Altronix ALTV615DCUL 16 Fused Outputs CCTV Power Supply Installation Guide
- June 4, 2024
- Altronix
Table of Contents
More than just power.™
ALTV615DCUL Series
CCTV Power Supplies
Installation Guide
Models Include:
ALTV615DC416UL
– 6-15VDC @ 4A
– Sixteen (16) fuse-protected outputs| ALTV615DC416ULCB
– 6-15VDC @ 4A
– Sixteen (16) PTC-protected outputs
---|---
ALTV615DC616UL
– 6-15VDC @ 6A
– Sixteen (16) fuse-protected outputs| ALTV615DC616ULCB
– 6-15VDC @ 6A
– Sixteen (16) PTC-protected outputs
Overview:
ALTV615DCUL Series DC CCTV Power Supplies provide 6 – 15VDC distributed via fuse or PTC protected outputs for powering CCTV cameras, heaters, and other video accessories.
ALTV615DCUL Series Reference Chart:
Altronix Model Number| 115VAC 50/60Hz
Input Current| Output Voltage| Total Output
Current (Power)| Number of
Outputs| Output Current
(max per output)| Fuse Protected
Outputs| PTC Protected
Outputs
(auto-resettable)| Class 2 Rated
Power-Limited
---|---|---|---|---|---|---|---|---
ALTV615DC416UL| 0.9A| 6 – 15VDC| 4A| 16| 3.5A| √| –| √
ALTV615DC416ULCB| 0.9A| 6 – 15VDC| 4A| 16| 2.5A| –| √| √
ALTV615DC616UL| 1.5A| 6 – 15VDC| 6A| 16| 3.5A| √| –| –
ALTV615DC616ULCB| 1.5A| 6 – 15VDC| 6A| 16| 2.5A| –| √| √
Specifications:
Agency Listings:
- UL Listed for Commercial CCTV Equipment (UL 2044).
CUL Listed – CSA Standard C22.2 No.1-98, Audio, Video, and Similar Equipment.
Input:
- Input 115VAC, 50/60Hz.
Output:
- Sixteen (16) individual outputs.
- 6VDC to 15VDC field adjustable.
- Outputs are rated @ 3.5A (fused) or 2.5A (PTC).
- Filtered and electronically regulated outputs.
Features:
- AC input and DC output LED indicators.
- Power ON/OFF switch.
- The unit maintains camera synchronization.
- Ease of installation saves time and eliminates costly labor.
Enclosure Dimensions (H x W x D approx.): 13.5” x 13” x 3.25” (342.9mm x 330.2mm x 82.6mm).
CAUTION: This installation should be made by qualified service personnel and should conform to the National Electrical Code and all local codes.
Installation Instructions:
-
Mount the unit in the desired location.
-
Connect AC power to the two black and two white flying leads of the transformer (Fig. 1, pg. 3).
Units with line cord installed skip Step 2.
Use 18 AWG or larger for all power connections. Connect the green ground leads to earth ground (Fig. 1, pg. 3).
Keep power-limited wiring separate from non-power-limited wiring.
Minimum 0.25” spacing must be provided. Use separate knockouts. -
Adjust output voltage (unit is factory set at 12VDC): use the trimpot on the power supply board prior to connecting CCTV devices (Fig. 1a, pg. 3).
-
Measure output voltage before connecting devices. This helps avoid potential damage.
CAUTION: Determine the maximum operating voltage of the equipment being powered before adjusting the output voltage. -
Connect devices to the terminals marked [1P – 1N] through [16P – 16N] on PD16W/PD16WCB board, carefully observing the correct polarity (Fig. 1, pg. 3).
Terminals marked [1P – 16P] are positive (+) and terminals marked [1N – 16N] are negative (–). -
Green LED will illuminate when the unit is powered.
-
Upon completion of wiring secure enclosure door with screws (supplied).
WARNING: To reduce the risk of fire or electric shock, do not expose the unit to rain or moisture.
Terminal Identification:
Power Supply Board
Terminal Legend | Function/Description |
---|---|
AC/AC | Low voltage AC input. |
+ DC – | 6VDC -15VDC output. |
PD16W/PD16WCB – Distribution Module
1P – 16P | Positive DC outputs. |
---|---|
1N – 16N | Negative DC outputs. |
Fig. 1
CAUTION: De-energize the unit prior to servicing. For continued
protection against fire, and hazards replace the fuse with the same type and
rating: 3.5A, 250V. Do not expose the unit to rain or moisture.
The lightning flash with an arrowhead symbol within an equilateral triangle is
intended to alert the user to the presence of an insulated DANGEROUS VOLTAGE
within the product’s enclosure that may be of sufficient magnitude to
constitute an electric shock.
The exclamation point within an equilateral triangle is intended to alert the
user to the presence of important operating and maintenance (servicing)
instructions in the literature accompanying the appliance.
CAUTION: To reduce the risk of electric shock do not open the enclosure.
There are no user-serviceable parts inside.
Refer servicing to qualified service personnel.
Enclosure Dimensions (H x W x D approximate): 13.5” x 13” x 3.25” (342.9mm x 330.2mm x 82.6mm)
For models with the factory-installed 3-wire line, cord add the suffix “3”, e.g. ALTV615DC616UL3
Installing Company:
Service Rep. Name: ____
Address: ____
Phone #: ____
Altronix is not responsible for any typographical errors.