FILTER SYSTEMS AUSTRALIA GT7- 2K Water Sterilisation System User Manual

October 30, 2023
Filter Systems Australia

GT7- 2K / 4K / 8K / 9K / 16K
Ultraviolet System Manual

FILTER SYSTEMS AUSTRALIA GT7- 2K Water Sterilisation
System

Technical Overview

Important Notes
For correct operation of this appliance, it is essential to observe the manufacturer’s instructions.
This system is designed for permanent fixed installation as a POE or POU treatment system. Installation must be carried out by a qualified plumber or authorized technician to comply with Australian Plumbing Codes. This system contains electrical components and plumbing components; Use caution and if leaking occurs, turn the power off immediately before conducting maintenance or repair to the system.
This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety.
Children should be supervised to ensure that they do not play with the appliance.
If the supply cord is damaged, it must be replaced by a special cord or assembly available from the manufacturer or its service agent.
Specifications

Part Number GT7-2K GT7-4K GT7-8K GT7-9K GT7-16K
Flow Rate @ 30mJ/cm² 3.8L/Min 30L/Min 50L/Min 50L/Min 105L/Min
Voltage   230V – 240V
Chamber 304SS 316SS
Max Pressure   700 kPa
Working Pressure   500 kPa
Lamp Power 14W 20W 40W 40W 87W

WARNING
This appliance must be installed directly into a single socket surge protector before being connected to a 240V 10A General Power Outlet (Power Point). It must be a surge protector – Circuit Breakers and Residual Current Devices (RCDs) are not suitable substitutes as they do not protect the unit from power surges.
Danger: Dangerous electrical voltage is present inside the power supply box & chamber. These instructions must be followed closely to prevent serious personal injury. Ensure eye protection is worn when servicing and installing this unit to protect from harmful UV-C Radiation. This radiation can be harmful to eyes and skin, UV lamps should only be used when properly installed in the irradiation chamber. The UV lamp must not be operated outside the chamber.

  • This unit must be used only for its intended purpose as described by the manufacturer.

  • This unit must be installed in accordance with this manual.

  • The unit must be unplugged when; The unit is not in use, before fitting or removing any parts.
    o The unit must be electrically isolated before Maintenance, Cleaning or Lamp Replacement.

  • The System will need to be de-pressurized before maintenance.

  • The UV lamp is designed for continuous usage to reach full disinfection capacity. Frequently turning the system on/off will cause the lamp to reduce in effectiveness and may cause the lamp to fail.

Overheating: For long periods of no flow through a UV system, it is required to fit a Thermal Relief Valve (TRV) which can be purchased separately. Excessive build up of temperature in the chamber may cause the O-ring to deform and fail, causing leakage which can come into contact with the lamp/power supply causing damage or personal injury. Installing a UV system without a TRV may void warranty – check the Warranty details for further clarification.
Before you Purchase/Open
The system requires specific working conditions to be met before installation, some general guidelines* are listed below. If these conditions are not met, the system may not be suitable for the application and may not function as specified. These systems are designed for sanitising water supplies including mains water, tank water and in some cases bore water and other water supplies. UV dosage ratings are based on UVT 94% and pre-filtered to 5uM. For applications on any water supply other than rain water tanks and mains water, please contact the manufacturer to determine the correct system.

Feed Water Conditions Guideline Only Min Max
Inlet Pressure 100 kPa 500 kPa
TDS 0 mg/L 2,000 mg/L
Iron 0 mg/L 0.02 mg/L
Manganese 0 mg/L 0.01 mg/L
Hardness 0 mg/L 150 mg/L

Space Requirements
The Ultraviolet systems are not IP rated, therefore are not suitable for external installation without adequate weatherproofing or cover from the elements including but not limited to Rain/Moisture/High Humidity & Frost. For external installations, the ballast must be installed in an IP 65 or better waterproof enclosure (not supplied) OR installed in a suitable location not exposed to the previously mentioned elements.
The System is supplied with either plastic (GT7-2K) or Aluminium mounting clamps designed for installation on the wall (screws not included). It is ideal for the system to be mounted horizontally however if necessary, vertical installation (open end to the top) is acceptable, the outlet should also be at the top.
The chamber must be mounted so that the chamber remains full of water at all times. The ports should be facing up for a horizontal installation so that the air can escape from the chamber. You must allow enough space to perform maintenance on the system. Allow 2x the length of the chamber at the open end to allow the UV Lamp & Thimble to be installed/removed. When mounting the chamber, consideration must be made for the weight of the system being full of water due to the stresses associated with the plumbing fixings. The stainless- steel chamber and surrounding plumbing must be earthed to prevent electrolysis (which will cause corrosion).
What is Ultraviolet Sanitation
Ultraviolet sanitation works by breaking down the cell wall of a micro- organism allowing oxidation to occur which in turn prevents the bacteria from multiplying until it is finally eradicated. Ultraviolet filtration is a chemical free solution to water sanitation creating no by products in the water.
Ultraviolet systems are rated based on a dosage level of radiation into the water (mJ/cm²) with 30mJ being the standard level of disinfection and up to 40mJ for Australian Drinking Water Guidelines.
For drinking water and domestic water use, a UV system should always be installed as the last point of contact. For example, on a whole house filtration system, the filters should be installed before the UV system. This effectively eliminates (or significantly reduces) the chances of re- contamination after the UV unit.
Example Applications
UV systems are utilized in many different ways. The main applications are Household Water Filtration, Commercial Water Treatment & Bacterial Pre- Treatment.
Household Water Filtration generally comes in 2 forms: Under sink Point of Use filtration or Whole House Point of Entry filtration. Both applications are set up the same, with a pre filter followed by the UV system as a final point of contact.
Commercial Water Treatment is common due to council regulations governing the supply or water or food to the public. The law requires a form of sanitation in the filtration process and this is usually done in the form of UV, RO or UF filtration.
Bacterial Pre-Treatment is sometimes required as a pre-treatment stage for ultra-fine (UF) or Reverse Osmosis (RO) systems to prevent possible bio- fouling. UV can treat higher levels of bacteria to reduce the chance of this occurring.

Installation Introductions

Site Preparation
When a suitable installation location is identified, you will need to determine if the system will be mounted horizontally as recommended, or vertically if necessary (if mounting vertically, the outlet will need to be at the top and a Thermal Relief Valve is required). Allow adequate space for the ongoing maintenance and pre-plan the plumbing so that the ports will be facing up.
Mounting
When mounting the system on a wall, mark out the approx. location of each wall bracket. Fix a bracket to the wall and using a level and ruler, mark out the appropriate location for the second bracket. Brackets should ideally have the pivot/hinge at the bottom and screw to close the bracket at the top. Hold the Chamber in firmly to the brackets and they do up one of the clamps to secure the system. A second set of hands can assist to make this easier.
Installing Connections
The UV systems are manufactured with male BSP threads either in 1” (GT7-8K/9K/16K) or ½” (GT7-4K). The smaller GT7-2K unit is ¼” Female. Use appropriate plumbing fittings to install onto the chamber for adapting to your plumbing.
Thermal Relief Valve
A Thermal Relief Valve is a valve with a build in sensor that will open and drain water once the temperature in the chamber reaches 56°C. A Thermal Relief Valve is recommended on installations where there can be prolonged periods of time without water flow. Generally lower wattage systems (less than 40W) do not reach extreme temperatures under normal conditions; however, it is best to install a TRV to limit the temperature.
When installing a TRV, note the below requirements:

  • The TRV must be installed on the Outlet of the UV System (which should be the open end).
  • The TRV tube must be allowed to drain freely without head pressure (don’t run the tubing vertically).
  • The TRV operates from temperature so always have the ports facing up (heat rises).
  • When vertical system installation is required, make sure the valve itself is also facing up.

The valve will open at 56°C and Close at ~ 54 – 55°C, if you have a pump without a bladder and a very sensitive high/low pressure switch, you may notice the pump cycling as the valve activates/deactivates during prolonged periods without flow.
Filter Protection
As per Australian Plumbing Codes, a pressure limiting valve should be installed to limit the pressure to 500 kPa when the feed pressure exceeds 500 kPa. If Water Hammer is present, install a suitable Water  Hammer Arresting device.

Commissioning & Start-up

Quartz Thimble Installation
Due to the fragile nature of the quartz, care must be taken when handling and installing the thimble and lamp. The below steps are for horizontal installations.

  1. Remove the knurled nut (see picture to right) from the end of the SS chamber.
  2. Wearing clean gloves or handling with a micro-fiber cloth, remove the glass thimble from packaging and check for any marks or blemishes. Slowly and carefully insert the thimble into the chamber at the open end (see picture to right). DO NOT DROP THE THIMBLE INSIDE THE CHAMBER AS IT WILL SHATTER. The thimble will need to go into the chamber via the domed (closed) end first. At the rounded (domed) end of the SS UV chamber, you will find a port to accommodate the domed end of the quartz tube. Carefully maneuver the quartz thimble into this port so the thimble is securely seated.
  3. Place the O-ring over the exposed end of the glass thimble and seat the O-ring firmly against the thread (see picture below). Knurled Nut
  4. When the o-ring is seated, gently screw the knurled nut onto the thread of the chamber. This will seal the o-ring against the sealing nut. NOTE: Firmly hand tightening is sufficient to seal these chambers without the use of tools – DO NOT APPLY THREAD TAPE OR SEALANT GLUE TO THE END THREADS. Caution: Overtightening the knurled nut may cause the glassware to crack. You can look through the open end of the nut (or feel with your finger) to check if the o-ring and thimble are seated correctly (per the below picture). There should be a small gap between the end edge of the thimble and the recessed stop-end of the knurled nut as shown below. NOTE: There should be no contact between the end of the glass thimble, and the recessed inner of the knurled nut. If there is no gap (ie. metal on glass), totally unscrew the knurled nut and ensure the thimble is correctly seated before proceeding.FILTER SYSTEMS AUSTRALIA GT7- 2K Water Sterilisation System - Start-up4
    5. From this point, the water supply should be turned on to pressurise the chamber and identify if there are any leaks from the plumbing connections or from the thimble. Take the time to check this before continuing. If leaking occurs from the thimble, it is possible that this may be a slow beading leak, which must to be rectified before installing the lamp. The thimble should be bone dry before the UV lamp is installed. If any water is present in or around the thimble or chamber from the installation process, it will need to be thoroughly dried and the leak fixed before continuing with the installation.
    NOTE: Damage caused by leaking or defective installation is not covered under warranty.
    6. For vertical installations, it is extremely important that there are no slow leaks, as over time, these will fill up the thimble with water and cause a short in the lamp, which can result in injury or damage to the lamp & ballast. This is not covered under warranty.

Ballast/Power Source Operation
GT7-8K-PS & GT7-9K-PS – The 10W – 40W ballast features straightforward operation. It features a lamp status & failure indicator light along with an audible alarm should there be a fault. The ballast will automatically reset when turned on/off.
WORKING CONDITIONS:
The Lamp and Ballast are working correctly when the Green LED Indicator Light shows:

FILTER SYSTEMS AUSTRALIA GT7- 2K Water Sterilisation System - Indicator
Light

ERROR/FAULT CONDITIONS (LAMP FAILURE):
× The Lamp and/or Ballast have failed when the Red LED Indicator Light shows and/or the system is alarming. Whilst it is usually the lamp that requires replacement, please refer to the Troubleshooting section of this guide to diagnose which element requires replacement.

FILTER SYSTEMS AUSTRALIA GT7- 2K Water Sterilisation System - Indicator
Light1

GT7-16K-PS – In order to guarantee user safety, this ballast features complete control and protection functions which are caused by;

  1. UV Lamp exceeding life cycle (365 Days).
  2. UV Lamp Failure.
  3. Working beyond rated voltage and load.

This ballast is designed to work with germicidal UV lamps. Do not mistake the input/output wire to avoid ballast failure.

  • Ensure the voltage is within the specification of the ballast.
  • Match the UV lamp with the power output of the ballast.
  • Ensure the connections (plugs) are fitted correctly – the earth wire must be affixed securely.

WORKING CONDITIONS:
The Lamp and Ballast are working correctly when the Green LED Indicator Light shows:

FILTER SYSTEMS AUSTRALIA GT7- 2K Water Sterilisation System - Indicator
Light2

Display Screen – Press the “SELECT” button (for 2 seconds) to toggle between the Lamp Life Remaining (Days) Default Display Screen and the Total Running (Days) Ballast Operation Time:
Lamp Life Remaining (Days) Default Display Screen – By default, the display screen will show the lamp life, which counts down from 0365 to 0 days. Once the lamp life timer reaches 0, the ballast will alarm to remind you to change the lamp.
Total Running (Days) Ballast Operation Time – Press the switch button (for up to 2 seconds) to display the ballast operation time, which counts up from 0 to 9999 days. After 10 seconds the screen will return to the default display.
LAMP REPLACEMENT DUE:
End of Lamp Life/UV Lamp Replacement Alarm: Once the Lamp Life Remaining timer reaches day 0, the digital display will show “A3”, the Red LED Error light will flash and an audible alarm will sound (beeping). This indicates that it is time to replace your UV lamp.

FILTER SYSTEMS AUSTRALIA GT7- 2K Water Sterilisation System - LED
Indicator

Temporary (7 Day) Alarm Pause/Cancellation: If the UV lamp cannot be immediately replaced, you can temporarily pause the alarm by pressing the “SELECT” button for 5 seconds until the buzzer sound stops. This will reset the Lamp Life Remaining display to 7 days, however, the display will continue to show “A3” and the Red Error LED Light will still show. Once those 7 days are up (i.e. lamp life reaches 0), the alarm will re-start. The ballast will provide 4x 7-Day alarm cancellations (for a total of 28 days), after which point the alarm will alarm will not stop until the lamp is replaced.

FILTER SYSTEMS AUSTRALIA GT7- 2K Water Sterilisation System - LED
Indicator1

Lamp Change/Ballast Reset:
Disconnect the power supply (See Part III: Installing New Lamp for detailed instructions on changing the Lamp).
  Remove the expired/failed lamp, and install the new lamp.
  Press and hold the “SELECT” button for 10 seconds until the display shows “RSET”. Continue holding for a further 5 seconds until the display shows “0365” and you will hear an audible beep. Release the button and the timer is successfully reset.

FILTER SYSTEMS AUSTRALIA GT7- 2K Water Sterilisation System - LED
Indicator2

ERROR/FAULT CONDITIONS:
Whilst it is usually the lamp that requires replacement, please refer to the below guidance along with the Troubleshooting section of this guide to diagnose which element requires replacement.
× LAMP FAILURE: The Lamp has failed when the Red LED Indicator Light shows and/or the system is alarming. Note: The Lamp Life will display “0”, but the Total Running (Days) count will continue.

FILTER SYSTEMS AUSTRALIA GT7- 2K Water Sterilisation System - LED
Indicator3

× BALLAST FAILURE: The display will be blank if the ballast has failed.
Installing the UV Lamp
When, and only when the chamber and thimble are deemed to be water-tight and free of leaks, can the lamp be installed. Handle the lamp only by the plastic end caps, and support it by both ends.

  1. Before the lamp is installed, the chamber and surrounding plumbing must be dry and free from water or leaks. Plug the ballast (power supply) into a certified single socket surge protector, then into a 240V 10A GPO. Ensure the ballast (power supply) is turned  OFF at the wall. Note: No warranty will be covered for a blown lamp if the ballast is not plugged directly into a surge protector.

  2. FOR THE GT7-16K SYSTEM ONLY – Connect (screw) the earth wire to the lug on the bottom of ballast (power source) as shown below.FILTER SYSTEMS AUSTRALIA GT7- 2K Water Sterilisation System - bottom

  3. Remove the lamp from its protective wrapping.

  4. Insert the UV lamp into the quartz thimble through the open end (see picture below). Leave the 4 pins of the lamp exposed to allow connection to the ballast. NOTE: For vertical installation, you will need to connect the power supply first before lowering the tube into the chamber. Do NOT drop the tube down into the thimble chamber, as this will cause the thimble to crack.FILTER SYSTEMS AUSTRALIA GT7- 2K Water Sterilisation System - thimble chamber

  5. Firmly hold the white cap of the UV lamp and the connection of the Ballast (see pictures below),  then push (wiggle) the power supply connection onto the UV lamp pins.
    NOTE: There is a long and short side of the pins so they will only go into the power supply one way. Ensure that this is connected firmly so there is a good connection.FILTER SYSTEMS AUSTRALIA GT7- 2K Water Sterilisation
System - lamp

  6. Next, connect the earth wire to the lug on the bottom of the UV chamber as shown below.FILTER SYSTEMS AUSTRALIA GT7- 2K Water Sterilisation System - lamp1

  7. At this point the lamp should be tested briefly to ensure it is in working order and the connection is sound.
    a. Keep your hands clear of the system and turn on the power for 5 seconds to allow the lamp to illuminate. Do not look directly at the lamp without eye protection.
    b. Confirm that the lamp lights up correctly, and the ballast is showing a green light to signify that the lamp is running correctly.
    c. Turn off the power.

  8. Slide the lamp the remaining way into the chamber, until the white cap sits on top (if 7-16K), (or gently wiggling the black rubber cap or over the stainless-steel knurled nut (see pictures below).
    NOTE: The rubber boot/white cap is not a waterproof seal and is not designed to seal the water in the chamber, it is only to hold the lamp in place and protect from slight splashing water – this does not make the chamber IP rated as waterproof.FILTER SYSTEMS AUSTRALIA GT7- 2K Water Sterilisation
System - lamp3

  9. Turn on the power supply to start the lamp.
    a. If there is a green light, everything is running correctly.
    b. If there is a red flashing light with an audible alarm sounding, the ballast is indicating that there is a problem with the lamp. This may be due to a faulty lamp, the connection was not sound during installation, or there may possibly be a water leak that is shorting out the lamp.
    c. Fix the issue if possible or contact the supplier for further information.

Maintenance

Replacement Parts
Ultraviolet systems are rated based on a dosage level of UV-C radiation into the water (mJ/cm²), with 30mJ/cm² being the standard level of disinfection and a minimum dose of 40mJ/cm² required to comply with Australian Drinking Water Guidelines. Ultraviolet Lamps are rated with a 9000-hour (1 year) lifespan, after which point the lamp will naturally degrade and the level of radiation produced by the lamp cannot be guaranteed. They are designed for continuous run, not for intermittent operation.
The UV lamp sits inside a quartz thimble, which protects the electrical components of the lamp from making contact with the water. We specifically use quartz (fused silica) for this application because it is strong, exhibits thermal resistance, and has excellent UV transmission properties. However, over time, metal ions fused within the silica structure of the quartz thimble interfere with the UV-C radiation produced by the lamp, which reduces the UV transparency of the glass and causes it to become fragile. This process is called polarization.
Tannin, bio-film, algae, and scale can also build up on the outside of the glass thimble, further preventing ultraviolet light produced by the lamp from penetrating through the thimble, and impairing the system’s ability to sanities the water passing through.
Thus, we recommend replacing the lamp every 12 months, and the thimble every 1-2 years.
Lamp Replacement | Every 12 Months

GT7-2K-Lamp 14W Replacement UV Lamp Suit GT7-2K
GT7-4K-Lamp 20W Replacement UV Lamp Suit GT7-4K
GT7-8K-Lamp 40W Replacement UV Lamp Suit GT7-8K
GT7-9K-Lamp 40W Replacement UV Lamp Suit GT7-9K
GT7-16K-Lamp 87W HO Replacement UV Lamp Suit GT7-16K
GT7-2K-Thimble 331mm x 23mm OD Single Open-End Thimble Suit GT7-2K
--- ---
GT7-4K-Thimble 490mm x 23mm OD Single Open-End Thimble Suit GT7-4K
GT7-8K-Thimble 895mm x 24.5mm OD Single Open-End Thimble Suit GT7-8K
GT7-9K-Thimble 895mm x 23mm OD Single Open-End Thimble Suit GT7-9K
GT7-16K-Thimble 895mm x 23mm OD Single Open-End Thimble Suit GT7-16K

O-Rings | Every 1 – 2 Years, must be changed if installing a new quartz

GT7-2NSF-OR O-Ring Suit 23mm Thimble (GT7-2K, GT7-4K, GT7-9K & GT7-16K)
GT7-8NSF-OR O-Ring Suit 24.5mm Thimble (GT7-8K)

Replacement Ballast | Replace after 5 years as a precaution

GT7-8K-PS 10W – 40W AU Certified (RCM) Ballast to Suit 4 Pin Lamps
GT7-9K-PS 10W – 55W AU Certified (RCM) Ballast to Suit 4 Pin Lamps
GT7-16K-PS 33W – 120W AU Certified (RCM) Ballast to Suit 4 Pin Lamps

Mounting Clamps

GT11-8G 1 PC Plastic Mounting Clamp Suitable for U/Sink Installation.
GT7-8-BRK 1 Pair Aluminium Mounting Brackets Suit GT7-4K GT7-8K GT7-9K

GT7-16K

Thermal Relief Valves

GT7-53 ¾” F-F BSP Thermal Relief Valve – 316SS + 2m Drain Tubing
GT7-51 1” F-F BSP Thermal Relief Valve – 316SS + 2m Drain Tubing
GT7-52 2” F-F BSP Thermal Relief Valve – 316SS + 2m Drain Tubing

Troubleshooting

Problem Possible Cause(s) Solution
Leaking from Chamber 1.  O-Rings Not Seated

2.  Knurled Nut Too Loose
3.  Damaged Thimble| 1. If there is any issue with the O-ring in the way they are seated this will need to be fixed. Remove the thimble and repeat steps 3 – 5.
2. If the nut is not tight enough, the O-rings will not have good enough compression and will cause a leak. Slightly tighten up the nut until a watertight seal is achieved. It is better to tighten slightly at a time to prevent overtightening.
3. If there is a crack or hole in the thimble, it will fill from the inside out. Turn off the water, disconnect the power, carefully remove the thimble and replace with a new one. If the thimble releases shards of glass, the chamber and downstream plumbing will need to be thoroughly checked. All glass shards must be removed before re-connection.
High Water Temperature| 1.  Low Flow Rate
2.  Oversized System| 1. Particularly on the smaller model (GT7-2K), if there are periods of low water usage or the water is allowed to stand for long periods of time, the water may be prone to heating up and may be either lukewarm or hot. Generally, this only occurs on systems that have a short distance between the outlet and point of use. Whole house systems have a larger length of cold plumbing pipes downstream which will dissipate this heat.
2. If the system is too large for the application, it is likely that even with frequent water usage, the water does not get a chance to cool down effectively. If there are significant fluctuations in usage or flow rates, it is good practice to install a thermal relief valve (sold separately) on the outlet of the UV chamber which can bleed water from the chamber and keep temperatures below 56°C.
Hot SS Chamber| 1. Low Usage| 1. As above, if the water is allowed to stand for periods of time, the chamber will heat up naturally. This is normal, however if the heating is excessive to the point where it is causing damage to the chamber or surrounding fixtures, a thermal relief valve (sold separately) should be installed on the outlet of the UV chamber, to bleed water from the chamber and keep temperatures below 56°C.
Ballast is Alarming| 1.  Lamp Failure
2.  False Alarm| 1. Usually if the ballast is alarming and showing a red flashing status indicating light, the lamp has failed and will require replacement. Before replacing a lamp, it is best to check firstly for an external cause for lamp failure turn off the power then check for; Water ingress from either rain, or leaks or any signs of moisture or condensation in/around the electricals. Due to the elevated temperature of the lamp, high humidity may cause condensate to form. If there are no signs of leaking, check for signs of shorts or charring on the lamp connection with the ballast. Lastly inspect the tube to see if there are any dark patches or if the filaments are burnt out.
2. Sometimes the ballast may trigger a failure alarm if the connection to the lamp is interrupted or perhaps the connection is not solid enough. If the above steps reveal no faults and the lamp is still working (lighting up), turn the power off for 5 minutes, check connections and then turn it back on to see if the fault clears.
---|---|---
No Lights on Ballast| 1.  Ballast Failure
2.  Interrupted Power Supply| 1. In the event of a large surge it is possible that the ballast failed. This can also occur from shorts and water ingress. Check for signs of a short around the lamp connection end. The ballast will need to be replaced. The UV lamp may also have blown at the same time, or could be the cause for the ballast failure – for safety it is best to replace both the lamp and ballast together. If it is within Warranty period please contact the manufacturer for further instructions.
2. Check the wall socket with a different electrical appliance to check if the GPO is functioning. Also check your circuit breaker to see if any switches are off.
---|---|---
Lamp is working but the ballast is alarming| 1.  Faulty Lamp
2.  Faulty Ballast| 1. The lamp may be lighting up but not working at its full capacity which may be caused by it not drawing enough power from the ballast. The lamp will require replacement. Turn the system off, check connections and turn back on to see if it fixes the alarm.
2. The ballast could have a problem with the lamp failure protection and may require replacement. Turn the system off, check connections and turn back on to see if it fixes the alarm.

General Warranty

Water Filter Systems¹ (Excluding consumables) Manufactured or Assembled² by Filter Systems Australia (FSA) are covered under a 12-month Warranty Against Defects (Manufacturer’s Warranty). This warrants the water filter system to be free from defects in material and workmanship for a period of 12 months from date of sale.
If applicable, FSA may cover the return freight in the form of a re- imbursement after the system has been inspected and confirmed it is a valid warranty claim.
FSA will not cover any labor charge incurred by the consumer for the replacement or repair of a product. The warranty is strictly parts only for the parts supplied by FSA. This warranty only applies to the original consumer of the product and is non-transferable. If you have purchased the system through a re-seller, please contact them to facilitate the warranty on your behalf. All replaced or exchanged parts become the property of FSA.
FSA does not cover the workmanship of the plumber who originally installed the system. Responsibility for damages that occur during installation fall with the plumber, this includes the Quartz Thimble and Lamp also.
Qualification for Warranty
As per Australian Plumbing Codes, all filter systems must be installed by a qualified plumber. The consumer is responsible for keeping record and proof of installation in the form of an invoice and/or receipt.
Filter systems must be maintained as per FSA recommendations³ including the use of replacement filters, fittings and components supplied by FSA. Failure to maintain the filtration systems using FSA supplied/approved products may void warranty.
The warranty only applies if the product was used and/or installed in accordance with the user guide and/or installation instructions. This warranty is given in lieu of all other express or implied warranties and manufacturer shall in no circumstance be held liable for damages consequential or otherwise or delays caused or faulty manufacturing except as excluded by law.
Warranties need to be approved by FSA to ensure the product was not incorrectly used, installed or claimed. False and incorrect claims will be pursued at FSA’s discretion including chargeable inspection and transit costs incurred.
Installation of UV systems with a lamp power >40W must be fitted with a Thermal Relief Valve to prevent overheating unless the application is for constant flow. Damage/Failure on installations without a TRV that is deemed to be due to overheating will not be covered under warranty.
FSA does not take responsibility for retaining customer records, it is the consumer’s responsibility to retain all invoices or proof of purchase from the original sale and ongoing maintenance records as proof of upkeep.
Warranty Exclusions
FSA Standard Warranty shall be void if the product sustains damage or failure resulting from any of the following:

  • If your system(s) fails to be installed and maintained in accordance with recommended servicing and as per the manufacturers operating instructions.
  • Unauthorised or abnormal use or operation.
  • Failure to install a Thermal Relief Valve on installations where there is a likelihood for the water temperature to exceed 56°C due to lack of frequent water flow
  • Failure to install a certified Single Socket Surge protector between the system and a 10A GPO
  • Exposure to unsuitable environmental conditions*.

FSA does not cover the work of the plumber who originally installed the system.
Definitions

  1. Water Filter Systems are defined as systems designed for drinking water under our Water filter Systems, Reverse Osmosis Systems & Ultraviolet Sanitation Categories – Excluding Cartridges and Shower Filters.
  2. Other products not manufactured or assembled by FSA are covered under the applicable manufacturer’s warranty.
  3. FSA specifies recommended or required filter maintenance – see product information for further details. If a maintenance schedule is not specified, filter maintenance is required at least once per 12 month period.
  • Unsuitable environmental conditions include but are not limited to; excessive hot or cold, Weather extremes, Moisture/Rain/High Humidity.

Warranty – Australia
This warranty is given by Filter Systems Australia (Jacknel Pty Ltd ATF The J & N Family Trust). ABN 64 855 305 562 Located at 1/38 Jade Drive, Molendinar QLD 4214. Ph 07 5597 4585 & email [email protected]
This warranty is provided in addition to other rights and remedies you have under law. Our products come with guarantees which cannot be excluded under the Consumer Guarantees Act.
Extended Warranty
Filter Systems Australia Ultraviolet Systems are eligible for an extended 4-year warranty (commencing no later than 12 months from sale date), to provide a total warranty of 5 years. This extended warranty is subject to terms and conditions outlined below. This extended warranty covers the below parts of the system.

  • Ultraviolet Chamber (316 Stainless Steel)

Extended Warranty Qualification
Extended Warranty is valid only if the following conditions are met:

  • The System was installed by a licenced plumber – proof of installation required in the form of a receipt or invoice for works.
  • The system was maintained in accordance with our recommendations in Maintenance – Section I. Replacement Parts.
    o UV parts must be genuine FSA products purchased through FSA or participating supplier/reseller of FSA products
    o Proof of purchase for replacement parts required.

Pro-Rata & Consumable Warranty
Some components are considered consumables including the Lamp, Quartz Thimble and O-rings. General Warranty does not apply to these consumables. These products are subject to Pro-Rata Warranty conditions. Pro-Rata Warranty is determined by the period of time remaining of the components ‘Lifespan’ as dictated in the instruction manual (and below). A discount of the remaining balance of value (in life) will be deducted from the price of a new replacement part.
For example; A lamp has a successful warranty claim after 6 months from date of original invoice, the discount will be 50% from the next purchase of a replacement UV lamp. Pro-Rata Warranty only applies for a single use within the pro-rata period (12 months).
Pro-Rata Warranty only applies to components purchased new at full list price or as part of an applicable UV system.
Definitions

  1. Water Filter Systems are defined as systems designed for drinking water under our Water filter Systems, Reverse Osmosis Systems & Ultraviolet Sanitation Categories – Excluding Cartridges and Shower Filters.
  2. Other products not manufactured or assembled by FSA are covered under the applicable manufacturer’s warranty.
  3. FSA specifies recommended or required filter maintenance – see product information for further details. If a maintenance schedule is not specified, filter maintenance is required at least once per 12 month period.
  • Unsuitable environmental conditions include but are not limited to; Excessive hot or cold, Weather extremes, Moisture/Rain/High Humidity.

Rev. 14/05/2021

Documents / Resources

| FILTER SYSTEMS AUSTRALIA GT7- 2K Water Sterilisation System [pdf] User Manual
2K, 4K, 8K, 9K, 16K, GT7- 2K, GT7- 2K Water Sterilisation System, Water Sterilisation System, Sterilisation System, System
---|---

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Filter Systems Australia User Manuals

Related Manuals