Overview
What can the DT10 do?
This is a dual relay output temperature controller which can be used as over-
temperature protection and automatic temperature control system for electrical
appliances for home-brew, aquarium, pet breeding, incubation, seedling heat
mat, oven, terrestrial heat pad/lamp, heating pump, home fermentation,
electric radiator, electric oven etc.
The temperature controller is equipped with a dual relay to connect with both
refrigeration and heating equipment to get the desired temperature. The dual
LED displays and offers display switch between Centigrade and Fahrenheit. With
its 1800 watt capacity, can handle most any 120 volt appliance.
The DT10 is designed with compressor delay protection for refrigeration, high
and low temperature alarm and sensor fault alarm. Functions such as
temperature calibration, separately set differential for refrigeration and
heating, enable more accurate temperature control.
Main Features
- Plug and play design, easy to use;
- Dual relay output, be able to connect with refrigeration and heating equipment at the same time;
- Support reading with Centigrade or Fahrenheit;
- Maximum output: 1800W 15A.
- Dual display window to display measured temperature and set temperature at the same time;
- Temperature calibration;
- Compressor delay protection for refrigeration control;
- High and low temperature alarms are available;
- Over-temperature and sensor fault alarm;
- Heating/cooling differential function can be set separately for refrigeration and heating.
Specification
Temperature Control Range | -50~99 °C / -50~210 ° F |
---|---|
Temperature Resolution | 0.1 ° C / 0.1° F |
Temperature Accuracy | ±1°C (-50 ~ 70°C) / ±1°F (-50 ~ 160° F) |
Temperature Control Mode | On/Off Control, Heating and Cooling |
Input Power | 115V |
Output | Max. 1800 watts, 15A, 115V |
Buzzer Alarm | High and Low Temperature Alarm |
Sensor Type | NTC sensor (Included) |
Sensor Length | 2m / 6.56ft |
Relay Contact Capacity
| Cooling (15A, 115V)
Heating (15A, 115V)
Input Power Cable Length| 1.5m (5ft)
Output Power Cable Length| 1.5m (5ft)
Dimensions
| Main Body: 145x68x30mm (5.5×2.7×1.3 inch) Socket : 83x43x25mm (3.3×1.7×1.0
inch)
Ambient Temperature| -30~ 75 ° C / -22~ 167 ° F
Storage
| Temperature -20~ 60 ° C / -4~ 140 ° F
Humidity 20~85% (No Condensate)
Warranty| 1 Year
Keys Instruction
- PV: Process Value. under running mode, display current measured temperature; under setting mode, display menu code.
- SV: Setting Value. under running mode, display setting temperature; under setting mode, display setting value.
- Cooling indicator: when the light is on, start refrigeration; when the light is flickering, the compressor is under delay protection.
- Heating Indicator: when the light is on, start heating.
- SET key: press SET key for 3 seconds to enter menu for function setting. During the setting process, press SET key for 3 seconds to quit and save setting changes.
- DECRESE key: under running mode, press DECRESE key to inquiry CD value; under setting mode, press DECRESE key to decrease value.
- INCREASE key: under running mode, press INCREASE key to inquiry HD value; under setting mode, press INCREASE key to increase value.
- Heating Device Socket: this socket is for heating output.
- Cooling Device Socket: the socket is for refrigeration output.
Key Operation Instructions
Enquiry Set Point
When the controller is working, short press the “UP” key for one time, the
heating differential (HD) will be displayed; short press the “ DOWN ” key for
one time, then the cooling differential (CD) will be displayed. The screen
will return to normal display mode after 2 seconds without any operate.
How to Set Parameters
When the controller is working normally, press “SET” key for over 3 seconds to
enter into parameters set up mode. “SET” indicator will be on. PV window
displays the first menu code “TS”, while SV window displays according setting
value. Press “SET” key to go to next menu and display according menu code,
press “UP” key or “DOWN” key to set current parameter value. After setting
done, press “SET” key for 3 seconds at any time to save the parameters change
and return to normal temperature display mode. During setting, if there is no
operation for 10 seconds, the system will quit setting mode and return to
normal temperature display mode without saving the parameters change.
Setup Flow Chart
Menu Instruction
When the temperature is displayed in Centigrade
Menu code| Function| Setting range| Default setting|
Remarks
---|---|---|---|---
TS| Temperature Set Value| -50~99.9℃| 25℃| ****
5.1
HD| Heating Differential Value| 0.3~15℃| 2.0℃
CD| Cooling Differential Value| 0.3~15℃| 2.0℃
AH| Alarm High Limit| -50~99.9℃| 90℃| 5.2
AL| Alarm Low Limit| -50~99.9℃| -40℃
PT| Compressor Delay| 0~10 minutes| 3 minutes| 5.3
CA| Temperature Calibration| -15℃~15℃| 0℃| 5.4
CF| Display in Fahrenheit or
Centigrade
| | C| 5.5
When the temperature is displayed in Fahrenheit
Menu code| Function| Setting range| Default setting|
Remarks
---|---|---|---|---
TS| Temperature Set Value| -50~210℉| 77℉| ****
5.1
HD| Heating Differential Value| 1~30℉| 3℉
CD| Cooling Differential Value| 1~30℉| 3℉
AH| Alarm High Limit| -50~210℉| 200℉| 5.2
AL| Alarm Low Limit| -50~210℉| -40℉
PT| Compressor Delay| 0~10 minutes| 3 minutes| 5.3
CA| Temperature Calibration| -15℃~15℉| 0℉| 5.4
CF| Display in Fahrenheit or
Centigrade
| | F| 5.5
Temperature Control Range Setting (TS, HD, CD)
When the controller is working normally, the LED displays current measured
temperature (PV), and will automatically identify and switch between
refrigeration and heating working modes. When the measured temperature PV ≥ TS
(temperature you set) + CD (cooling differential value), system enters
refrigeration status, the cool indicator will be on, and refrigeration relay
starts to work; when the cool indicator is flickering, it means the
refrigeration equipment is under compressor delay protection status. When the
measured temperature PV≤TS (temperature set value), the cool indicator will be
off, and the refrigeration relay stops working. When the measured temperature
PV≤TS (temperature set value)-HD (heating differential value), system enter
heating status, the heat indicator will be on and heating relay starts to
work; when the measured temperature PV≥ TS (temperature setting), the heat
indicator will be off, then heating relay stops working. For example, if set
TS=75°F, CD=2°F and HD=3°F, then when measured temperature is higher than or
equal to 77°F ( TS+CD), system enters refrigeration status; when temperature
decline to 75°F (TS), stop refrigeration; when measured temperature is lower
or equal to 72°F(TS-HD), system enters heating status; when the temperature
raised to 75°F (TS), stop heating. Repeat that so as to get the desired
temperature range we want.
In case the time interval between two refrigeration is less than PT, please
refer to 5.3.
Alarm High/Low Limit Setting (AH, AL)
When the measured temperature is higher or equal to AH, the high-temperature
alarm will be triggered, the buzzer will alarm with tone “bi-bi-Biii” until
the temperature is lower than AH or any key is pressed. When measured
temperature is lower or equal to AL, low-temperature alarm will be triggered,
the buzzer will alarm with tone “bi-bi-Biii” until the temperature >AL or any
key is pressed.
Compressor Delay (PT)
Under refrigeration mode, after power on, if the measured temperature is
higher than set temperature (TS) plus cooling differential (CD), the equipment
won’t start refrigeration immediately but waiting for a delay time.
When the time interval between two refrigeration operations is larger than
preset delay, the equipment will start refrigeration immediately; when the
time interval between two refrigeration is less than preset delay, the
equipment won’t start refrigeration until the preset delay is satisfied. Delay
time will be calculated right after the moment the refrigeration stops.
Temperature Calibration (CA)
If there is a deviation between measured temperature and actual temperature,
use temperature calibration function to align the measured temperature and
actual temperature.
Display in Fahrenheit or Centigrade unit (CF)
Customers can set the temperature display in Fahrenheit or Centigrade
according to their own habit. Default display is in Centigrade temperature. To
display in Fahrenheit, set CF value as F.
Attention: when CF value changed, all the setting value will be recovered to
factory settings.
Error Description
Sensor Fault Alarm: when the temperature sensor is in a short circuit or open loop, the controller will initiate sensor fault mode, and cancel all the actions. The buzzer will alarm, LED displays ER. Buzzer alarm could be dismissed by pressing any key. After the faults are solved, the system will return to normal working mode. Over-temperature Alarm: when the measured temperature exceeds the measuring range (less than -50°C /-58° F or higher than 99 °C/210 ° F), the controller will initiate over-temperature alarm mode, and cancel all the actions. The buzzer will alarm, LED displays HL. The buzzer alarm could be dismissed by pressing any key. When the temperature returns to measuring range, the system will return to normal working status.