DSC PG9936 Wireless Smoke and Heat Detector Instruction Manual
- June 11, 2024
- DSC
Table of Contents
- Introduction
- Compatible Devices
- Operation
- Wireless Transmissions
- Batteries
- Battery Installation and Replacement
- Installation Instructions
- Owner’s Instructions
- Family Escape Planning
- Testing Your Smoke Detector
- Owner’s Maintenance
- Specifications
- Limited Warranty
- Regulatory Information
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
PG9936/PG8936/PG4936 Series Wireless Smoke and Heat Detector
Installation and Operating Instructions
Read this instruction sheet thoroughly before installation and use of the
PG9936/PG8936/PG4936
Introduction
The PG9936/PG8936/PG4936 is a wireless photoelectric smoke and heat detector
with a fixed temperature and rate of rise heat detector, and an internal
piezoelectric alarm.
The following versions are available:
Frequency (MHz) | Version | Region |
---|---|---|
915 | PG9936 | North America |
868 | PG8936 | Europe |
433 | PG4936 | Europe/International and Australia |
Compatible Devices
This smoke detector is compatible with UL/ULC Listed DSC Wireless Control Panels and DSC Wireless Receivers using PowerG Technology, PowerSeries Neo and iotega platform 3.
NOTE: For UL/ULC installations use this device only in conjunction with
compatible DSC wireless receivers: HS2128, HS2064, HS2032, HS2016 control
units when connected to HSM2HOST9 wireless receiver, HS2LCDRF(P)9, HS2ICNRF(P9
Keypads with integrated receiver, PG9920 repeater and Wireless Alarm Systems
WS90019,
and WS900-29. Transmissions occur at approximately 915 MHz (912 MHz to 919
MHz).
Operation
Approximately every 7 to 8 seconds the unit tests for a smoke or heat alarm
condition. During this sequence the unit also performs self diagnostics, and
checks for tampers and faults. During normal operation the green LED flashes
every 60 seconds and the sounder does not sound.
Smoke Alarm
The smoke detector alarms when the signal level exceeds the “alarm” threshold
and automatically restores when the signal level falls below the alarm
“restore” threshold. During an alarm the red LED flashes once per second and
the sounder sounds the evacuation temporal pattern.
Alarm Silencing
This smoke alarm is provided with an automatically resettable alarm silencing
feature. When the sensor is in alarm, press the Test/Silence/Reset button to
silence the local annunciation of the alarm and transmit an alarm restore
event to the control panel. The red LED flashes once per second for up to 7
minutes, to indicate the alarm has been silenced.
After an alarm the red LED will flash once every 4 seconds to indicate an
alarm in memory.
The alarm silence feature has a fixed time setting that desensitizes the smoke
alarm for 7 minutes.
Alarm silencing does not disable the smoke alarm but rather reduces its smoke
sensitivity. Following the silenced period the smoke alarm restores
automatically to its intended operation. If smoke around the unit is dense
enough to suggest a potentially dangerous situation, it remains in alarm, or
may return to the alarm state quickly.
Detector Trouble
When the detector has a general fault, the yellow LED blinks once every four
seconds and there is a chirp every 48 seconds. After 4 hours, the panel will
display a fire trouble message.
Detector and Status Indication
Status | LEDs | Sounder |
---|---|---|
Normal | Green flash every 60 seconds | Off |
Heat Alarm | Red flash every 1 second | ANSI S3.41 temporal 3 |
Heat Test | Red flash every 1 second | ANSI S3.41 temporal 3 |
Smoke Alarm | Red flash every 1 second | ANSI S3.41 temporal 3 (press button to |
hush for 5-10 minutes)
Smoke Test (with canned smoke)| Red flash every 1 second| ANSI S3.41 temporal
3 (press button to hush for 5-10 minutes)
Test Alarm (button press)| Red flash every 1 second| ANSI S3.41 temporal 3
Detector Trouble| Yellow flash every 4 seconds| One chirp every 48 seconds
Low Battery| Yellow flash every 12 seconds| One chirp every 48 seconds (press
button to hush for 12 hours)
Detector Dirty| Yellow flash every 8 seconds| One chirp every 48 seconds
Power-up| Red, yellow, green, flash sequence| One chirp at the end of the
powerup sequence
Tamper| Red, yellow, green flash sequence every 12 seconds| Off
Hush Mode| Red flash every 1 second (alarm hush)| Off
Yellow flash every 12 seconds (low battery hush)| Off
Detector Cleaning Required
When the detector is contaminated, the yellow LED blinks once every 8 seconds
and there is a chirp every 48 seconds. Refer to the MAINTENANCE section for
cleaning the detector. After 4 hours, the panel displays a message fire clean.
Heat Alarm
The heat detector (cULus versions only) alarms when the heat signal level
exceeds the heat alarm threshold (135 ºF / 58 ºC); and will automatically
restore when the heat signal level falls below the heat alarm threshold
(restore). The detector also goes into a heat alarm state when there is a
rapid increase in the temperature over a short period of time. During an alarm
the LED flashes 1/second and the sounder sounds the evacuation temporal
pattern.
Tamper
The removal of the detector from the mounting plate initiates a “tamper”
transmission. The tamper condition is restored after the detector is mounted
on the plate.
Wireless Transmissions
A supervisory message is transmitted at 64 minute intervals for the PG9936 and
12-minute intervals for the PG8936/PG4936 models. If the signal is not
received the control panel determines that the detector is missing.
The detector transmits the following:
-
Alarm / Alarm Restore – (heat or smoke alarm). Transmitted at time of occurrence.
NOTE: During an alarm condition, the detector sends an alarm event to the control panel.
When the condition is restored, the detector sends an alarm restore event to the panel and sets the alarm restore indicator. The red LED blinks once every 4 seconds until the Alarm in memory is cleared. You can clear the alarm restore indicator from the control panel, or press and hold the test button for 5 seconds. -
Tamper / Tamper Restore – (tamper switch activated) 10 second maximum delay on restore before transmission.
-
Low Battery – (battery voltage falls below threshold). Battery voltage is tested & transmitted at the time of a supervisory or other transmissions.
-
Trouble – (detector fault or sensor compensation limit reached). Troubles are transmitted at the time of occurrence (one trouble per supervisory interval).
Batteries
The wireless smoke heat alarm is powered by 3 AAA Duracell Procell PC2400 or 3
AAA Energizer E92 batteries (included). The detector regularly checks for a
low battery. If a low battery is detected, the transmitter sends a low battery
message to the control panel, which displays the detector’s ID at low battery.
In addition, the yellow LED of the detector blinks every 12 seconds. The
detector’s sounder chirps every 48 seconds and the yellow LED continues to
blink until the batteries are replaced. Pressing the hush button silences the
chirps for 12 hours, if no other trouble conditions exist. The batteries
should be replaced with new batteries when the chirps begin.
At low battery, the test button is disabled. An alternative test method is to
use an aerosol test gas such as ‘Solo A10 smoke detector tester’. Shake the
can well, aim it at the smoke detector and spray a short burst (no more than 1
sec) at the detector. If the alarm does not sound, repeat every 10 seconds
until alarm sounds or for a maximum of 1 minute.
NOTE: If the alarm does not sound, contact the installer or dealer for
service.
Battery Installation and Replacement
CAUTION: Risk of explosion if battery is replaced by an incorrect type.
Dispose of used battery according to the manufacturer’s instructions.
To replace batteries, complete the following steps:
-
Remove the detector from its mounting base by twisting the detector counterclockwise.
Carefully remove batteries by lifting from the “+” end using a flathead screwdriver and dispose of them according to local regulations. -
To ensure a proper power-down sequence, wait a minimum of 30 seconds before installing new batteries.
-
Install 3 new AAA batteries, available from a local Duracell or Energizer dealer in the battery compartment. Install the batteries by inserting the “-” end first, then pushing the “+” end down. If the batteries are incorrectly inserted, please remove them carefully by lifting them out from the “+” end and correctly re-inserting them.
-
Re-install the detector on its mounting base by turning the detector clockwise until the mating marks align.
-
After the power-up sequence, the green LED should blink once every 60 seconds to indicate normal operation. If the batteries are not installed correctly, the detector will not operate and the batteries may be damaged. If the detector does not power up, check that the batteries are installed correctly and fully charged.
-
Test the detector as described later.
CONSTANT EXPOSURES TO HIGH OR LOW TEMPERATURES OR HIGH HUMIDITY MAY REDUCE BATTERY LIFE.
Installation Instructions
The PGx936 Series wireless smoke detector shall be installed and used within an environment that provides the pollution degree max 2 and over voltages category II in non- hazardous locations, indoor only. The equipment is designed to be installed by SERVICE PERSONS only; (SERVICE PERSON is defined as a person having the appropriate technical training and experience necessary to be aware of hazards to which that person may be exposed in performing a task and of measures to minimize the risks to that person or other persons).
1. Smoke Detector Placement
Research has shown that all hostile fires in homes generate smoke to a greater
or lesser extent. Experiments with typical fires in homes indicate that
detectable quantities of smoke precede detectable levels of heat in most
cases. For these reasons, smoke alarms should be installed outside of each
sleeping area and on each storey of the home.
The following information is for general guidance only and it is recommended
that local fire codes and regulations be consulted when locating and
installing smoke alarms. It is recommended that additional smoke alarms beyond
those required for minimum protection be installed. Additional areas that
should be protected include: the basement; bedrooms, especially where smokers
sleep; dining rooms; furnace and utility rooms; and any hallways not protected
by the required units. On smooth ceilings, detectors may be spaced 9.1 m (30
ft) apart as a guide. Other spacing may be required depending on ceiling
height, air movement, the presence of joists, uninsulated ceilings, etc.
Consult National Fire Alarm Code NFPA 72, CAN/ULC- S553 or other appropriate
national standards for installation recommendations.
- Do not locate smoke detectors at the top of peaked or gabled ceilings; the dead air space in these locations may prevent the unit from detecting smoke.
- Avoid areas with turbulent air flow, such as near doors, fans or windows. Rapid air movement around the detector may prevent smoke from entering the unit.
- Do not locate detectors in areas of high humidity.
- Do not locate detectors in areas where the temperature rises above 38 ºC (100 ºF) or falls below 5 ºC (41 ºF).
- Smoke detectors must always be installed in USA in accordance with Chapter 29 of NFPA 72, the National Fire Alarm Code: 29.5.1.1.
Where required by applicable laws, codes, or standards for a specific type of occupancy, approved single and multiple-station smoke alarms shall be installed as follows:
- In all sleeping rooms and guest rooms.
- Outside of each separate dwelling unit sleeping area, within 6.4 m (21 ft) of any door to a sleeping room, the distance measured along a path of travel.
- On every level of a dwelling unit, including basements.
- On every level of a residential board and care occupancy (small facility), including basements and excluding crawl spaces and unfinished attics.
- In the living areas of a guest suite.
- In the living areas of a residential board and care occupancy (small facility).
NOTE: In Australia the device shall not be installed in locations where the normal ambient temperature is lower than 5 ºC or higher than 45 ºC.
2. Mount Smoke Detector Backplate
NOTE: The alarm device should only be installed by a competent engineer
or technician.
Smoke detectors are not to be used with smoke detector guards unless the
combination has been evaluated and found suitable for that purpose.
Once a suitable location is found, mount the detector backplate. Install the
mounting base on the ceiling or on the wall (if local ordinances permit) using
screw locations as required. Use the two screws and anchors provided. Maneuver
the base so the screws are at the elbow of the screw slots and secure.
3. Mounting
Fit the detector inside the base by aligning it over the base. The detector’s
alignment notch should be slightly offset from the mounting base tamper
release tab. Then turn the detector clockwise until it clicks into place.
If there is a need to activate the built- in anti-tamper lock, carefully
remove the breakaway tab on the backplace as shown in the following figure.
4. Device Enrollment
The 7-digit serial number located on the back of the smoke detector housing
must be enrolled on the alarm systems control panel. See the Receiver
Installation Manual and follow the enrollment procedure. For placement tests
remove the detector from its backplate for one second (tamper) and then
reattach. Wait at least 30 seconds for the test result before activating
again.
A general description of the procedure is provided in the following flow
chart:
Step Procedure
-
See the Installation Manual for the alarm system that the device is being enrolled on, to ensure that the proper steps are used.
-
Enter the Device Enrollment option through the specified method and select the appropriate option to add the new device.
-
Enroll the device by inserting the batteries to power up the device and enter the Device
ID. For example, ID No. 202-XXXX.
NOTE: When enrolling the PGx936 detector to DSC control panels (see Compatible Devices), the detector will be enrolled as a Smoke and Heat detector ID 201xxxx,
and labeled Smoke and Heat in the panel. -
Select the desired Zone Number.
-
Configure any device parameters that are required. Enter the DEV SETTINGS menu and select the required options to configure the detector:
-
Mount and test the detector. See Smoke Detector Unit Test for information on testing the device. In addition, see the alarm systems Installation Manual that the device is enrolled on for other test procedures that are required.
5. Test Unit
NOTE: The central monitoring station if used, should be notified prior to
the test being generated.
This prevents a false alarm and an unnecessary response from the central
monitoring station.
Initiate test by pressing the test button for 5 seconds minimum. Alarm
activation is indicated by the flashing red LED, the sounder, and transmission
of the alarm signal to the control panel.
The detector restores to normal when the test button is released.
NOTE: Allow a minimum of 20 seconds after power up and after test, alarm
or tamper restore activations.
NOTE: If the detector is in one of the following states when a test is
initiated; it will not enter an alarm state:
- Compensation Trouble
- Other internal faults that could prevent a smoke or heat alarm
Owner’s Instructions
Fire Safety In The Home
Most fires occur in the home, and to minimize this danger, it is recommended
that a household fire safety audit be conducted and a family escape plan be
developed.
Household Fire Safety Audit
- Are all electrical appliances and outlets in safe condition? Check for frayed cords, overloaded lighting circuits, etc. If you are uncertain about the condition of your electrical appliances or household service, have a professional evaluation.
- Are all flammable liquids safely stored in closed containers, and in a cool and well ventilated area? Cleaning the unit with flammable liquids should be avoided.
- Are hazardous materials for example, matches out of the reach of children?
- Are furnaces and wood burning appliances properly installed, clean, and in good working order? If in doubt, have a professional evaluation.
Family Escape Planning
There is often very little time between the detection of a fire and the time
it becomes deadly.
Because of this, it is very important that a family escape plan be developed
and rehearsed.
- Every family member should participate in the escape plan.
- Study the possible escape routes from each location within the house. Since many fires occur at night, special attention should be given to the escape routes from sleeping quarters.
- It is essential that escape from a bedroom be possible without opening the interior door. Consider the following when making your escape plans:
- Ensure that doors and windows that open to the outside are easily opened. Ensure that they are not painted shut and that the locking mechanisms operate smoothly.
- If opening or using the exit is too difficult for children, the elderly or handicapped, plans for their rescue should be developed. This plan includes making sure that those who are to perform the rescue can promptly hear the fire warning signal.
- If the exit is above the ground level, an approved fire ladder or rope should be provided, as well as training in its use.
- Exits on the ground level should be kept clear. Be sure to remove snow from exterior patio doors in the winter and that outdoor furniture or equipment does not block exits.
- The family should have a predetermined assembly point where everyone can be accounted for; for example, across the street or at a neighbor’s house.
- Once everyone is out of the house, call the Fire Department.
- A good plan emphasizes a quick escape. Do not investigate first or attempt to fight the fire, and do not attempt to rescue belongings or valuables as this takes up time. Once outside, do not re-enter the house; wait for the Fire Department.
- Write the plan down and rehearse it frequently so that should an emergency ever arise, everyone will know what to do. Revise the plan as conditions change; for example, when there are more or fewer family members in the home or if there are changes to the house.
- Make sure your fire warning system is operational by conducting weekly tests. If you are unsure about system operation, contact your smoke detector installer or dealer.
- It is recommended that you contact your local Fire Department and request further information on home fire safety and escape planning. If available, have your local fire prevention officer conduct an in-house fire safety inspection.
Testing Your Smoke Detector
Follow the test procedure described here or contact your smoke detector dealer
or installer for testing instructions. It is recommended to test the entire
alarm system at least once a week to verify the operation of all system
functions.
Smoke Detector Unit Test
Initiate test by pressing the test button for 5 seconds, the sounder makes
chirping noises during this time. Press the button until the unit alarm
sounds, an alarm should be sent to the control panel. When the button is
released, the alarm should cease. If this does not occur, ensure batteries are
the correct type, in good condition and are installed correctly.
Upon completing the functional testing of the smoke detector, check the unit’s
sensing chamber to ensure proper operation. To test the sensing chamber, use
an aerosol test gas such as ‘Solo A10 smoke detector tester’. Shake the can
well, aim it at the smoke detector and spray a short burst (no more than 1
second) at the detector. If the alarm does not sound, repeat every 10 seconds
until alarm sounds or for a maximum of 1 minute. If the smoke detector does
not function properly, call your smoke detector installer or dealer for
service.
Smoke Detector Test
Before you test, complete the following steps:
- Insert the battery and then mount the detector on the bracket before conducting the smoke detector test.
- After the battery is inserted, wait 2 minutes before testing it. The detector enters into Local Diagnostic Test Mode for 15 minutes.
- It is recommended to perform the Periodic Test and use either the Installer code (Installer Diagnostic Mode) or the User code (User Diagnostic Mode) to test.
CAUTION: The diagnostic test cannot be performed when the tamper is open.
Press and hold the test button for 2 seconds. When the button is released, the
following sequence of events occur, the Red LED lights for 0.5 s > off for 0.5
s.
This is followed by 2 loud alarm beeps and at the same time the red LED
flashes. In test mode, the detector tests smoke, heat, and battery functions.
If the detector is in diagnostic mode, the detector performs the diagnostic
test as described below.
Sensitivity Indicating Means
If the detector is indicating ‘Detector Dirty’ with a Yellow LED flash every 8
seconds, a chirp every 48 seconds and a fire clean message on the panel, the
detector’s in built automatic drift compensation feature is no longer able to
compensate for dust and dirt accumulation and may no longer be within the
marked sensitivity. If the detector is indicating ‘Normal’ with Green LED
flash every 60 seconds it is within the marked sensitivity range.
NOTE: If the panel dispays the fire clean message after cleaning, call
the installer or dealer for service.
Diagnostic Test
The following sequence of events occur during a diagnostic test:
A. The detector performs a link quality test.
Note: The detector must be in local or diagnostic mode to perform the
link quality test.
In diagnostic mode, if you press the test button for more than 6 seconds, an
alarm message is sent to the panel and a Temporal-3 alarm signal is sounded.
After this sequence
is completed, the panel responds by sending an “Alarm in Memory” message to
the device.
B. At the end of the diagnostic test the LED blinks three times. The following
table indicates the received signal strength.
LED Response | Green LED blinks | Orange LED blinks | Red LED blinks | No blinks |
---|---|---|---|---|
Reception | Strong | Good | Poor | Paired, no communicaton |
IMPORTANT! Reliable reception must be confirmed. Therefore, “poor” signal strength is not acceptable. If you receive a “poor” signal from the device, re-locate it and re-test until a “good” or “strong” signal strength is received. For UL/CUL installations, the test results must be “strong”. See the alarm systems installation guide for detailed diagnostic tests.
Owner’s Maintenance
The smoke detector is designed to require minimum maintenance. If the case
becomes dusty, vacuum with a small brush attachment. If the case is greasy,
wipe the case gently with a soft cloth slightly dampened with soapy water.
Never disassemble the smoke detector; there are no user serviceable parts
inside the unit.
You may only remove detector from backplate to replace batteries if not
serviced by installer. When replacing the batteries, follow the instructions
specified in the Installation
Instructions.
Never paint the unit. Paint may prevent smoke from entering the unit. If you
are planning renovations or repainting, take precautions to avoid dust, paint
or chemical contamination to the detector.
If the unit is located in an area where it is exposed to high levels of dust
or insects and causes false alarms, it may require service; contact your smoke
detector installer or dealer.
Testing and maintenance procedures shall be in accordance with
CAN/ULC-S552-14.
Specifications
- Regulatory Listings: UL268/ULC-S531 PG9936
- Diameter: 5 in (125 mm)
- Height: 2.5 in (63 mm)
- Weight (including battery): 8.75 oz (243 g)
- Color: White
- Spacing rating: 70 ft (21.3 m)
- Alarm Sensitivity (threshold) PG9936 (cULus): 1.26 – 2.39 %/ foot obscuration
- Alarm Sensitivity (threshold) PG4936 / PG8936: complies with EN14604
- Audible Signal (ANSI Temporal 3): 85 dBA minimum in alarm
- Operating Temperature: PG9936 40 ºF – 100 ºF (4.4 ºC – 37.8 ºC)
- Operating Temperature with Heat Detector: 32 ºF – 100 ºF (0 ºC – 37.8 ºC)
- Operating Temperature for Smoke Alarm:PG4936 41 ºF – 113 ºF (5 ºC – 45 ºC); Type A Photoelectric Smoke Alarm (Australia)
- Heat Alarm: 135 ºF (57 ºC);
- Humidity: 15 % – 90 % RH, non-condensing
- Approved Batteries: 3 AAA Energizer E92 or Duracell Procell PC2400
- Alarm Silencing: PG4936 8 minutes automatically resettable
- Supervisory Transmission Frequency:PG9936 64 minute intervals
- Supervisory Transmission Frequency: PG4936 / PG8936 12 minute intervals
- Maximum Tx Power: 433.22 MHz – 434.64 MHz: 10 mW, 868.0 MHz – 868.6 MHz: 14 mW, 868.7 MHz – 869.2 MHz: 14 mW.
- Low Battery Detection: Low battery 14 days remaining
Limited Warranty
Digital Security Controls warrants that for a period of twelve months from the
date of purchase, the product shall be free of defects in materials and
workmanship under normal use and that in fulfillment of any breach of such
warranty, Digital Security Controls shall, at its option, repair or replace
the defective equipment upon return of the equipment to its repair depot. This
warranty applies only to defects in parts and workmanship and not to damage
incurred in shipping or handling, or damage due to causes beyond the control
of Digital Security Controls such as lightning, excessive voltage, mechanical
shock, water damage, or damage arising out of abuse, alteration or improper
application of the equipment.
The foregoing warranty shall apply only to the original buyer, and is and
shall be in lieu of any and all other warranties, whether expressed or implied
and of all other obligations or liabilities on the part of Digital Security
Controls. Digital Security Controls neither assumes responsibility nor
authorizes any other person purporting to act on its behalf to modify or to
change this warranty, nor to assume for it any other warranty or liability
concerning this product. In no event shall Digital Security Controls be liable
for any direct, indirect or consequential damages, loss of anticipated
profits, loss of time or any other losses incurred by the buyer in connection
with the purchase, installation or operation or failure of this product.
Smoke Detectors: Smoke detectors that are a part of this system may not
properly alert occupants of a fire for a number of reasons, some of which
follow. The smoke detectors may have been improperly installed or positioned.
Smoke may not be able to reach the smoke detectors, such as when the fire is
in a chimney, walls or roofs, or on the other side of closed doors.
Smoke detectors may not detect smoke from fires on another level of the
residence or building.
Every fire is different in the amount of smoke produced and the rate of
burning. Smoke detectors cannot sense all types of fires equally well. Smoke
detectors may not provide timely warning of fires caused by carelessness or
safety hazards such as smoking in bed, violent explosions, escaping gas,
improper storage of flammable materials, overloaded electrical circuits,
children playing with matches or arson.
Even if the smoke detector operates as intended, there may be circumstances
when there is insufficient warning to allow all occupants to escape in time to
avoid injury or death.
Warning: Digital Security Controls recommends that the entire system be
completely tested on a regular basis. However, despite frequent testing, and
due to, but not limited to, criminal tampering or electrical disruption, it is
possible for this product to fail to perform as expected.
Important Information: Changes or modifications not expressly approved by
Digital Security Controls could void the user’s authority to operate this
equipment.
EULA
IMPORTANT – READ CAREFULLY: DSC Software purchased with or without Products
and Components is copyrighted and is purchased under the following license
terms:
This End-User License Agreement (“EULA”) is a legal agreement between You (the
company, individual or entity who acquired the Software and any related
Hardware) and Digital Security Controls, a division of Tyco Safety Products
Canada Ltd. (“DSC”), the manufacturer of the integrated security systems and
the developer of the software and any related products or components
(“HARDWARE”) which You acquired. If the DSC software product (“SOFTWARE
PRODUCT” or “SOFTWARE”) is intended to be accompanied by HARDWARE, and is NOT
accompanied by new HARDWARE, You may not use, copy or install the SOFTWARE
PRODUCT. The SOFTWARE PRODUCT includes computer software, and may include
associated media, printed materials, and “online” or electronic documentation.
Any software provided along with the SOFTWARE PRODUCT that is associated with
a separate end-user license agreement is licensed to You under the terms of
that license agreement. By installing, copying, downloading, storing,
accessing or otherwise using the SOFTWARE PRODUCT, You agree unconditionally
to be bound by the terms of this EULA, even if this EULA is deemed to be a
modification of any previous arrangement or contract. If You do not agree to
the terms of this EULA, DSC is unwilling to license the SOFTWARE PRODUCT to
You, and You have no right to use it.
SOFTWARE PRODUCT LICENSE
The SOFTWARE PRODUCT is protected by copyright laws and international
copyright treaties, as well as other intellectual property laws and treaties.
The SOFTWARE PRODUCT is licensed, not sold.
GRANT OF LICENSE This EULA grants You the following rights:
Software Installation and Use – For each license You acquire, You may have
only one copy of the SOFTWARE PRODUCT installed. Storage/Network Use – The
SOFTWARE PRODUCT may not be installed, accessed, displayed, run, shared or
used concurrently on or from different computers, including a workstation,
terminal or other digital electronic device (“Device”). In other words, if You
have several workstations, You will have to acquire a license for each
workstation where the SOFTWARE will be used.
Backup Copy – You may make back-up copies of the SOFTWARE PRODUCT, but You may
only have one copy per license installed at any given time. You may use the
back-up copy solely for archival purposes. Except as expressly provided in
this EULA, You may not otherwise make copies of the SOFTWARE PRODUCT,
including the printed materials accompanying the SOFTWARE.
DESCRIPTION OF OTHER RIGHTS AND LIMITATIONS
Limitations on Reverse Engineering, Decompilation and Disassembly – You may
not reverse engineer, decompile, or disassemble the SOFTWARE PRODUCT, except
and only to the extent that such activity is expressly permitted by applicable
law notwithstanding this limitation. You may not make any changes or
modifications to the Software, without the written permission of an officer of
DSC. You may not remove any proprietary notices, marks or labels from the
Software Product. You shall institute reasonable measures to ensure compliance
with the terms and conditions of this EULA.
Separation of Components – The SOFTWARE PRODUCT is licensed as a single
product. Its component parts may not be separated for use on more than one
HARDWARE unit.
Single INTEGRATED PRODUCT – If You acquired this SOFTWARE with HARDWARE, then
the SOFTWARE PRODUCT is licensed with the HARDWARE as a single integrated
product. In this case, the SOFTWARE PRODUCT may only be used with the HARDWARE
as set forth in this EULA.
Rental – You may not rent, lease or lend the SOFTWARE PRODUCT. You may not
make it available to others or post it on a server or web site.
Software Product Transfer – You may transfer all of Your rights under this
EULA only as part of a permanent sale or transfer of the HARDWARE, provided
You retain no copies, You transfer all of the SOFTWARE PRODUCT (including all
component parts, the media and printed materials, any upgrades and this EULA),
and provided the recipient agrees to the terms of this EULA. If the SOFTWARE
PRODUCT is an upgrade, any transfer must also include all prior versions of
the SOFTWARE PRODUCT.
Termination – Without prejudice to any other rights, DSC may terminate this
EULA if You fail to comply with the terms and conditions of this EULA. In such
event, You must destroy all copies of the SOFTWARE PRODUCT and all of its
component parts.
Trademarks – This EULA does not grant You any rights in connection with any
trademarks or service marks of DSC or its suppliers.
COPYRIGHT
– All title and intellectual property rights in and to the SOFTWARE PRODUCT
(including but not limited to any images, photographs, and text incorporated
into the SOFTWARE PRODUCT), the accompanying printed materials, and any copies
of the SOFTWARE PRODUCT, are owned by DSC or its suppliers. You may not copy
the printed materials accompanying the SOFTWARE PRODUCT. All title and
intellectual property rights in and to the content which may be accessed
through use of the SOFTWARE PRODUCT are the property of the respective content
owner and may be protected by applicable copyright or other intellectual
property laws and treaties. This EULA grants You no rights to use such
content. All rights not expressly granted under this EULA are reserved by DSC
and its suppliers.
EXPORT RESTRICTIONS – You agree that You will not export or re-export the
SOFTWARE PRODUCT to any country, person, or entity subject to Canadian export
restrictions.
CHOICE OF LAW – This Software License Agreement is governed by the laws of the
Province of Ontario, Canada.
ARBITRATION – All disputes arising in connection with this Agreement shall be
determined by final and binding arbitration in accordance with the Arbitration
Act, and the parties agree to be bound by the arbitrator’s decision. The place
of arbitration shall be Toronto, Canada, and the language of the arbitration
shall be English.
LIMITED WARRANTY
NO WARRANTY – DSC PROVIDES THE SOFTWARE “AS IS” WITHOUT WARRANTY. DSC DOES NOT
WARRANT THAT THE SOFTWARE WILL MEET YOUR REQUIREMENTS OR THAT OPERATION OF THE
SOFTWARE WILL BE UNINTERRUPTED OR ERROR-FREE.
CHANGES IN OPERATING ENVIRONMENT – DSC shall not be responsible for problems
caused by changes in the operating characteristics of the HARDWARE, or for
problems in the interaction of the SOFTWARE PRODUCT with non-DSCSOFTWARE or
HARDWARE PRODUCTS.
LIMITATION OF LIABILITY; WARRANTY REFLECTS ALLOCATION OF RISK – IN ANY EVENT,
IF ANY STATUTE IMPLIES WARRANTIES OR CONDITIONS NOT STATED IN THIS LICENSE
AGREEMENT, DSC’S ENTIRE LIABILITY UNDER ANY PROVISION OF THIS LICENSE
AGREEMENT SHALL BE LIMITED TO THE GREATER OF THE AMOUNT ACTUALLY PAID BY YOU
TO LICENSE THE SOFTWARE PRODUCT AND FIVE CANADIAN DOLLARS (CAD$5.00). BECAUSE
SOME JURISDICTIONS DO NOT ALLOW THE EXCLUSION OR LIMITATION OF LIABILITY FOR
CONSEQUENTIAL OR INCIDENTAL DAMAGES, THE ABOVE LIMITATION MAY NOT APPLY TO
YOU.
DISCLAIMER OF WARRANTIES – THIS WARRANTY CONTAINS THE ENTIRE WARRANTY AND
SHALL BE IN LIEU OF ANY AND ALL OTHER WARRANTIES, WHETHER EXPRESSED OR IMPLIED
(INCLUDING ALL IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A
PARTICULAR PURPOSE) AND OF ALL OTHER OBLIGATIONS OR LIABILITIES ON THE PART OF
DSC. DSC MAKES NO OTHER WARRANTIES. DSC NEITHER ASSUMES NOR AUTHORIZES ANY
OTHER PERSON PURPORTING TO ACT ON ITS BEHALF TO MODIFY OR TO CHANGE THIS
WARRANTY, NOR TO ASSUME FOR IT ANY OTHER WARRANTY OR LIABILITY CONCERNING THIS
SOFTWARE PRODUCT.
EXCLUSIVE REMEDY AND LIMITATION OF WARRANTY – UNDER NO CIRCUMSTANCES SHALL DSC
BE LIABLE FOR ANY SPECIAL, INCIDENTAL, CONSEQUENTIAL OR INDIRECT DAMAGES BASED
UPON BREACH OF WARRANTY, BREACH OF CONTRACT, NEGLIGENCE, STRICT LIABILITY, OR
ANY OTHER LEGAL THEORY. SUCH DAMAGES INCLUDE, BUT ARE NOT LIMITED TO, LOSS OF
PROFITS, LOSS OF THE SOFTWARE PRODUCT OR ANY ASSOCIATED EQUIPMENT, COST OF
CAPITAL, COST OF SUBSTITUTE OR REPLACEMENT EQUIPMENT, FACILITIES OR SERVICES,
DOWN TIME, PURCHASERS TIME, THE CLAIMS OF THIRD PARTIES, INCLUDING CUSTOMERS,
AND INJURY TO PROPERTY.
DSC recommends that the entire system be completely tested on a regular basis.
However, despite frequent testing, and due to, but not limited to, criminal
tampering or electrical disruption, it is possible for this SOFTWARE PRODUCT
to fail to perform as expected.
Regulatory Information
The smoke alarm PG9936/PG8936/PG4936 has a recommended service life of 10
years under normal conditions of use.
Please refer to the label applied to the device indicating the recommended
replacement year. For servicing the unit or replacement batteries please call
your installation company that provided you with the alarm system.
NOTE: In Australia, the device shall not be installed in locations where
the normal ambient temperature is lower than 41°F (5°C) or higher than 113°F
(45°C).
This manual shall be used in conjunction with the Installation Manual of the
alarm control panel. All the instructions specified within that manual must be
observed.
FCC and ISED Canada Compliance Statement
This device complies with FCC Rules Part 15 and with ISED Canada licence-
exempt RSS standard(s). Operation is subject to the following two conditions:
(1) this device may not cause interference, and (2) this device must accept
any interference, including interference that may cause undesired operation of
the device.
CAN ICES-3 (B)/NMB-3(B)
WARNING! To comply with FCC and IC RF exposure compliance requirements,
the device should be located at a distance of at least 20 cm from all persons
during normal operation. The antennas used for this product must not be co-
located or operated in conjunction with any other antenna or transmitter.
Simplified EU declaration of conformity
Hereby, Tyco Safety Products Canada Ltd. declares that the radio equipment
type is in compliance with Directive
2014/53/EU. The full text of the EU declaration of conformity is available at
the following internet address:
PG4936: http://dsc.com/pdf/1709001
PG8936: http://dsc.com/pdf/1709003
Frequency band
433.04 MHz – 434.79 MHz
868.0 MHz – 868.6 MHz
868.7 MHz – 869.2 MHz| Maximum power
10 mW
14 mW
14 mW
---|---
European single point of contact: Tyco Safety Products, Voltaweg 20, 6101 XK
Echt, Netherlands.
DSC, Toronto, Canada Smoke Alarm Device
© 2018 Tyco Security Products. All Rights Reserved.
Tech Support: 1-800-387-3630 (Canada &
U.S.)
or 905-760-3000 •
www.dsc.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>