no delay
65| Maximum Heat Limit (maximum set point for heat mode)| 99| 47 to 99
66| Minimum Cool Limit (minimum set point for cool mode)| 45| 45 to 97
Installer’s Menu # (Hold Menu 8 Seconds)| Description| Default Setting (flashing icons)| Settings
---|---|---|---
79| Fahrenheit or Celsius| °F| °F – Fahrenheit °C – Celsius
81| Temperature Display Adjustment (adjust the displayed “Room Temperature”)| **0| ****-5 to +5
83| Continuous Display Light (keep the backlight always on – “C” wire required)| ****OFF| On – always on OFF – momentarily
99| Keypad Lock (prevent unwanted changes to the thermostat)| ****OFF| On – disable buttons OFF** – all buttons are

active

TEST EQUIPMENT

Turn on power to the system.

Fan Operation

  • If your system does not have a G terminal connection, skip to Heating System.
  • Move fan switch to On position. The blower should begin to operate.
  • Move fan switch to Auto position. The blower should stop immediately.

Heating System

  • Move System Switch to Heat position.
  • Press  to adjust thermostat setting to 1° above room temperature. The system should begin to operate and the thermostat will indicate Heat On.
  • Press  to adjust thermostat setting 1° below room temperature. The heating system should stop operating and the thermostat should indicate Heat.

Cooling System

  • Move System Switch to Cool position.
  • Press  to adjust thermostat setting 1° below room temperature. The blower should come on immediately on high speed, followed by cold air circulation. The thermostat will indicate Cool On. There can be up to a 5 minute delay. (see INSTALLER MENU, item 50)
  • Press  to adjust thermostat setting to 1° above room temperature. The cooling system should stop operating and the thermostat will indicate Cool.

USING THE THERMOSTAT

THERMOSTAT OVERVIEW
Before you begin using your thermostat, you should be familiar with its features, display and the location/operation of the thermostat buttons and switches.

THERMOSTAT BUTTONS AND SWITCHES THE DISPLAY
1.) Fan Switch 7.) Thermostat is protecting the equipment from short cycling

(5-minute delay)
2.) System Switch| 8.) Indicates that the system is running in cool or heat
3.) Backlight Button (located on the top of the thermostat| 9.) Battery status indicator
4.) Raises Temperature Setting| 10.) Low battery indicator *
5.) Access Menu Options| 11.) Temperature setpoint
6.) Lowers Temperature Setting| 12.) Appears when the keypad is locked (to prevent unwanted changes)
| 13.)  Next (Menu button) is used to navigate within a menu
| 14.)  SEE TROUBLESHOOTING

USER MENU
To customize thermostat settings, press and hold the Menu button for ½ second from the home screen. Use the Next button to advance through menu items. Press or to change the setting.

User’s Menu # (Press Menu button and release)| Description| Default Setting (flashing icons)| Settings (Press ** or  )
---|---|---|---
01| Continuous Display Light (keep the backlight always on – “C” wire required)| OFF| On – always on OFF** – momentarily

TROUBLESHOOTING

Symptom Possible   Cause Corrective   Action

No Heat/ No Cool/ No Fan

(common problem)

| 1.) Blown fuse or tripped circuit breaker2.) Furnace power switch to OFF

3.) Furnace blower compartment door panel loose or not properly installed

4.) Loose connection to

thermostat or system

| 1.) Replace fuse or reset breaker2.) Turn switch to ON

3.) Replace door panel in proper position to engage safety interlock or door switch

4.) Tighten Connections

No Heat

| 1.) System Switch not set to Heat2.) Loose connection to thermostat or system

3.) Heating System requires service or thermostat requires replacement

| Verify thermostat and system wires are securely attached.Diagnostic: Set System Switch to Heat and raise the setpoint above room temperature. Within five minutes the thermostat should make a soft click sound and “Heat On” should appear on display. This sound indicates the thermostat is operating properly. If the thermostat does not click, try the

reset operation listed below. If the thermostat does not click after being reset, contact your heating and cooling service person or place of purchase for a replacement. If the thermostat clicks, contact the furnace manufacturer or a service person to verify

the heating system is operating correctly.

No Cool

| 1.) System Switch not set to Cool2.) Loose connection to thermostat or system

3.) Cooling System requires service or thermostat requires replacement

| Verify thermostat and system wires are securely attached.Diagnostic: Set System Switch to Cool and lower setpoint below room temperature. Same procedures as diagnostic for “No Heat” condition except set the thermostat to Cool and lower the setpoint below the room temperature. There may be up to a five minute delay before the thermostat clicks in Cooling if the compressor lock-out option is selected in the installer

menu. (see INSTALLER MENU, item 50)

Heat, Cool or Fan Runs Constantly| Possible short in wiring, thermostat, heat, cool or fan system| Check each wire connection to verify they are not shorted or touching other wires. Try resetting the thermostat. If the condition persists contact your HVAC service person.
Thermostat Display & Thermometer Disagree| Thermostat display requires adjustment| Display can be adjusted +/-5°. See User Menu item

04

Symptom Possible   Cause Corrective   Action

Furnace (Air Conditioner) Cycles Too Fast or Slow (narrow or wide temperature swing)| **** The location of the thermostat and/or the size of the Heating System may be influencing the cycle rate| Digital thermostats provide precise control and cycle faster than older mechanical models. The system turns on and off more frequently but runs for a shorter time. If you would like to increase cycle time, choose SLO for slow cycle in the Installer menu. (Reference menu items 30 & 35) If an acceptable cycle rate is not achieved, contact your HVAC service person.






“Call for Service” icon appears on displayed

| 1.) Heating system is not able to heat the space to within 10 degrees of the setpoint within 2 hours2.) Cooling system is not able to cool the space to within 10 degrees of the setpoint within 2 hours

3.) If “–” is displayed for the Room Temperature, a replacement thermostat is needed

4.) None of the buttons operate on the thermostat

| 1.) See corrective action for “No Heat” ****


2.) See corrective action for “No Cool”



3.) Replace thermostat



4.) Make sure keypad lockout is not turned on

(denoted by  icon)

Emerson- 1F83C-11NP- Non-Programmable- Thermostats- 10

Resetting the Thermostat or Thermostat Settings
If the thermostat has good batteries, but has a blank display or does not respond to key presses, the thermostat should be reset by removing the batteries for 2 minutes. This reset will not change the menu settings. If the condition persists after reinstalling the batteries, replace the thermostat. To conveniently reset only the user settings back to factory defaults, press Menu and Backlight buttons at the same time and hold until the display goes blank and resets.

Emerson

  • HOMEOWNER HELP LINE: 1-800-284-2925
  • Emerson and White-Rodgers are trademarks of Emerson Electric Co. ©2020 Emerson Electric Co. All rights reserved.
  • emerson.com/white-rodgers

Emerson 1F83C-11NP Non-Programmable Thermostats Operating Manual

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Emerson User Manuals

Related Manuals