Bi-level ANT-5-4T Microwave Sensor for High Bay Light Instructions
- June 9, 2024
- Bi-level
Table of Contents
Bi-level Microwave Sensor For High Bay Light
ANT-5-4T Instruction
INTRODUCTION
The ANT-5-4T is a motion sensor that dims lighting from high to low based on
movement. This slim, low-profile sensor is designed for installation inside
the bottom of a light fixture body.
The sensors use microwave sensing technology that reacts to changes in
movement within the coverage area.
Once the sensor stops detecting movement and the time delay elapses lights
will go from high to low mode and eventually to an OFF position if it is
desired. Sensors must directly “see” motion of a person or moving object to
detect them, so careful consideration must be given to sensor luminaire
placement and lens selection. Avoid placing the sensor where obstructions may
block the sensor’s line of sight.
SPECIFICATIONS
Power supply | 12V-24V DC, >50mA |
---|---|
Dim control output | 0-10y, max. 25mA sinking current |
HF System | 5.8GHz±75MHz |
Transmission power | <0.2mW |
Detection radius | 20%/50%/75%/100`)/0(1-8m) |
Mounting height | Max 50ft.(15meters) |
Time setting | 10s/1min/5min/10min/15min/20min/30min/60min |
Light-control | 24H/10LUX/30LUX/50LUX |
Temperature | -4°F – +140°F (-20°C – +60°C) |
IP rating | IP65 |
WARNING
NOTE: Warm up time is 15seconds. After the sensor connects input power first
time, the light will keep on 15seconds, then go to dimming to work normally.
NOTE: Factory Default Setting: 100% sensitivity, Hold on time: 5min,
Daylight sensor is , Dimming level: 30%,Dimming time: 6Ominitues.
NOTE: Any setting changed by remote control, the led light that sensor
connect will on/off as confirm.
CORRIDOR FUNCTION
This function inside the motion sensor to achieve tri-level control, for some areas which require a light change notice before switch-off. The sensor offers 3 levels of light: 100%–>dimmed light (natural light is insufficient) –>off; and 2 periods of selectable waiting time: motion hold-time and stand-by period; Selectable daylight threshold and freedom of detection area.
|
---|---
With sufficient natural light, the light does not switch on when
presence is detected.| With insutficient natural light, the sensor switches on
the light automatically when presence is detected.
|
After hold-time, the light dims to stand-by level if the surrounding natural
light is below the daylight threshold.| Light switches off automatically after
the stand-by period elapses.
DAYLIGHT SENSOR FUNCTION
Open the daylight sensor by push when remote control is in setting condition.
| |
---|---|---
The light switches on at 100% when there is
movement detected.| The light dims to stand-by
level after the hold-time.| The light remains in dimming
level at night.
| |
| When the natural light level exceeds setpoint off to light, the light will
turn off even if when the space is occupied.| The light automatically turns on
at 10% when natural light is insuffcient (no motion).
Settings on this demonstration:
Hold-time: 30min
Setpoint on:50lux
Setpoint off:300lux
Stand-by Dim: 10%
Stand-by period: +∞
(when the smart photocell sensor open, the stand-by time is only +∞)
SENSOR COVERAGE
V1.0
Documents / Resources
| Bi-
level ANT-5-4T Microwave Sensor for High Bay
Light
[pdf] Instructions
ANT-5-4T Microwave Sensor for High Bay Light, ANT-5-4T, Microwave Sensor for
High Bay Light, Sensor for High Bay Light, High Bay Light, Bay Light
---|---
Read User Manual Online (PDF format)