Schneider Electric EBX510 ComX 510 Energy Server Instructions

June 11, 2024
Schneider Electric

Schneider Electric - logo

EBX200pp EBX210pp EBX510pp
5406AD002-07

Schneider Electric EBX510 ComX 510 Energy Server -
cover

www.se.com 

DOCA0036EN DOCA0098EN
User guide

EBX510 ComX 510 Energy Server

|
---|---
5406AD002-07| https://www.youtube.com/playlist?list=PLa7UGrWOTyjmFx8D7LEqX5lDqvucNtExH

WARNING: Cancer and Reproductive Harm www.P65Warnings.ca.gov

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

  • Wear personal protective equipment (PPE) and comply with the safety procedures.
    Refer to the NFPA 70E standard (United States) or applicable local installation standards.

  • Turn off all power supplying the equipment in which the Commix is to be installed before working on it.

  • Always use a properly rated voltage sensing device to confirm that all power is off.

  • Do not exceed the device’s ratings for maximum limits.

  • Do not obstruct the ventilation grilles (on the top and underside of the product). Failure to follow these instructions will result in death or serious injury.

Content

PL EASE NOTE
Do not disassemble the Commix case: this would render the product warranty null and void.

mm in.

Dimensions

Schneider Electric EBX510 ComX 510 Energy Server - Dimensions
1

Installation

HAZARD OF EQUIPMENT DAMAGE

  • Do not expose the device to conditions that exceed the specifications listed in “Characteristics.”
  • The device must be installed horizontally inside an electrical cabinet, in accordance with current standards and local regulations.
  • The product must be earthed (DIN rail) to ensure conformity with electromagnetic compatibility limits (EMC).
  • Due to use in OVCIII environment, external overvoltage, overcurrent, short-circuit backup protection must be provided in accordance with national wiring regulations.
  • An appropriate disconnect device shall be provided in the building installation.
  • Only use accessories listed in the Com’X catalogue, except for USB storage devices.
  • Only use connectors provided with the Com’X.
    Failure to follow these instructions can result in equipment damage.

Schneider Electric EBX510 ComX 510 Energy Server - Installation
1

Description

Schneider Electric EBX510 ComX 510 Energy Server - Description
1

1. 100-230 VA power supply (Com’X 200 only)
2. 24 Vac power supply
3. Modbus RS485 communication port
4. Ethernet 1 PoE communication port
5. Ethernet 2 communication port
6. USB port (backup, Wi-Fi)
7. Backup button / LED
8. Wi-Fi button / LED| 9. Digital inputs
10. Analog inputs
11. Digital input LED
12. Power / status LED (POWER LED)
13. Radio modem communication LEDs (modem LED)
14. RS485 communication LED (RS485 LED)
15. Ethernet communication LEDs (Ethernet 1 LED, Ethernet 2 LED)
---|---

Schneider Electric EBX510 ComX 510 Energy Server - Description
2

16. SD card (Com’X 510 only)
17. GPRS modem connector
18. USB1 port
19. USB2 port| 20. Label for naming digital / analog inputs
21. Expansion bus
---|---

NOTICE
LOSS OF DATA OR DATA CORRUPTION
Power down the Com’X 510 before inserting or removing the SD card.
Failure to follow these instructions will result in lost or corrupt data.

NOTICE

HAZARD OF EQUIPMENT DAMAGE
Do not remove label of expansion bus if no expansion module is due to be installed.
Failure to follow these instructions can result in equipment damage.

Wiring

Power supply

Com’X 200: 100-230 V~, 24 V , Ethernet 1 PoE port
Com’X 210 and Com’X 510: 24 V , Ethernet 1 PoE port

DANGER

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

  • If the equipment is only supplied with 24 Vac, use only a SELV or PELV power supply designed for a line power supply in the appropriate overvoltage category.
  • Do not get within 10 mm (0.4 in.) of the 100-230 VA power supply connector when the Com’X 200 is powered up.
  • Com’X is intended to be supplied by external power supply not provided in compliance with LPS according to UL/IEC 60950-1 Ed2 or class 2 per NEC.
  • Wiring to the primary power supply must be compliant with EN/IEC/UL/CSA60950-1 and NEC and CEC part 1.
  • All cables wired to Com’X 200 shall be connected to a single building earth and must not be connected to another building. Failure to follow these instructions will result in death or serious injury.

DANGER

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
The product must be powered with a power supply of type limited power source in accordance with of Clause 2.5 as part of the UL/IEC6050-1.
Failure to follow these instructions will result in death or serious injury.

Schneider Electric EBX510 ComX 510 Energy Server - Description
3

Schneider Electric EBX510 ComX 510 Energy Server - Description
4

PLEASE NOTE

  • PoE is not available if GPRS modem is installed.
  • PoE injector must fully comply with 802.3af standard for active midspan devices including overload and short circuit protection.
  • When supplied with PoE, product shall be used indoor and connected only to indoor equipment’s.

Wiring

Digital inputs

12 Vac power supply for inputs from Commix

External power supply for inputs

Analog inputs

0-10 Vc / 4-20 mA

|
---|---
Sensor powered from Commix (maximum load: 50 mA)| External sensor power supply

Pt RTD (Pt100 / Pt1000)

Schneider Electric EBX510 ComX 510 Energy Server - Wiring
4

2-wires temperature sensor

RS485 (RJ45) Modbus

Schneider Electric EBX510 ComX 510 Energy Server - Wiring
5

  1. Modbus RJ45 cable VW3A8306R03 or VW3A8306R10 or VW3A8306R30
Pin no Description
1
2
3
4 D1+
5 D0-
6
7
8 0 V
RS485 Modbus (screw-type connector)

Schneider Electric EBX510 ComX 510 Energy Server - Wiring
7

Consumption of the USB ports and of the extension bus
  • The maximum consumption of devices connected to the USB ports and the expansion bus depends on the power supply type (100-230 VA, 24 Vac, PoE) and the equipment connected to Commix. For more details, see the Commix installation manual: document DOCA0035.
  • The USB (see page 3/12) must not be used constantly.

Commissioning

NOTICE
HAZARD OF EQUIPMENT DAMAGE
Check that the inputs are connected correctly in accordance with the recommended wiring diagrams.
Failure to follow these instructions can result in equipment damage.

LED POWER| | | |
---|---|---|---|---
| | | |
No power| Inoperative product| Degraded mode| Starting ≈ 10 min ± 2 min| Operational
LED Modem|
---|---
| | | | |
No modem detected| Modem detected| Modem not connected to the network| Low signal| Medium signal| Strong signal
LED Ethernet 1, Ethernet 2|
---|---
| |
No Ethernet communication| 10 Mb Ethernet communication active| 100 Mb Ethernet communication active
LED RS485|
---|---
|
No serial Modbus communication| Serial Modbus communication active
LED Wi-Fi|
---|---
| | | | |
No dongle detected| Dongle detected| Dongle not connected to the network| Connected to the LAN medium signal| Connected to the LAN strong signal| Access Point mode
Digital inputs LEDs I1, I2, I3, I4, I5, I6|
---|---
| |
State 0 (open contact)| The LED lights up each time a pulse is received| State 1 (closed contact)

Ethernet connection

  1. Disconnect your computer from all networks.
  2. Connect an Ethernet cable between your PC (configured as DHCP client) and the Ethernet 2 port on the COMM’s.
  3. Perform the actions described in section 9.

Wi-Fi connection

  1. Connect the Wi-Fi dongle to a USB port on the Commix in accordance with the Wi-Fi dongle instruction sheet (253537634)
  2. Press the Wi-Fi button (no. 8), it starts to flash green.
  3. Open the “Wireless Network Connection” window on your computer, then connect to the “Commix” wireless network.
  4. Perform the actions described in section 9.

Access to the Commix web application

Windows 7
  1. Open Windows Explorer and click on Network, the Commix appears in the list of devices (if the Commix does not appear, see troubleshooting on p. 9/12).
  2. Double-click on the Commix, the login page automatically opens in your browser.
  3. Type the user name (admin by default) and password (admin by default). These identifiers are case-sensitive.
  4. Then click OK.
Windows XP
  1. Launch your Internet browser.

  2. In the “Address” field, type:
    10.25.1.1 if you are on an Ethernet connection
    10.25.2.1 if you are on a Wi-Fi connection and press Enter to access the login page.

  3. Type the user name (admin by default) and password (admin by default). These identifiers are case-sensitive.

  4. Then click OK.

Troubleshooting

The Commix does not appear in the list of devices in Windows Explorer.| Check that the computer and the COMM’s are connected by a cable or switches, not by a router.
---|---
The login page in the Internet browser does not open or does not display correctly.| Check that the browser is compatible with the following versions:
Internet Explorer 8, Mozilla Firefox 15, Chrome 24 and later versions.
Check in Internet Explorer, under the “Tools \ View Settings
Compatibility” option, that the “Display intranet sites in Compatibility View” option (check box) is disabled.

Reset

RISK OF ETHERNET (IP) ADDRESS CONFLICT
Disconnect the Commix from all Ethernet networks before Resetting factory settings.
Failure to follow these instructions can result in equipment damage.

Resetting factory settings.

  • Turn off the Commix.
  • Press and hold buttons (7) and (8) and power up the Commix. Hold buttons for at least 10 seconds until the POWER LED flashes three times.
  • The Commix then starts up with factory settings.

Characteristics

Communication

  • 2 Base 10/100 Ethernet RJ45 ports, DPWS ready

    • Eth1: PoE class 3 (802.3af), DHCP client
    • Eth2: DHCP client or server
  • Protocols: IPv4, IPv6 – HTTP, HTTPS, Modbus TCP/IP

  • 1 Modbus RS485 serial port

    • RJ45 and removable screw terminal connector (0 V, Screen, D0, D1)
      Both connectors are plugged into the same Modbus RS485 serial port

    • 32 devices maximum.

Input characteristics

  • 6 digital inputs:
    • Pulse counting (minimum pulse width 20 ms) conforming to IEC 62053-31 or Status
    • Internal power supply for inputs 12 Vac, 60 mA
    • External power supply for inputs 10-30 Vac
  • 2 analog inputs:
    • 0-10 Vac, 4-20 mA (accuracy 0.5 %),
    • PT100, PT1000: 2-wire (accuracy 1 %)
    • Power supply available for analog sensors: 24 Vc (50 mA for each input).

Power supply

  • 100-230 VA (Commix 200 only) (±15 %) OVCIII
    • Fuse protection type T 0.63AE/250V (F1)
  • 24 Vac (±10 %)
    • Fuse protection type 3.15AL/250V (F1500)
  • Power consumption (100-230 Val, 24 Vac): 26 W max.
  • Power consumption (PoE): 15 W max.

USB 2.0 host ports

  • 1 USB port on front face
    • max. current: 500 mA
  • 2 USB ports behind the cover
    • USB1 port: maximum current 500 mA
    • USB2 port: maximum current 100 mA
  • If powered by PoE, the maximum power drawn in sum from all USB ports must not exceed 1.25 W (i. e. 250 mA).

Expansion bus

  • Consumption on 24 Vac: 160 mA max..
  • Consumption on 3.3 Vac: 110 mA max.

Memory

  • 128 Mb RAM, 256 Mb Flash.
  • 4 GB SD card (Commix 510 only): EXT3 format

Mechanical characteristics

  • Front face IP40, Connectors IP20
  • Weight: 450 g.

Environment

  • Operating temperature:
    • Commix 200: -25°C…+40°C (-13°F…+104°F); Peak temperature: +60°C (+140°F)
    • Com’X210/510: -25°C…+50°C (-13°F…+122°F); Peak temperature: +70°C (+158°F)
    • Life time could be reduced by using the COMM’s at peak temperature
  • Storage temperature:
    • 40 °C…+85 °C (-40°F…+185 °F)
  • Humidity: 5…95 % relative humidity (without condensation) at 55 °C
  • Level of pollution: Class 3
  • Altitude: 2000 m (maximum).

Standards
Conforming to safety standards/regulations

  • United States: UL 508, UL 60950 (EBX210 and EBX510 only)
  • Canada: cull
  • Europe: EN 60950, EN 61010-1.

PC specification for configuration

  • Operating system: Windows 7 (recommended), Vista or XP

  • Web browsers: latest version of Mozilla Firefox, Chrome or IE.

  • Radio certification:

    • FCC Part 15 class B
      Marking
  • UL, C-tick,

Notices

Read these instructions carefully and look at the equipment to become familiar with the device before trying to install, operate, service or maintain it.
Electrical equipment should be installed, operated, serviced and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material. A qualified person is one who has skills and knowledge related to the construction, installation, and operation of electrical  equipment and has received safety training to recognize and avoid the hazards involved.
Power Logic and Schneider Electric are trademarks or registered trademarks of Schneider Electric in France, the USA and other countries.

  • This product must be installed, connected and used in compliance with prevailing standards and/or installation regulations.
  • If this product is used in a manner not specified by the manufacturer, the protection provided by the product may be impaired.
  • The safety of any system incorporating this product is the responsibility of the assembler/installer of the system.
    As standards, specifications and designs change from time to time, always ask for confirmation of the information given in this publication.

Schneider Electric Industries SAS
35, rue Joseph Moniker
CS 30323
F – 92506 Ruel Malmaison Cedex
www.se.com
5406AD002-07
© 12-2021 Schneider Electric
All rights reserved.

Documents / Resources

| Schneider Electric EBX510 ComX 510 Energy Server [pdf] Instructions
EBX510 ComX 510 Energy Server, EBX510, ComX 510 Energy Server, Energy Server, Server
---|---

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Schneider Electric User Manuals

Related Manuals