VENTS-US Airvents RV Air Handling Unit Owner’s Manual
- June 9, 2024
- VENTS-US
Table of Contents
Airvents RV Air Handling Unit
Owner’s Manual
Airvents RV Air Handling Unit
This user’s manual is a main operating document intended for technical,
maintenance, and operating staff.
The manual contains information about purpose, technical details, operating
principle, design, and installation of the Airvents RV unit and all its
modifications.
Technical and maintenance staff must have theoretical and practical training
in the field of ventilation systems and should be able to work in accordance
with workplace safety rules as well as construction norms and standards
applicable in the territory of the country.
SAFETY REQUIREMENTS
THE UNIT MUST BE GROUNDED!
DO NOT BEND THE POWER CABLE.
AVOID DAMAGING THE POWER CABLE.
DO NOT PUT ANY FOREIGN OBJECTS ON THE POWER CABLE.
DO NOT USE DAMAGED EQUIPMENT OR CABLES WHEN CONNECTING THE UNIT TO POWER
MAINS.
DO NOT TOUCH THE UNIT CONTROLS WITH WET HANDS.
DO NOT CARRY OUT THE INSTALLATION AND MAINTENANCE OPERATIONS WITH WET HANDS.
DO NOT ALLOW CHILDREN TO OPERATE THE UNIT.
DO NOT STORE ANY EXPLOSIVE OR HIGHLY FLAMMABLE SUBSTANCES IN CLOSE PROXIMITY
TO THE UNIT.
DO NOT OPEN THE UNIT DURING OPERATION.
DO NOT BLOCK THE AIR DUCT WHEN THE UNIT IS SWITCHED ON.
DO NOT SIT ON THE UNIT AND AVOID PLACING FOREIGN OBJECTS ON IT.
UNPACK THE UNIT WITH CARE.
WHILE INSTALLING THE UNIT, FOLLOW THE SAFETY REGULATIONS SPECIFIC TO THE USE
OF ELECTRIC TOOLS.
DO NOT LAY THE POWER CABLE OF THE UNIT IN CLOSE PROXIMITY TO HEATING
EQUIPMENT.
DO NOT OPERATE THE UNIT OUTSIDE THE TEMPERATURE RANGE STATED IN THE USER’S
MANUAL.
DO NOT OPERATE THE UNIT IN AGGRESSIVE OR EXPLOSIVE ENVIRONMENTS.
DO NOT WASH THE UNIT WITH WATER.
PROTECT THE ELECTRIC PARTS OF THE UNIT AGAINST INGRESS OF WATER.
DISCONNECT THE UNIT FROM POWER MAINS PRIOR TO ANY TECHNICAL MAINTENANCE.
WHEN THE UNIT GENERATES UNUSUAL SOUNDS, ODOR, OR EMITS SMOKE, DISCONNECT IT
FROM POWER SUPPLY AND CONTACT THE SELLER.
DO NOT DIRECT THE AIR FLOW PRODUCED BY THE UNIT TOWARDS OPEN FLAME OR IGNITION
SOURCES.
IN CASE OF CONTINUOUS OPERATION OF THE UNIT, PERIODICALLY CHECK THE SECURITY
OF MOUNTING.
USE THIS UNIT ONLY IN THE MANNER INTENDED BY THE MANUFACTURER. IF YOU HAVE
QUESTIONS,CONTACT THE MANUFACTURER.
THE UNIT SHOULD NOT BE OPERATED BY CHILDREN OR PERSONS WITH REDUCED PHYSICAL,
MENTAL, OR SENSORY CAPACITIES, OR THOSE WITHOUT THE APPROPRIATE TRAINING.
THE CHOICE OF UNIT INSTALLATION LOCATION MUST PREVENT UNAUTHORIZED ACCESS BY
UNATTENDED CHILDREN.
READ THE USER’S MANUAL BEFORE INSTALLING THE UNIT.
INSTALLATION WORK AND ELECTRICAL WIRING MUST BE DONE BY QUALIFIED PERSON(S).
WHEN CUTTING OR DRILLING INTO WALL OR CEILING, DO NOT DAMAGE ELECTRICAL WIRING
AND OTHER HIDDEN UTILITIES.
DO NOT MOUNT ROOM-TO-ROOM FAN IN A FIRE-RATED WALL.
POWER OFF THE POWER SUPPLY PRIOR TO ANY OPERATIONS WITH THE UNIT.
THE UNIT MUST BE CONNECTED TO POWER SUPPLY BY A QUALIFIED ELECTRICIAN.
THE RATED ELECTRICAL PARAMETERS OF THE UNIT ARE GIVEN ON THE MANUFACTURER’S
LABEL.
ANY TAMPERING WITH THE INTERNAL CONNECTIONS IS PROHIBITED AND WILL VOID THE
WARRANTY.
INSTALLATION ONLY BY EXPERTS AND ONLY IN ACCORDANCE WITH LOCAL REQUIREMENTS
AND NATIONAL ELECTRICAL CODE.
DISCONNECT THE UNIT FROM POWER SUPPLY BEFORE ANY MAINTENANCE OPERATIONS!
ENSURE THAT THE UNIT IS SWITCHED OFF FROM THE SUPPLY MAINS BEFORE REMOVING THE
GUARD.
FOLLOWING THE REGULATIONS STIPULATED HEREIN WILL ENSURE A LONG AND TROUBLE-
FREE OPERATION OF THE UNIT.
USER’S WARRANTY CLAIMS SHALL BE SUBJECT TO REVIEW ONLY UPON PRESENTATION OF
THE UNIT, THE PAYMENT DOCUMENT AND THE USER’S MANUAL WITH THE PURCHASE DATE
STAMP.
TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS, OBSERVE THE
FOLLOWING:
USE THIS UNIT ONLY IN THE MANNER INTENDED BY THE MANUFACTURER. IF YOU HAVE
QUESTIONS, CONTACT THE MANUFACTURER.
BEFORE SERVICING OR CLEANING THE UNIT, SWITCH POWER OFF AT THE SERVICE PANEL
AND LOCK THE SERVICE DISCONNECTING MEANS TO PREVENT POWER FROM BEING SWITCHED
ON ACCIDENTALLY. WHEN THE SERVICE DISCONNECTING MEANS CANNOT BE LOCKED,
SECURELY FASTEN A PROMINENT WARNING DEVICE, SUCH AS A TAG, TO THE SERVICE
PANEL.
FOR GENERAL VENTILATING USE ONLY. DO NOT USE TO EXHAUST HAZARDOUS OR EXPLOSIVE
MATERIALS AND VAPORS.
**** THE PRODUCT MUST BE DISPOSED SEPARATELY AT THE END OF ITS SERVICE LIFE.
DO NOT DISPOSE THE UNIT AS UNSORTED DOMESTIC WASTE
PURPOSE
CAUTION!
FOR GENERAL VENTILATING USE ONLY.
DO NOT USE TO EXHAUST HAZARDOUS OR EXPLOSIVE MATERIALS AND VAPORS AS WELL AS
FLAMMABLE MIXTURES, EVAPORATION OF CHEMICALS, STICKY SUBSTANCES, FIBROUS
MATERIALS, COARSE DUST, SOOT AND OIL PARTICLES OR ENVIRONMENTS FAVOURABLE FOR
THE FORMATION OF HAZARDOUS SUBSTANCES (TOXIC SUBSTANCES, DUST, PATHOGENIC
GERMS).
FOR USE IN NON FIRE RATED INSTALLATIONS ONLY.
FOR USE IN ONE- AND TWO-FAMILY DWELLINGS ONLY.
The air handling unit with heat recovery is designed for integration into
central mechanical ventilation systems.
The unit is rated for continuous operation.
Transported air must not contain any flammable or explosive mixtures,
evaporation of chemicals, sticky substances, fibrous materials, coarse dust,
soot and oil particles or environments favourable for the formation of
hazardous substances (toxic substances, dust, pathogenic germs).
DELIVERY SET
Name | Number |
---|---|
Unit | 1 pc. |
User’s manual | 1 pc. |
Technical data sheet | 1 pc. |
Automation wiring | 1 pc. |
Control panel | 1 pc. |
User’s manual for automation | 1 pc. |
Packing box | 1 pc. |
DESIGNATION KEY
TM| Casing size| Core type| Installation| Nominal
airflow| Heater type| Heat exchanger type|
Cooling coil type| Service side| Controller
---|---|---|---|---|---|---|---|---|---
Airvents| AV01
AV02
AV03
AV07
AV12| CF-counter flow
R – rotary
| P – ceiling
H – double-deck
V – vertical
T – rooftop| 1000
1200
1500
2500
3500
5000
6000
9000| HE – electric
HW – water
– no heater| E – enthalpy heat exchanger
– sensible heat exchanger| CDX – DX-coil
CW – water coil
_ – no cooling| L – left
R – right| A30 – Kvent with thTune
A31 – Kvent
A32 – Kvent with pGDE
TECHNICAL DATA
The unit is designed for indoor or sheltered use. The installation conditions
must prevent ingress of atmospheric precipitations and direct solar radiation
at the ambient temperatures from -31 °F up to +122 °F. The frost protection
for the water drainage and connected pipelines must be provided during sub-
zero ambient temperatures (if the unit is equipped with an air cooler). The
heat medium temperature in the water heat exchangers (if available) must be
sufficient to prevent its freezing.
Hazardous parts access and water ingress protection rating:
- IP54 for the unit motors
- IP40 for the assembled unit connected to the air ducts without extra cover or weather hoods
- IP44 for the assembled unit with connected air ducts, extra cover and weather hoods (specially ordered accessories)
- IP00 for the unit not connected to the air ducts
The unit design is constantly being improved, thus some models may be slightly
different from those described in this manual.
UNIT OVERALL DIMENSIONS
Model| A| A1| A2| B| B1| B2| C1|
C2| C3| C4| C5| C6| C7| C8| D| D1
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---
AV01 RV 800-R(L)
AV01 RV 1200-R(L)| 55.2| 785| —| 44.9| —| —| 6.50| 4.06| 2.48| 4.88| 2.44|
6.69| 4.49| 3.54| —| 9.84
AV01 RV 800-HE-R(L)
AV01 RV 1200-HE-R(L)
AV01 RV 800-HW-R(L)
AV01 RV 1200-HW-R(L)| 3/4’
AV02 RV 1500
AV02 RV 2500| 65.8| 38.8| 19.7| 55.1| 51.3| 9.84| —| —| —
AV02 RV 1500-HE AV02 RV 2500-НЕ
AV02 RV 1500-HW AV02 RV 2500-HW| 3/4’
AV03 RV 3500| 86.3| 50.6| 23.6| 63.0| 59.2| 11.8| —
AV03 RV 3500-HE
AV03 RV 3500-HW| 3/4’
AV07 RV 5000
AV07 RV 6000| 92.9| 55.7| 39.4| 75.2| 71.0| 13.8| —
AV07 RV 5000-HE AV07 RV 6000-HE
AV07 RV 5000-HW AV07 RV 6000-HW| 1’
The full technical data list is stated in the supplied technical data sheet.
UNIT DESIGN
- protective dampers with electric actuator
- extract fan
- rotary heat exchanger
- supply filter
- control unit
- extract filter
- electric heater (only for the models with electric heater)
- supply fan
- water heater (only for the units with water heater)
INSTALLATION AND SET-UP
The units are available in left- and right-sided modifications with the right or left service side. All the assembly units are accessible on the service side
During installation works sufficient maintenance and service access must be provided. The recommended minimum distances from the unit to the walls are shown below.
Casing dimensions | A, mm |
---|---|
AV01 RV | 31 ½ |
AV02 RV
AV03 RV| 35 7/16
AV07 RV| 39 ⅜
The unit must be mounted to an even installation surface, with a loading capacity matching the unit weight, in compliance with safety requirements. The delivery set includes removable levelling feet to adjust horizontal levelling of the unit.
Connection of the water heater (only for the models with water heater.
The connecting spigots for the water heater are located on the side opposite
to the service side.
While connecting the water heater keep the straight air duct section length
not less than 15 3/4 from the unit. Otherwise the maintenance panel cannot be
opened!
CONNECTION TO POWER MAINS
Connection to power mains must be conducted in compliance with the automation
user’s manual.
TECHNICAL MAINTENANCE
WARNING – TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO
PERSONS, OBSERVE THE FOLLOWING:
BEFORE REMOVING THE FILTERS, SWITCH OFF THE EXTERNAL AUTOMATIC CIRCUIT BREAKER
AND LOCK THE SERVICE DISCONNECTING MEANS, THEN OPEN THE HINGED SERVICE PANEL
AND REMOVE THE FILTERS CAREFULLY.
IT IS POSSIBLE TO CLEAN FILTERS WITH A VACUUM CLEANER OR RINSE THEM WITH WATER
AND DRY. MAKE SURE FILTERS ARE COMPLETELY DRY BEFORE THEY HAVE BEEN INSTALLED
BACK INTO THE UNIT.
OPEN THE UNIT FOR INSPECTION AND SERVICE NOT LESS THAN 2 MINUTES AFTER
COMPLETE DE-ENERGIZING OF THE UNIT. THE FANS ROTATION MAY BE STILL PRESENT.
IN CASE OF ANY ABNORMAL NOISE, SMELL AND COMPONENT DEFORMATION IMMEDIATELY CUT
OFF POWER SUPPLY TO THE UNIT AND CONTACT
A SERVICE PROVIDER OR THE UNIT SELLER.
The unit operation requires regular inspection, dry cleaning of inner
components, check-up and replacement of air filters in case of filter
contamination.
3-6 months after commissioning of the unit it must be inspected by a service
expert for planned preventive maintenance of the unit. Next maintenance
operations must be conducted at least every 6-12 months. Maintenance
periodicity is determined by a service expert depending on operation
conditions of the unit. Dust deposits on the inner parts of the unit,
especially in the electric heater, may lead to unpleasant odours.
It is not a malfunction. Clean the unit to troubleshoot unpleasant odours.
Filters
Open the service doors to access the filters and pull the filters from the
unit.
Remove the service panel to access the heat exchanger. Disconnect the socket from the actuator. Remove the heat exchanger.
STORAGE AND TRANSPORTATION REGULATIONS
- Store the unit in the manufacturer’s original packaging box in a dry closed ventilated premise with temperature range +41 ˚F…+104 ˚F and relative humidity up to 70 %.
- Storage environment must not contain aggressive vapors and chemical mixtures provoking corrosion, insulation, and sealing deformation.
- Use suitable hoist machinery for handling and storage operations to prevent possible damage to the unit.
- Follow the handling requirements applicable for the particular type of cargo.
- The unit can be carried in the original packaging by any mode of transport provided proper protection against precipitation and mechanical damage. The unit must be transported only in the working position.
- Avoid sharp blows, scratches, or rough handling during loading and unloading.
- Prior to the initial power-up after transportation at low temperatures, allow the unit to warm up at operating temperature for at least 3-4 hours.
MANUFACTURER’S WARRANTY
Production meets standard operating requirements in the USA and Canada.
Vents US warrants to the original purchaser of the unit that it will be free
from defects in materials or workmanship for a period of 24 months from the
date of original purchase. The Vents US warrants to the original purchaser of
the unit that the integrated control unit will be free from defects in
materials and workmanship for a period of 24 months from the date of original
purchase.
THERE ARE NO OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING, BUT NOT
LIMITED TO,
IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE.
During the stated warranty period, Vents US will, at its option, repair or
replace, without charge, any product or part which is found to be defective
under normal use and service. This warranty does not cover (a) normal
maintenance and normal service or (b) any products or parts which have been
subject to misuse, negligence, accident, improper maintenance or repair (other
than by Vents US), faulty installation or installation contrary to recommended
installation instructions. Labor to remove and replace products is not
covered. The duration of any implied warranty is limited to the time period
specified for the express warranty. Some states do not allow limitations on
how long an implied warranty lasts, so the above limitation may not apply to
you.
VENTS US OBLIGATION TO REPAIR OR REPLACE, AT VENTS US OPTION, SHALL BE THE
PURCHASER’S SOLE AND EXCLUSIVE REMEDY UNDER THIS WARRANTY. VENTS US SHALL NOT
BE LIABLE FOR INCIDENTAL, CONSEQUENTIAL OR SPECIAL DAMAGES ARISING OUT OF OR
IN CONNECTION WITH PRODUCT USE OR PERFORMANCE.
Some states do not allow the exclusion or limitations of incidental or
consequential damages, so the above limitation or exclusion may not apply to
you. This warranty gives you specific legal rights, and you may also have
other rights which vary from state to state. This warranty supersedes all
prior warranties. If proof of sales date is absent, warranty period is
calculated from the production date. The unit can be exchanged at the
following address:
Vents-US
400 Murray Road, Cincinnati, OH 45217, USA
Tel: 1-888-640-0925,
513-583-5786, Fax:
513-268-4597
E-mail: support@ventsus.com
www.vents-us.com
Please follow guidelines in this manual for product problem-free operation.
FOLLOWING THE REGULATIONS STIPULATED HEREIN WILL ENSURE A LONG AND TROUBLE-
FREE OPERATION OF THE UNIT.
USER’S WARRANTY CLAIMS SHALL BE SUBJECT TO REVIEW ONLY UPON PRESENTATION OF
THE UNIT, THE PAYMENT DOCUMENT AND THE USER’S MANUAL WITH THE PURCHASE DATE
STAMP.
CERTIFICATE OF ACCEPTANCE
Unit Type | Air handling unit |
---|---|
Model | |
Serial Number | |
Manufacture Date | |
Quality Inspector’s Stamp |
SELLER INFORMATION
Seller|
---|---
Address|
Phone Number|
E-mail|
Purchase Date|
This is to certify acceptance of the complete unit delivery with the user’s
manual. The warranty terms are acknowledged and accepted.
Customer’s Signature|
Seller’s Stamp
INSTALLATION CERTIFICATE
The __ unit is installed pursuant to the requirements stated in the present user’s manual.
Company name|
Address|
Phone Number|
Installation Technician’s Full Name|
Installation Date:| Signature:
The unit has been installed in accordance with the provisions of all the
applicable local and national construction, electrical and technical codes and
standards. The unit operates normally as intended by the manufacturer.
Signature:|
Installation Stamp
WARRANTY CARD
Unit Type | Air handling unit |
---|---|
Model | |
Serial Number | |
Manufacture Date | |
Purchase Date | |
Warranty Period | |
Seller |
Seller’s Stamp
www.vents-us.com
VUSA192-4EN-02
Documents / Resources
|
VENTS-US Airvents RV Air Handling
Unit
[pdf] Owner's Manual
Airvents RV Air Handling Unit, Airvents RV, Air Handling Unit, Handling Unit
---|---
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>