VEGATRENN 141 Channel Separator
Product Information
VEGATRENN 141 Ex Separator for 4 … 20 mA
Sensors
The VEGATRENN 141 is an Ex separator designed for use with 4 … 20 mA/HART
sensors in a two-wire version. The instrument is intended for use in hazardous
areas and has a separate power supply for safe operation. The device ensures
operational reliability when used according to the specifications outlined in
the operating instructions manual.
Target Audience
This operating instructions manual is intended for trained personnel who are
authorized by the plant operator. The contents of this manual must be made
available to qualified personnel and implemented.
Safety Information
During work on and with the device, the required personal protective equipment must always be worn. Inappropriate or incorrect use of this product can give rise to application-specific hazards, e.g. vessel overfill through incorrect mounting or adjustment. Damage to property and persons or environmental contamination can result. Also, the protective characteristics of the instrument can be impaired.
Product Usage Instructions
Mounting
Before mounting the VEGATRENN 141, please read the general instructions provided in section 4.1 of the operating instructions manual. Ensure that the device is mounted securely and safely to prevent any damage or hazards.
Setup
To set up the VEGATRENN 141, refer to section 6 of the operating instructions manual. This section provides information on the adjustment system and adjustment elements required for proper setup.
Dismounting
If you need to dismount the VEGATRENN 141, follow the steps outlined in section 8.1 of the operating instructions manual. Also, refer to section 8.2 for information on proper disposal methods.
About this document
Function
This instruction provides all the information you need for mounting,
connection and setup as well as important instructions for maintenance, fault
rectification, the exchange of parts and the safety of the user. Please read
this information before putting the instrument into operation and keep this
manual accessible in the immediate vicinity of the device.
Target group
This operating instructions manual is directed to trained personnel. The
contents of this manual must be made available to the qualified personnel and
implemented.
Symbols used Document ID
This symbol on the front page of this instruction refers to the Document ID.
By entering the Document ID on www.vega.com you will
reach the document download.
Information, note, tip: This symbol indicates helpful additional information
and tips for successful work.
Note: This symbol indicates notes to prevent failures, malfunctions, damage to devices or plants.
Caution: Non-observance of the information marked with this symbol may result in personal injury.
Warning: Non-observance of the information marked with this symbol may result in serious or fatal personal injury.
Danger: Non-observance of the information marked with this symbol results in serious or fatal personal injury.
Ex applications
This symbol indicates special instructions for Ex applications.
List
The dot set in front indicates a list with no implied sequence.
Sequence of actions
Numbers set in front indicate successive steps in a procedure.
Disposal
This symbol indicates special instructions for disposal.
For your safety
Authorised personnel
All operations described in this documentation must be carried out only by
trained, qualified personnel authorised by the plant operator.
During work on and with the device, the required personal protective equipment
must always be worn.
Appropriate use
VEGATRENN 141 is an [Ex ia] separator with separate power supply for
connection of 4 … 20 mA/HART sensors in two-wire version.
You can find detailed information about the area of application in chapter ”
Product description”.
Operational reliability is ensured only if the instrument is properly used
according to the specifications in the operating instructions manual as well
as possible supplementary instructions.
Warning about incorrect use
Inappropriate or incorrect use of this product can give rise to applica-tion-
specific hazards, e.g. vessel overfill through incorrect mounting or
adjustment. Damage to property and persons or environmental contamination can
result. Also, the protective characteristics of the instrument can be
impaired.
General safety instructions
This is a state-of-the-art instrument complying with all prevailing
regulations and directives. The instrument must only be operated in a
technically flawless and reliable condition. The operator is responsi-ble for
the trouble-free operation of the instrument. When measuring aggressive or
corrosive media that can cause a dangerous situation if the instrument
malfunctions, the operator has to implement suitable measures to make sure the
instrument is functioning properly.
The safety instructions in this operating instructions manual, the na-tional
installation standards as well as the valid safety regulations and accident
prevention rules must be observed by the user.
For safety and warranty reasons, any invasive work on the device beyond that
described in the operating instructions manual may be carried out only by
personnel authorised by the manufacturer. Arbitrary conversions or
modifications are explicitly forbidden. For safety reasons, only the accessory
specified by the manufacturer must be used.
To avoid any danger, the safety approval markings and safety tips on the
device must also be observed.
Installation and operation in the USA and Canada
This information is only valid for USA and Canada. Hence the following text
is only available in the English language.
Installations in the US shall comply with the relevant requirements of the
National Electrical Code (ANSI/NFPA 70).
Installations in Canada shall comply with the relevant requirements of the
Canadian Electrical Code.
Safety instructions for Ex areas
For applications in explosion-proof areas (Ex), only devices with cor-
responding Ex approval may be used. Observe the Ex-specific safety
instructions. These are an integral part of the operating instructions and are
enclosed with every device with Ex approval.
Product description
Configuration
The scope of delivery encompasses:
Scope of delivery
- VEGATRENN 141
- Documentation
- This operating instructions manual
- Ex-specific ” Safety instructions” (depending on the version)
- If necessary, further certificates
Type label
The type label contains the most important data for identification and use of
the instrument:
- Instrument type
- Information about approvals
- Technical data
- Serial number of the instrument
- QR code for device documentation
- Manufacturer information
Documents and software
Move to ” www.vega.com” and enter in the search
field the serial number of your instrument.
There you can find the following information about the instrument:
- Order data
- Documentation
- Software
Alternatively, you can find all via your smartphone:
- Scan the QR-code on the type label of the device or
- Enter serial number manually in the VEGA Tools app (available free of charge in the respective stores)
Application area
Principle of operation
VEGATRENN 141 is an [Ex ia] separator with separate power supply for
connection of 4 … 20 mA/HART sensors in two-wire version. As an associated
electrical device, it ensures a galvanic separation between sensor circuit and
processing circuit and thus between Ex and non-Ex areas.
Functional principle
An integrated transmitter power supply powers the connected sensor. The
current signal from the sensor (4 … 20 mA) is transferred to the output
linearly and galvanically separated. The instrument is HART transparent, i.e.
the HART signals are transmitted bidirectionally between input and output.
Adjustment
No adjustment or configuration of VEGATRENN 141 is necessary. A parameter
adjustment of the connected sensors can be carried out via the HART
communication sockets behind the hinged front cover. Adjustment of the
connected sensors is carried out preferably via a Windows PC with a parameter
adjustment software such as PACT-ware and corresponding DTM. A VEGACONNECT
interface adapter or a HART modem is necessary for connecting the PC.
**Packaging, transport and storage
**
Packaging
Your instrument was protected by packaging during transport. Its capacity to
handle normal loads during transport is assured by a test based on ISO 4180.
The packaging of standard instruments consists of environment-friendly,
recyclable cardboard. For special versions, PE foam or PE foil is also used.
Dispose of the packaging material via specialised recycling companies.
Transport
Transport must be carried out in due consideration of the notes on the
transport packaging. Nonobservance of these instructions can cause damage to
the device.
Transport inspection
The delivery must be checked for completeness and possible transit damage
immediately at receipt. Ascertained transit damage or concealed defects must
be appropriately dealt with.
Storage
Up to the time of installation, the packages must be left closed and stored
according to the orientation and storage markings on the outside.
Unless otherwise indicated, the packages must be stored only under the
following conditions:
Storage and transport temperature
- Not in the open
- Dry and dust free
- Not exposed to corrosive media
- Protected against solar radiation
- Avoiding mechanical shock and vibration
- Storage and transport temperature see chapter ” Supplement – Technical data – Ambient conditions”
- Relative moisture 20 … 85 %
Mounting
**General instructions
**
Mounting options
VEGATRENN 141 is designed for carrier rail mounting (top hat rail 35 x 7.5
according to DIN EN 50022/60715). Due to its protection rating of IP20, the
instrument is suitable for mounting in switching cabinets. It can be mounted
horizontally and vertically.
Note:
When several instruments are mounted together without space in between, the
ambient temperature at the installation location of the instrument must not
exceed 60 °C. Around the ventilation slots there must be a distance of at
least 2 cm to the next component.
VEGATRENN 141 is a corresponding, intrinsically safe equipment and must not be
installed in hazardous areas of zone 0/1. A safe operation is only ensured if
the operating instructions and EU type approval certificate are observed.
VEGATRENN 141 must not be opened.
A distance of 50 mm to the intrinsically safe terminals must be en-sured when
mounting.
Ambient conditions
The instrument is suitable for standard and extended ambient conditions acc.
to DIN/EN/IEC/ANSI/ISA/UL/CSA 61010-1.
Make sure that the environmental and ambient conditions specified in chapter ”
Technical data” are maintained.
Connecting to power supply
Preparing the connection
Always keep in mind the following safety instructions:
Warning:
Connect only in the complete absence of line voltage.
- Connect only in the complete absence of line voltage
- If overvoltage surges are expected, overvoltage arresters should be installed
Safety instructions for Ex applications
Note:
Install a disconnecting device for the instrument which is easy to access. The
disconnecting device must be marked for the instrument (IEC/EN 61010).
Voltage supply
In hazardous areas you must take note of the respective regulations,
conformity and type approval certificates of the sensors and power supply
units.
The data for power supply are specified in chapter ” Technical data”.
Connection cable
The voltage supply of VEGATRENN 141 is connected with standard cable according
to the national installation standards.
Make sure that the cable used has the required temperature resist-ance and
fire safety for max. occurring ambient temperature
The sensors are connected with standard two-wire cable without shielding. If
electromagnetic interference is expected which is above the test values of EN
61326 for industrial areas, shielded cable should be used. In general, cable
screening is necessary in HART multidrop mode.
Cable screening and grounding
Connect the cable shielding on both ends to ground potential. In the sensor,
the shielding must be connected directly to the internal ground terminal. The
ground terminal on the outside of the sensor housing must be connected to the
potential equalisation (low impedance).
If potential equalisation currents are expected, the connection on the
processing side must be made via a ceramic capacitor (e. g. 1 nF, 1500 V). The
low-frequency potential equalisation currents are thus suppressed, but the
protective effect against high frequency interference signals remains.
Connection cable for Ex applications
Take note of the corresponding installation regulations for Ex applications.
In particular, make sure that no potential equalisation currents flow over the
cable screen. In case of grounding on both sides this can be achieved by the
use of a capacitor or a separate potential equalisation.
HART communication
The instrument is equipped with communication sockets in the front for
connection of a VEGACONNECT or another HART handheld as well as an integrated
HART resistor.
If the resistance of the connected processing system is less than 230 Ω, the
digital adjustment signal is extremely damped or short-circuited. Digital
communication with the PC is then no longer possible. With low impedance
processing systems, a resistor of approx. 230 Ω must be looped into the 4 … 20
mA cable. This resistor is already integrated in VEGATRENN 141 and can be
chosen through the selection of the respective terminals.
No additional resistor is required in the sensor circuit for direct connection
of a HART-Master. When connecting a VEGADIS 82, the communication resistor in
the VEGADIS 82 must be deactivated.
HART multidrop mode
In HART multidrop mode, the measured values are transmitted
on the same cable (bus) as the digital HART signals. An analogue 4 … 20 mA
transmission is not possible, the current is limited to 4 mA. An own,
unambiguous address (address range 1-15) must be as-signed to each connected
sensor. In this mode, up to five sensors can be connected to one channel.
Information:
When using a HART resistor, keep in mind that there is an additional voltage
loss. You can find details in chapter ” Technical data”.
Connection procedure
The pluggable terminals can be removed as needed to allow more convenient
connection. To make the electrical connection, proceed as follows:
- Mount the instrument as described in the previous chapter
- Connect sensor cable to terminal 1/2, and where applicable, connect the shielding
- Connect switched-off power supply to terminal 16/17
- Connect processing circuit, e.g. from PLC to terminal 11/12 or 10/12 (with HART resistor), and shielding, if necessary
The electrical connection is finished.
Note:
If several sensors should be connected in HART multidrop mode, a respective
HART address must be assigned to each sensor before connecting to VEGATRENN
141.
Wiring plan
- Sensor circuit (4 … 20 mA/HART, Ex area)
- HART communication sockets for connection of a HART handheld, e.g. a VEGACONNECT
- Processing circuit (4 … 20 mA/HART, active output)
- Processing circuit (4 … 20 mA/HART, active output with looped HART resistor)
- Voltage supply
Information:
The connection terminals can be detached towards the front, if necessary. This
can be useful when working in tight spaces or when exchanging an instrument.
Setup
Adjustment system
Fig. 1: Display and adjustment elements
- HART communication sockets
- Signal lamps (LEDs)
- Hinged front cover
Adjustment elements
Control lamps (LED) in the front plate indicate operation and fault signal.
Control lamps
- Green operating control lamp lights in case of
- Mains voltage, instrument is operating
- Red fault lamp lights in case of
- Short-circuit on the input
- Line break on the output
- Too high load on the output
- Internal faults
Front cover
The adjustment elements are located under a hinged front cover. To open it,
use a small screwdriver in conjunction with the slot on the upper side of the
front cover. To close it, push the cover at bottom and top firmly onto the
front cover until you hear the two retaining clips snap in.
HART communication sockets
No adjustment or configuration of VEGATRENN 141 is necessary. Via the HART
communication sockets, parameter adjustment of the connected HART sensors can
be carried out without interrupting the measuring circuit. The resistor (230
Ω) required for this purpose is already integrated in VEGATRENN 141 (only in
case of connection of terminals 10/12). The adjustment of the connected sensor
is carried out via a Windows PC with a parameter adjustment software such as
e.g. PACTware and corresponding DTM.
Diagnostics and servicing
Maintenance
If the device is used properly, no special maintenance is required in normal
operation.
The cleaning helps that the type label and markings on the instrument are
visible.
Take note of the following:
Cleaning
- Use only cleaning agents which do not corrode the housings, type label and seals
- Use only cleaning methods corresponding to the housing protection rating
Rectify faults
Reaction when malfunction occurs
The operator of the system is responsible for taking suitable measures to
rectify faults.
Causes of malfunction
Maximum reliability is ensured. Nevertheless, faults can occur during
operation. These may be caused by the following, e.g.:
- Voltage supply
- Interference in the cables
Fault rectification
The first measure to be taken is to check the input/output signal as well as
the power supply. In many cases, the causes can be deter-mined and faults can
be quickly rectified.
Reaction after fault rectification
Depending on the reason for the fault and the measures taken, the steps
described in chapter ” Setup” must be carried out again or must be checked for
plausibility and completeness.
24 hour service hotline
Should these measures not be successful, please call in urgent cases the VEGA
service hotline under the phone no. +49 1805 858550.
The hotline is also available outside normal working hours, seven days a week
around the clock.
Since we offer this service worldwide, the support is provided in English. The
service itself is free of charge, the only costs involved are the normal call
charges.
How to proceed if a repair is necessary
You can find an instrument return form as well as detailed information about
the procedure in the download area of our homepage. By doing this you help us
carry out the repair quickly and without having to call back for needed
information.
In case of repair, proceed as follows:
- Print and fill out one form per instrument
- Clean the instrument and pack it damage-proof
- Attach the completed form and, if need be, also a safety data sheet outside on the packaging
- Ask the agency serving you to get the address for the return shipment. You can find the agency on our homepage.
Dismount
Dismounting steps
Take note of chapters ” Mounting” and ” Connecting to voltage sup-ply” and
carry out the listed steps in reverse order.
Disposal
Pass the instrument on to a specialised recycling company and do not use the
municipal collecting points.
Remove any batteries in advance, if they can be removed from the device, and
dispose of them separately.
If personal data is stored on the old device to be disposed of, delete it
before disposal.
If you have no way to dispose of the old instrument properly, please contact
us concerning return and disposal.
Certificates and approvals
Approvals for Ex areas
Approved versions for use in hazardous areas are available or in preparation
for the device or the device series.
You can find the relevant documents on our homepage.
EU conformity
The device fulfils the legal requirements of the applicable EU direc-tives. By
affixing the CE marking, we confirm the conformity of the instrument with
these directives.
The EU conformity declaration can be found on our homepage.
SIL conformity
Instruments with SIL option fulfill the requirements of functional safety
according to IEC 61508. You can find further information in the sup-plied
Safety Manual.
Environment management system
Protection of the environment is one of our most important duties. That is why
we have introduced an environment management system with the goal of
continuously improving company environmental pro-tection. The environment
management system is certified according to DIN EN ISO 14001. Please help us
fulfil this obligation by observ-ing the environmental instructions in
chapters ” Packaging, transport and storage”, ” Disposal” of these operating
instructions.
Technical data
Note for approved instruments
The technical data in the respective safety instructions are valid for
approved instruments (e.g. with Ex approval). In some cases, these data can
differ from the data listed herein.
All approval documents can be downloaded from our homepage.
General data
- Series : Module unit for mounting on carrier rails 35 x 7.5 acc. to EN 50022/60715
- Weight : 160 g (5.14 oz)
- Housing material : Polycarbonate PC-FR
Connection terminals
- Type of terminal : Screw terminal
- Wire cross-section : 0.25 mm² (AWG 23) … 2.5 mm² (AWG 12)
- HART communication sockets : ø 2 mm
Voltage supply
Operating voltage
- Nominal voltage AC : 24 … 230 V (-15 %, +10 %) 50/60 Hz
- Nominal voltage DC : 24 … 65 V (-15 %, +10 %)
- Max. power consumption : 3 W (15 VA)
Sensor input
- Number of sensors : 1 x 4 … 20 mA/HART (5 x HART multidrop)
- Input type : Active (sensor power supply by VEGATRENN 141)
- Terminal voltage : 21 … 16.5 V DC at 4 … 20 mA
- Off-load voltage : 24 V DC (+/- 1 V)
- Short-circuit current : < 26 mA
- Residual ripple : < 50 mV RMS
Processing circuit
- Quantity : 1 x 4 … 20 mA/HART
- Type of output : Active
- Off-load voltage : < 15.5 V DC
- Residual ripple of the output current : < 50 μA RMS
- Current on the input in case of short circuit : < 10 μA
Current without connected sensor
- In the range of +20 … +60 °C (+68 … +140 °F) : < 50 μA
- In the range of -20 … +20 °C (-4 … +68 °F) : < 200 μA
Max. connectable load 1)
- at 20 mA : 600 Ohm
- at 22 mA : 550 Ohm
Deviation
- Reference conditions : Calibration temperature 25 °C (77 °F)
- Linearity : < 0.1 %
Influence of the ambient temperature
- In the range of +20 … +60 °C : < 0.2 % (+68 … +140 °F)
- In the range of -20 … +20 °C : < 0.6 %
Deviation due to strong, high-frequency electromagnetic fields (EN 61326) : < 0.5 %
Integrated HART resistor
Resistance value : 232 Ω
Indicators
LED displays
- Status, operating voltage : LED green
- Status fault signal : LED red
Ambient conditions
- Ambient temperature at the installation site of the instrument : -20 … +60 °C (-4 … +140 °F)
- Storage and transport temperature : -40 … +70 °C (-40 … +158 °F)
- Relative humidity : < 96 %
Mechanical environmental conditions
- Vibrations (oscillations) : Class 4M4 acc. to IEC 60721-3-4 (1 g, 4 … 200 Hz)
- Impacts (mechanical shock) : Class 6M4 acc. to IEC 60721-3-6 (10 g/11 ms, 30 g/6 ms, 50 g/2.3 ms)
Electrical protective measures
- Protection rating : IP20
- Overvoltage category (IEC 61010-1)
- up to 2000 m (6562 ft) above sea level II
- up to 5000 m (16404 ft) above sea
- level II – Only with connected overvoltage protection with response voltage of < 1000 V
- up to 5000 m (16404 ft) above sea level :I
- Protection class : II
Measures for electrical separation
Reliable separation according to VDE 0106 part 1 between all circuits
- Reference voltage 253 V
- Insulation resistance (voltage supply – output) : 5.1 kV DC
- Insulation resistance (input – output) : 2.55 kV DC
Approvals
Instruments with approvals can have different technical specifications
depending on the version.
For that reason the associated approval documents of these instruments have to
be carefully noted. They are part of the delivery or can be downloaded by
entering the serial number of your instrument into the search field under
www.vega.com as well as in the general download area.
Dimensions
Fig. 2: Dimensions VEGATRENN 141
Industrial property rights
VEGA product lines are global protected by industrial property rights. Further
information see www.vega.com.
Trademark
All the brands as well as trade and company names used are property of their
lawful proprietor/originator.
All statements concerning scope of delivery, application, practical use and
operating conditions of the sensors and processing systems correspond to the
information available at the time of printing.
Subject to change without prior notice