Dwyer Series 616W Differential Pressure Transmitter Instruction Manual
- June 9, 2024
- Dwyer
Table of Contents
- Series 616W Differential Pressure Transmitter
- Product Information: Series 616W Differential Pressure Transmitter
- Product Usage Instructions
- MODEL CHART
- SPECIFICATIONS
- INSTALLATION
- ELECTRICAL CONNECTIONS
- LCD DISPLAY
- MAINTENANCE/REPAIR
- WARRANTY/RETURN
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Series 616W Differential Pressure Transmitter
Product Information: Series 616W Differential Pressure Transmitter
The Series 616W Differential Pressure Transmitter is a device used to measure differential pressure in air and non-combustible,compatible gases. It comes in various models with different ranges and digital displays. The transmitter has a vertical position with the pressure connection pointing downwards, which is the position in which all standard models are spanned and zeroed at the factory. It has two integral barbed tubing connections that fit both 1/8 and 3/16 (3.12 and 4.76 mm) I.D. tubing. The transmitter utilizes a 2-wire 4-20 mA Current Output, or a 3-wire 0-5 V / 0-10 V Voltage Output. It is also capable of Simultaneous Current and Voltage Output.
Product Usage Instructions
- Location: Choose a clean, dry mounting location free from excess vibration.
- Position: Use a vertical position with the pressure connection pointing downwards. The transmitter can be used at other angles, but final zeroing and spanning must be done while in that alternate position.
- Pressure Connections: The transmitter has two integral barbed tubing connections that fit both 1/8 and 3/16 (3.12 and 4.76 mm) I.D. tubing. Be sure the pressure rating of the tubing exceeds that of the operating range. On ranges over 20 psi, use a suitable hose clamp to assure the integrity of the connection.
- Electrical Connections: The transmitter utilizes a 2-wire 4-20 mA Current Output, or a 3-wire 0-5 V / 0-10 V Voltage Output. It is also capable of Simultaneous Current and Voltage Output. Use a removable European-style four conductor terminal block, or optionally, the included tooless terminal block to connect the power and signals. If equipped, remove the LCD before wiring by pulling it out.
- Power Supply: Do not exceed specified supply voltage ratings as permanent damage not covered by warranty will result. The selection of using a DC or AC power supply is made via the terminal block.
The Series 616W Differential Pressure Transmitter senses the pressure of air and non-combustible, compatible gases and sends a standard 4-20 mA or selectable 0 to 5/0 to 10 VDC output signal. All models, including those featuring an LCD, are factory calibrated to specific ranges. Positive, negative, and differential pressures can be measured within a full-scale accuracy of ±0.25%. This weatherproof unit is enclosed in a polycarbonate case, rated NEMA 4X (IP66). The span and zero controls are for use when checking calibration, and are not intended for re-ranging.
MODEL CHART
SPECIFICATIONS
- Service: Air and non-combustible, compatible gases.
- Wetted Materials: Consult factory.
- Accuracy: 0.25% FS @ 77°F (25°C), display accuracy ±0.5%.
- Thermal Effect: ±0.02% FS/°F (±0.036% FS/°C).
- Stability: ±1% FS/yr.
- Temperature Limits: -4 to 158°F (-20 to 70°C).
- Pressure Limits: See chart.
- Power Requirements: 10-36 VDC (2-wire), 17-36 VDC, or isolated 21.6-33 VAC (3-wire).
- Output Signal: 4-20 mA (2-wire), 0-5 VDC, or 0-10 VDC (3-wire).
- Zero and Span Adjustments: Digital push-button.
- Response Time: Instantaneous (default) or 3 s (selectable).
- Loop Resistance: Current output: 0-1250 Ω max.; Voltage output: Min. load resistance 1 kΩ.
- Current Consumption: 21 mA max. continuous.
- Electrical Connections: 4-wire removable European style terminal block for 16 to 26 AWG.
- Process Connections: Barbed, dual size to fit 1/8˝ and 3/16˝ (3.12 and 4.76 mm) I.D. rubber or vinyl tubing.
- Enclosure Rating: NEMA 4X (IP66).
- Mounting Orientation: Any orientation.
- Weight: Without LCD: 8.9 oz (253 g); With LCD: 9.5 oz (269 g).
- Compliance: CE.
INSTALLATION
- Location: Select a clean, dry mounting location free from excess vibration where the temperature will remain between -4 to 158°F (-20 to 70°C). Distance from the receiver is limited only by total loop resistance. See Electrical Connections below. The tubing supplying pressure to the instrument can be practically any length required, but long lengths will increase response time slightly.
- Position: A vertical position, with the pressure connection pointing down, is recommended. That is the position in which all standard models are spanned and zeroed at the factory. They can be used at other angles, but final spanning and zeroing must be done while the transmitter is in that alternate position.
- Pressure Connections: Two integral barbed tubing connections are provided. They are dual-sized to fit both 1/8˝ and 3/16˝ (3.12 and 4.76 mm) I.D. tubing. Be sure the pressure rating of the tubing exceeds that of the operating range. On ranges over 20 psi, we recommend use of a suitable hose clamp to assure the integrity of the connection.
ELECTRICAL CONNECTIONS
The 616W transmitter utilizes a 2-wire 4-20 mA Current Output, or a 3-wire 0-5 V / 0-10 V Voltage Output. It is also capable of Simultaneous Current and Voltage Output. The power and signals interconnect via a removable European- style four conductor terminal block, or optionally, via the included tooless terminal block.
NOTICE If equipped, the LCD must be removed before wiring. Pull the LCD directly away from the product to remove. Reinstall the LCD after wiring is completed.
2-Wire 4-20 mA Current Output
DO NOT EXCEED SPECIFIED SUPPLY VOLTAGE RATINGS. PERMANENT DAMAGE NOT COVERED
BY WARRANTY WILL RESULT. SIMULTANEOUS OUTPUTS ARE NOT DESIGNED FOR AC VOLTAGE
OPERATION.
The connections to the transmitter are made through terminals VDC and COM on the terminal block as shown in Figure 1. The terminal block is removable and each of the terminals are labeled next to the terminal block on the circuit board. Polarity is indicated by VDC and COM. See Figure 1.
The maximum receiver load resistance (RL) for a given power supply voltage (Vps) is defined by the formula:
Shielded 2-wire cable is recommended for control loop wiring. Ground the shield at the power supply end only. The receiver may be connected to either the negative or positive side of the loop, whichever is most convenient. Should polarity of the transmitter or receiver be inadvertently reversed, the loop will not function properly but no damage will be done to the transmitter. The maximum length of connecting wire between the transmitter and the receiver is a function of wire size and receiver resistance. That portion of the total current loop resistance represented by the resistance of the connecting wires themselves should not exceed 10% of the receiver resistance. For extremely long runs (over 1,000 feet), it is desirable to select receivers with lower resistances in order to keep the size and cost of the connecting leads as low as possible. In installations where the connecting run is no more than 100 feet, you can use a connecting lead wire as small as No. 22 ga.
3-Wire 0-10 V and 0-5 V Voltage Output
DO NOT EXCEED SPECIFIED SUPPLY VOLTAGE RATINGS. PERMANENT DAMAGE NOT COVERED
BY WARRANTY WILL
RESULT.
The terminal block is removable and each of the terminals are labeled next to
the terminal block on the circuit board. Positive polarity is indicated by
VOUT. AC/DC selection is made via the terminal block. If the polarity of the
transmitter is inadvertently reversed, the unit will not function properly,
but no damage will be done to the transmitter.
Selection of using a DC or AC power supply is made via the terminal block.
See Figure 2 for DC Wiring.
See Figure 3 for AC Wiring.
The minimum receiver load is 1 kΩ. The resistance due to the wire should be low compared to the receiver load resistance. While the voltage at the terminal block remains unchanged with a 10 mA current flow, resistive losses in the wiring do cause errors in the voltage delivered to the receiver. For a 1% accurate gage, the resistance of the wires should be less than 0.1% of the value of the receiver load resistance. This will keep the error caused by the current flow below 0.1%. The output across VOUT and COM will be either 0-5 V, 0-10 V depending on the DIP switch setting. See DIP Switch Settings Section for more information.
3-Wire 0 to 10 V and 0 to 5 V Voltage Operation Simultaneous Current and Voltage Output
CAUTION DO NOT EXCEED SPECIFIED SUPPLY VOLTAGE RATINGS. PERMANENT DAMAGE NOT COVERED BY WARRANTY WILL RESULT. SIMULTANEOUS OUTPUTS ARE NOT DESIGNED FOR AC VOLTAGE OPERATION.
The terminal block is removable and each of the terminals is labeled underneath the terminal block on the circuit board. Positive polarity is indicated by VOUT. The VDC terminal and a DC power supply must be used for Simultaneous Current and Voltage Output. The voltage output and the power supply must have separate wire leads that are only joined at terminal 2 of the transmitter. Additional error may occur for the voltage output if a single wire is used or if the wires are joined at the power supply or receiver. For the current output, the maximum allowable loop resistance (wiring + receiver resistance) is dependent on the power supply. The maximum loop voltage drop must not reduce the transmitter voltage below 17 V. The maximum loop resistance (RMAX) for a given power supply voltage (VPS) can be calculated using the following equation:
The equation uses 17.0 instead of 10.0 as seen in the equation earlier with Figure 1. This represents the minimum voltage supply which is higher on the simultaneous output configuration due to the requirements of the voltage outputs. A shielded 4-wire cable is recommended for control loop wiring. Ground the shield at the power supply end only. Should the polarity of the transmitter or receiver be inadvertently reversed, the unit will not function properly, but no damage will be done to the transmitter. For voltage outputs, the minimum receiver load is 1 kΩ. The resistance due to the wire should be low compared to the receiver load resistance. While the voltage at the terminal block remains unchanged with a 10 mA current flow, resistive losses in the wiring do cause errors in the voltage delivered to the receiver. For a 1% accurate gage, the resistance of the wires should be less than 0.1% of the value of the receiver load resistance. This will keep the error caused by the current flow below 0.1%. The output across VOUT and COM will be either 0-5 V or 0-10 V depending on the DIP switch setting. See DIP Switch Settings Section for more information.
Power Supply
Refer to the following tables for the required supply rating.
DIP SWITCH SETTINGS
DIP switch settings are marked directly on the PCBA as shown in Figure 5.
Switches are factory-set, based on the order configuration. You can also use a
small screwdriver or pen to change the position of the switches.
NOTICE
Figure 5 is a depiction of a 5 in w.c. pressure board. Other pressure boards,
while similar, will vary from the below.
WARNING There are no hazardous voltages if supplied power is within the specified range. However, it is a good idea to shut control systems down while changing DIP switches to prevent erratic control system behavior.
Key To DIP Switch Settings
DIP Switch 4 – Voltage Output Range
Voltage output range can be either 0-10 V or 0-5 V depending on the position
of DIP Switch 4.
- • When the switch is in the OFF or down position, the output will be 0-10 V
• When the switch is in the ON or up position, the output will be 0-5 V.
DIP Switch 6 – Response Time Selection
DIP Switch 6 toggles to select the desired response time.
- • When the switch is in the OFF or down direction, the transmitter response time will be instantaneous.
• When the switch is in the ON or up direction, the response time will be 3 seconds.
NOTICE
The remaining DIP switches are disabled.
CALIBRATION
There is a 3 second delay from the time the zero or span calibration buttons
are released until the time that the change in calibration takes place. This
delay is used to prevent stress related offsets on the lower ranges.
Zero Calibration
The zero calibration can be set by applying zero pressure to both of the
pressure ports and pressing the zero button for 3 seconds. If the LCD display
is present, the display will read ZERO and then sequence back to the home
display.
Span Calibration
NOTICE
For a positive span, apply pressure to the positive “+” port.
The span calibration function allows the pressure value to be adjusted so that the currently applied pressure is the maximum configured pressure. This will in turn set the maximum analog output at the set pressure. It is recommended that the ZERO function be applied before performing a span. Apply the maximum desired pressure to the device, press and hold span for 3 seconds. If the LCD display is present, SPAN is displayed. The span function will be processed 3 seconds after the span button is released.
LCD DISPLAY
The LCD comes with a housing cover, which contains a window. The display plugs into the pins on top of the circuit board. The LCD is 180° rotatable so that it will read properly if the device must be mounted with the connections facing up. The following error messages will appear if an LCD is present and the device is an error state.
MAINTENANCE/REPAIR
Upon final installation of the Series 616W Differential Pressure Transmitter, no routine maintenance is required. The Series 616W is not field serviceable and is not possible to repair the unit. Field repair should not be attempted and may void warranty.
This symbol indicates waste electrical products should not be disposed of with household waste. Please recycle where facilities exist. Check with your Local Authority or retailer for recycling advice.
WARRANTY/RETURN
Refer to “Terms and Conditions of Sale” in our catalog and on our website. Contact customer service to receive a Return Goods Authorization number before shipping the product back for repair. Be sure to include a brief description of the problem plus any additional application notes.
©Copyright 2022 Dwyer Instruments, Inc.
DWYER INSTRUMENTS, INC.
P.O. BOX 373
MICHIGAN CITY,
INDIANA 46360,
U.S.A.
Printed in U.S.A. 8/22
Phone: 219/879-8000
Fax: 219/872-9057
www.dwyer-inst.com
e-mail: info@dwyermail.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>