HC201 Series Air Conditioners
User Manual User & Technical Manual
HC201 Series
Rev 1.0
CAUTION
Read Manual Before Installation.
For Questions, Please Call Thermal Edge Inc. at (888)-580-0202
To Be Professionally Installed Only
Title: HC201 Air Conditioner Technical Manual
Department: Engineering
Objective: To provide important information for maintenance, diagnostics
and advance operations of the Thermal Edge HC201 Series Air Conditioners.
Revision History:
Rev | Date | Owner | Description of Changes |
---|---|---|---|
1.0 | 10-06-11 | G. Gonzalez | Initial Release |
Statement of Confidentiality
The Manual and other materials contain proprietary information, comprising
Thermal Edge Inc.’s trade secrets. Please maintain the confidentiality of all
proprietary information during and after the term of the use agreement. Also,
please refrain from using this proprietary information in any other manner,
including in any other business, without Thermal Edge Inc.’s written approval.
Thermal Edge Inc. reserves the right to revise and otherwise modify the Manual
to reflect changes in the requirements, standards, and operating
recommendations. The Manual is the sole property of Thermal Edge Inc. It must
be returned upon the expiration or the termination of the term of use
agreement.
By accepting the Manual you have read and understand the Statement of
Confidentiality and will abide by its terms and conditions.
Overview
Thank you for your purchase of the Thermal Edge Special Purpose Air
Conditioner. Our air conditioning equipment is carefully designed to cool and
dehumidify the air in electronic component enclosures. Thermal Edge has
designed air conditioners for all types of electronic equipment enclosures
providing capacity from 1,000 to 24,000 BTUH.
This manual will guide you through the installation, maintenance, diagnostics
and advance operations of the HC201 Series Air Conditioners. This manual
contains important information for the end-user who installs, maintains and/or
operates the HC201 Air Conditioner.
Technical Support
By Phone: 972-580-0200 /
888-580-0202
(Monday – Friday, 7:30 am – 5:00 pm Central Time)
By Email: support@thermal-edge.com
Our goal is to have continuous improvement for both our equipment and our
documentation. We rely and appreciate your feedback to help us achieve our
goal. Our technical support team is glad to work with you if you require
additional technical information not provided in this manual.
Inspecting the Equipment
Thermal Edge air conditioning equipment is designed, manufactured and packed
to prevent damage from normal handling, shock and vibration during shipment.
It is necessary to inspect your equipment upon receipt to insure that there
is no visual or hidden damage.
Upon receipt of the equipment, insure that it is always top side up as
indicated by “THIS SIDE UP” labels. This insures that the compressor oil is
not displaced.
Note: If the equipment has been on its side it must be put upright for at
least 24 hours before installing or running to insure the compressor oil has
returned to the compressor.
All physical damage to packing or signs of damage to the equipment must be
noted on the freight bill of lading. Packages must be opened after receipt and
inspected for any internal or concealed damage to the equipment and to verify
proper count and order fulfillment. Delivery of without the pallet, not top
side up, other freight on top, damaged or wet should be refused.
Unpacking the Air Conditioner
Always keep air conditioner top up as shown by the packaging label and arrows.
If the unit is to be transported after initial unpacking, place air
conditioner back in original packing to prevent damage.
For shipment by UPS or freight carrier, repack as received and re-band to the
pallet.
Note: Shipping without being strapped to the pallet may result in tipping
and damage, this will void the warranty.
Moving the Air Conditioners
Read this section completely before running or installing your Thermal Edge
air conditioning equipment.
Note: You will need to perform a Preliminary Test before mounting the air
conditioner. Refer to the Preliminary Test section in this manual for
instructions on how to run this test. You will also need to prepare the
enclosure that is to be cooled for mounting in accordance with this manual and
the template supplied.
Note: Thermal Edge air conditioning equipment must be mounted vertically
with a minimum of 3” air space for condenser air return and supply. If
necessary, equipment may be mounted at up to a 5 degree angle (rotary
compressors) without damaging the compressor.
If air conditioner is to be shipped or transported at any time; pack in
original packaging and strap to pallet to prevent damage. Air conditioner must
be kept upright at all times. Air conditioners are not designed to be shipped
attached to an equipment enclosure. Air conditioners shipped which have
internal damage due to shipping while attached to enclosures are warranty
voided.
Unit Label
Each air conditioner has a unit label, be sure to record the data from the label to the template below and keep this information in a safe place for warranty and ordering parts. To prevent damage to equipment, electrical panel and wiring, and to prevent personal injury, assure that the power source is compatible with the equipment before operating. When recharging, refrigeration type and amount must be the same as shown on the unit label or air conditioner will not operate properly or may be damaged and may result in the warranty voided and UL listing voided.
Operation
Thermal Edge air conditioners will lower (or increase as necessary) the
temperature inside an enclosure to ensure its proper operational temperature.
Our air conditioners, when sized properly, will provide cooling or heating
automatically controlled by the temperature digital controller.
Thermal Edge air conditioners operate as a “closed loop” system with no
exposure or introduction of outside air. This insures that the enclosure is
separated from and is not contaminated with ambient air, dirt, chemicals,
dust, moisture or foreign matter so that sensitive enclosure components are
protected and are kept at your required operational temperature.
An air conditioner is designed to dehumidify and extract heat from an area, or
provide heat to an area. The cooling is done using a simple refrigeration
cycle. A product of this simple refrigeration cycle is excess humidity that
condenses to a liquid.
Thermal Edge air conditioners are designed using an advanced refrigeration
cycle and are equipped with a Condensate Removal System that changes the
excess humidity liquid into a vapor which is then vented to the atmosphere. In
the event of excess water vapor where the enclosure door has been left open
there is an overflow hole on the bottom of every unit. Please contact Thermal
Edge Inc. if you encounter excess water coming from your air conditioner.
Preliminary Testing
Before mounting the air conditioner to the enclosure, test for proper
operation. Follow the steps below prior to installation.
WARNINGS
The air conditioner must sit upright for 24 hours to assure the compressor oil
has drained down to the compressor. Check the unit label to assure the
electric power available to the air conditioner is the proper voltage and
phase. Check the electric power source for proper ground wire and neutral wire
installation per 2011 NEC. Assure that the electric power is protected by a
circuit protection device; refer to the Unit Specification section in this
manual for proper circuit protection sizing.
- Plug the unit’s power cord into your source to start the evaporator fan and, if desired, change the set point. Refer to Digital Temperature Controller Programming section on this manual for details on changing the set point. Factory default settings should be satisfactory; however you may want to adjust heat, cooling and alarm set points for your specific application.
- The condenser fan is controlled by the refrigerant high heat pressure and will turn on later when the operating pressure builds up. This feature allows low ambient operation and reduces current inrush at initial power on.
- Run the air conditioner for 15 minutes; during this time the condenser fan will turn on after the condenser coil warms up. Note: Ambient Temperature must be at least 75°F.
- Turn the unit off if the equipment makes any unexpected or hard mechanical noises or vibrations and refer to the troubleshooting guide in this manual.
- The supply cold air should be at least 10°F colder than the return air entering the unit. If it is not, refer to the troubleshooting guide in this manual;
- When you are satisfied that the unit is operating properly, turn unit off, disconnect the power and mount the unit on the enclosure in accordance with the Mounting the Air Conditioner section in this manual.
Mounting the Air Conditioner
Using the template supplied, determine where the air conditioner is to be
mounted and assure that all required cuts and holes will not interfere with or
damage the enclosure or its contents. Assure that there is a 3” clearance
between walls / obstructions and the air conditioner for the condenser supply
air and return air flow so that it is not restricted. Restricted condenser air
flow will affect the air conditioner’s performance. Mount the air conditioner
high on the enclosure in order to cool the hot air in the top of the
enclosure. Position the unit where the cold air can circulate across the width
of the enclosure to cool it all the way across.
Once proper mounting placement is determined, turn the enclosure equipment
off, if possible, to prevent damage. Drill and cut the holes as indicated on
the mounting template. Install insulation gasket as required to insure an air
tight closed loop seal. Be cautious not to let any cutting debris fall into
the enclosure. Attach the hanging bolts as indicated on the template to hold
the unit onto the enclosure and then use the mounting screws that are
provided.
Hang the air conditioner on the hanging bolts and from inside the enclosure
use the fasteners supplied to attach the air conditioner to the enclosure.
Insure that these fasteners are tight in order to prevent the unit from
falling off the enclosure. These fasteners should be checked periodically to
insure that they have not become loose due to vibration.
Ensure that the power supplied is compatible with the air conditioner’s power
requirements. Properly attach the unit’s power cord to a circuit that meets
the equipment requirements and provide a circuit protection device based on
the Unit Specifications section of this manual.
After mounting the air conditioner, replace/close the enclosure door and start
air conditioner; test for air leaks to assure a proper closed air loop seal
and run test the unit to assure proper operation after mounting. If any cold
air leaks are found, check for proper mounting and apply silicone-free Lexel
seal if leaks persist. Assure that the air conditioner’s condenser inlet air
filter is installed properly and cleaned regularly.
CAUTION
If mounting the air conditioner to the enclosure door, confirm with the
enclosure manufacturer that the door’s hinges will support the air
conditioner’s added weight (see equipment specifications). Insure that when
the door is fully open that the enclosure will not topple over due to the off-
center load.
Unit Specifications
The following table provides electrical and refrigeration specifications for
the HC201 Series Air Conditioners.
HC201 Series
Nominal Capacity Rating: 20,000 BTUH
Standard Maximum Ambient: 131°F
Model| Operating Voltage Range (Volts)| Inrush Current
(Start Up
Current)
(Amps)| Loading Current (Running Current)
(Amps)| SCCR
(ShortCircuit CurrentRating) (Amps)
| Recommended Circuit Protection
(Amps)| KVA Rating
(K- Watts)| Refrigerant Type| Refrigerant Amount
(ounces)| Low/High Unit Pressures (psi)| Noise Level
(dBA)| Weight
(Unit/Ship
(lbs)
---|---|---|---|---|---|---|---|---|---|---|---
HC201236| 207-253| 51.50| 13.7| 2| 25 Amp Class CC, CCMR TimeDelay| 3.1|
R407f| 42| 140 / 397| n/a| 205/226
HC201486| 440-480| 24.68| 6.56| 160K| 12 Amp Class CC, CCMR TimeDelay *| 3.1|
R407f| 42| 140 / 397| n/a| 320/342
- Time-delay Fuses with the following electrical characteristics are recommended. Fast-acting fuses are not recommended.
% of Ampere Rating | Opening Time |
---|---|
110 % | 15min Minimum |
125 % | 1hr Maximum |
200 % | 12sec Minimum |
4min Maximum
*2 SCCR rating is based on the SCCR rating for the circuit protection device installed in the panel / enclosure per UL50 & UL508a to protect the AC unit. Typically 100KA – 200KA for Time-Delay Fuses.
THIS PAGE IS INTENTIONALLY LEFT BLANK
Options
The HC201 Series Air Conditioners may be ordered with the following
options. Review the list below for the specifications and functions of the
option(s) that apply to your unit.
Built-in Heater
This unit is configurable to include a Built-in Heater to increase the
temperature of your enclosure in lower temperature conditions. The digital
controller is programmed with an individual heater set point to maintain your
enclosure at your desired operating temperature.
Heater capacities are available in 500 Watt, 1000 Watt and 1500 Watt.
Default Settings:
- 55°F Heat Set Point
- 3°F Differential
At the default settings the heater turns on at 52°F and operates until
temperature has reached 55°F. Refer to Digital Temperature Controller
Programming section for details on changing these parameters.
Low Ambient
This option consists of circuitry to protect the compressor in a low ambient
temperature environment. The low ambient package is designed to provide an
optimum constant low current in the compressor motor during the non cooling
state. This option provides internal heat to the compressor to protect it from
stalls and hard starts during long periods of compressor off state.
Dry Contact
This option provides an early warning capability to your enclosure to aid in
the protection of your expensive equipment. The Dry Contact is programmed with
an individual dry contact set point to monitor the enclosure temperature limit
that you require. When the enclosure temperature has exceeded the maximum
limit, the Form C gold plated contact will activate to notify you that there
is a problem in achieving your cooling set point.
Default Settings:
- 105°F Dry Contact High Temperature Alarm Set Point
- 2°F Recovery Differential
- 3min Temperature Alarm Delay
At the default settings the Dry Contact initial conditions are normally open
and/or normally closed. When the unit is powered on and the temperature
exceeds 105°F for a period longer than 3 minutes the Dry Contact will
activate. At this time the normally open contact will close and the normally
closed contact will open. This state will remain until the temperature has
decreased to 103°F.
Note: The dry contact is not a power status indicator, rather a high
temperature alarm alerting you that the unit is unable to meet the cooling set
point.Refer to Advanced Digital Temperature Controller Programming
section on page 8 for details on changing these parameters.
Celsius Programming
Celsius Programming option allows the user to control the Thermal Edge Air
Conditioner in SI units. This feature can be programmed into the digital
temperature controller at time of manufacturing. This feature is also
available as an upgrade to air conditioners already in the field equipped with
Gen 2.0 controller via a flash drive key.
External Heat Output
This option allows you to add an external heater to be located anywhere in
your enclosure. These external heaters are ideal for focusing on individual
sections of the enclosure without having a large capacity Built-in Heater.
External Heater capacities available are 100 Watt, 150 Watt, 200 Watt, 250
Watt, 300 Watt, 400 Watt, 550 Watt, 650 Watt & 950 Watt
Default Settings:
- 55°F Heat Set Point
- 3°F Differential
At the default settings the heater output turns on at 52°F and operates until
the temperature has reached 55°F. Refer to Advanced Digital Temperature
Controller Programming section on this manual for details on changing these
parameters.
Special Programming
All Thermal Edge Air Conditioners have a Special Programming option for
selecting unique pre in programmed settings for special requirements. Although
most parameters are accessible in our digital controller, this option allows
you to receive a unit preset to your requirements without the need to manually
configure the unit. Refer to Advanced Digital Temperature Controller
Programming section for details on all default settings.
High Ambient
Most of our air conditioners have capabilities for high ambient application
upgrades from our Standard Maximum Ambient temperature of 131°F. With this
option we can optimize the Air Conditioner during manufacturing to achieve
improved performance at high ambient conditions.
Open Door Kill Switch
This option provides you with an adjustable and mountable safety switch for
your electronics enclosure. This switch will disable power to the air
conditioner when your electronics enclosure door is open allowing you to work
on your enclosure without the risk of unintentionally powering the unit.
Adjustable Temperature Probe
The adjustable temperature probe provides you with a 5’ temperature probe
that can be installed anywhere in your enclosure. This allows you to have the
flexibility to monitor and maintain the temperature at any specific location
of your enclosure.
Ethernet/IP Controller Output
This option provides the ability to communicate with the Thermal Edge Air
Conditioner controller via the Ethernet/IP protocol. You can monitor and
control all settings from a remote location with a PLC. Full specifications
will be provided with this option. For full details refer to the Ethernet/IP
Option Specifications included with the Air Conditioner.
Outdoor Option
When having our Programmable Digital Controller on the face of our Air
Conditioner does not fit your application, Thermal Edge offers the OD Package
(i.e. Outdoor Option). This option moves the controller into your enclosure
using a 10’ cable along with a universal, 16 gauge powder coated steel
mounting bracket. The Air Conditioner will have no openings on the face of the
unit. Below is partial schematic showing the OD option wiring connections to
the digital controller.
**System Faults
**
If any of the critical control parameters exceed limits, the compressor is
turned off and an alarm condition is indicated on the front panel.
There are three main conditions that can shut the AC compressor down:
- The condenser high temperature alarm
- The evaporator coil alarm
- The compressor thermal overload
In the event that the condenser coil overheats, a condenser high temperature
alarm, HA2, will flash on the display of the digital temperature controller
and the compressor will turn off after a 3 minute time delay.
In the case that the evaporator coil ices up or there is a leak, an evaporator
coil alarm, CA, will flash on the display of the digital temperature
controller and the compressor will turn off after a 2 minute time delay.
A thermal overload protects the compressor against faults. In the event that
the snowflake status LED is not flashing on the display and the compressor is
not running, an internal fault may have occurred on the unit. Refer to the
Troubleshooting Guide in this manual.
Digital Temperature Controller Programming
For the end user this section will provide all the necessary information to
view and change all functions and parameters available to you.
HOW TO SEE THE SETPOINT……..
- Press and immediately release the SET key. The display will show the setpoint value.
- Press and immediately release the SET key or wait for 15 seconds to display the enclosure temperature again.
HOW TO CHANGE THE SETPOINT……..
- Press the SET key for more than 2 seconds to change the setpoint value.
- The value of the setpoint will be displayed and the “F” LED starts blinking.
- To change the SET value, press the UP or DOWN arrow key within 15 seconds.
- To store the new setpoint value, press the SET key again or wait 15 seconds.
Note: The set value is stored even when the procedure is exited by waiting for the time-out to expire.
HOW TO ACCESS HIDDEN MENU 1……..
- Enter the Programming mode by pressing the SET + DOWN arrow keys simultaneously for 3 seconds. The “F” LED starts blinking.
- Select the required parameter by pressing the UP or DOWN arrow key. Press the SET key to display its value.
- Use the UP or DOWN arrow key to change its value.
- Press SET to store the new value and move to the following parameter.
To exit: Press SET + UP arrow keys or wait 15 seconds without pressing a key.
Note: The set value is stored even when the procedure is exited by waiting for the time-out to expire.
HOW TO ACCESS HIDDEN MENU 2……..
-
Enter the Programming mode by pressing the SET + DOWN arrow keys simultaneously for 3 seconds.
The “F” LED starts blinking. -
Release the keys, then push the SET + DOWN arrows keys simultaneously, again for more than 7 seconds.
The Pr2 label will be displayed immediately followed by the HY parameter. -
Select the required parameter by pressing the UP or DOWN arrow key. Press the SET key to display its value.
-
Use the UP or DOWN arrow key to change its value.
-
Press SET to store the new value and move to the following parameter.
To exit : Press SET + UP arrow keys or wait 15 seconds without pressing a key.
Note: The set value is stored even when the procedure is exited by waiting for the time-out to expire.
HOW TO LOCK THE KEYPAD……..
- Press and hold the UP and DOWN arrow keys simultaneously for more than 3 seconds.
- The POF message will be displayed and the keyboard will be locked. At this point, it will be possible only to see the setpoint or the MAX or MIN temperature stored.
- If a key is pressed for more than 3 seconds the POF message will be displayed.
HOW TO UNLOCK THE KEYPAD……..
- Press and hold the UP + DOWN arrow keys simultaneously for more than 3 seconds until the Pon message is displayed.
Functions and Parameters
Function| Operation| Parameter| Menu Location|
Factory Default| Operating Range| Unit
---|---|---|---|---|---|---
Cooling Setpoint| Set Desired Cooling Temperature| SET|
Main| 90| 70 – 95| °F
Cooling Differential| Control Hysteresis| Hy| Hidden Menu 1| 5|
1 – 45| °F
Compressor Protection| Anti short-cycle delay| AC| Hidden Menu
2| 5| 0 – 50| min
Probed Displayed| Select Display Probe
P1 – Enclosure Temperature
P2 – Condenser Temperature| Lod| Hidden Menu 2| P1| P1 / P2| N/A
Auxiliary Setpoint| Setpoint for Dry Contact *1/Heater| SAA| Hidden Menu
2| 105 / 55| -67 – 302| °F
Auxiliary Differential| Heater or Dry Contact Hysteresis *1| Shy| Hidden
Menu 2| 3| 1 – 45| °F
---|---|---|---|---|---|---
Maximum
Temperature Alarm| Alerts with “HA” when maximum
temperature has been exceeded| ALU| Hidden Menu 2| 105| 45 –
302| °F
Minimum Temperature
Alarm| Alerts with “LA” when minimum temperature has been exceeded|
ALL| Hidden Menu 2| 45| -67 – 105| **** °F
*1Note: When both Heater and Dry Contact options are included, these parameters only control Heater Settings. Dry Contact is controlled by ALU.
Alarms Signals
Message | Cause | Outputs |
---|---|---|
“P1” | Enclosure Probe Failure | Start and stop of the compressor after 15 |
minute intervals 2
“P2”| Condenser Probe Failure| No Output 2
“HA”| Maximum Temperature Alarm: P1 > 105°F for 3 minutes (after initial
30 min. start up delay)| No Output *2
“LA”| Minimum Temperature Alarm: P1 < 45°F for 3 minutes (after initial
30 min. start up delay)| No Output *2
“HA2”| Condenser High Temperature Alarm: P2 > 145°F for 3 minutes|
Compressor Off *2
“LA2”| Condenser Low Temperature Alarm: P2 < 50°F for 3 minutes|
No Output 2
“CA”| Evaporator Coil Alarm: Low Pressure for 2 minutes| Compressor Off 2
“noP”| Invalid Probe Selected: Low Evaporator Coil| No Output, Display
Only
ALARM RECOVERY……..
If the compressor is turned off due to an alarm, it will be able to restart
after the AC anti short-cycle time delay.
(Parameter AC = 5minutes)
Probe alarm P1 is cleared with no time delay after the fault is cleared.
Probe alarm P2 starts and stops with no time delay.
Temperature alarm HA automatically clears as soon as the temperature returns
to below 105°F (the ALU setpoint) -2°F = 103°F.
Temperature alarm LA automatically clears as soon as the temperature returns
to above 55°F (the ALL setpoint) +2°F = 47°F.
Temperature alarm HA2 automatically clears as soon as the condenser coils
temperature returns to below 135°F.
Temperature alarm LA2 automatically clears as soon as the condenser coils
temperature returns to above 60°F.
Temperature alarm CA automatically clears as soon as the pressure returns to
normal.
Preventative Maintenance
Air conditioners require regular cleaning of the condenser air inlet filter.
Wash filter often if washable using proper cleaning compound and back flushing
the dirt out, or replace if not washable whenever it appears physically dirty.
Restriction to the flow of air over the condenser coil will degrade the
performance of the equipment, cause it to overheat, reduce cooling and can
damage the compressor.
The overload switch in the compressor may cause the compressor to cycle if the
condensing coil pressure becomes too high due to air restriction. A further
safety feature is the refrigerant high pressure cut off switch which will stop
the compressor if the condensing pressure becomes too high due restricted
condenser air flow or some other cause.
Restricted air flow due to neglecting a dirty filter will cause unit to
repeatedly turn off and then turn back on after it cools off. An operation in
this safety cycling mode will eventually damage the equipment and void the
warranty.
Refer to Field Serviceable Parts section in this manual for details on parts
that can be changed to help increase the uninterruptable life of the Air
Conditioner.
Air Filter Service
Remove the air conditioner filter and wash if washable or replace if not
washable. Dry thoroughly before replacing. THERMAL EDGE Air Filter Treatment
Spray in aerosol cans or spray bottle is recommended to enhance air filter
efficiency. Replacement filters are readily available from THERMAL EDGE
Customer Service. DO NOT operate the air conditioner without the air filter.
Such operation will allow the condenser coil to become dirty and loose
efficiency, causing overheating and diminished cooling capacity. Dirty
condensing coils must be back-flush cleaned using proper commercial coil
cleaning compounds and thorough back-flush rinsing. Refer to directions on the
cleaning compounds selected. Acid wash is not recommended as it reduces the
life of the coil.
Note: Do not use solvents to clean the programmable thermostat. Wipe with mild
soap and water.
Condenser and Evaporator Fans
Thermal Edge air conditioners use high efficiency, long life, sealed ball
bearing fans engineered for optimum performance that require no maintenance.
Keep fan blades clean for optimal performance.
Fans are removable and attached by plug in connections.
Compressor
Thermal Edge uses hermetically factory sealed compressors that are quiet, low
vibration and are maintenance free. Thermal overload devices are installed to
protect the compressor from damage due to overheat and short cycle faults. If
the compressor thermal overload fails, it is recommended to return the unit to
Thermal Edge customer service for proper replacement. Note that the rotary
compressor runs with compressed refrigerant gas on the outer case and
therefore is hot to the touch.
Loss of Refrigerant
Thermal Edge air conditioners are meticulously leak and run tested after
assembly. If a leak in the system should develop due to shipping damage or
mechanical vibration, the leak must be detected, repaired and the refrigerant
charge restored to the system by a qualified refrigeration professional.
Field Serviceable Parts
Thermal Edge carefully designs and selects components with the maximum life expectancy. Due to OEM manufacturing tolerances, poor unit maintenance or extreme operating conditions, components may fail before their maximum life expectancy. The table below lists parts that are serviceable in the field by an Air Conditioner Technician.
Part Description | Thermal Edge Part # |
---|---|
Digital Controller | 52112-1 52111-2 w/ both Dry C and Heater |
Low Pressure Switch | 38151-1 |
Condenser Fan Cut-In Pressure Switch | 38001-1 |
Temperature Probe | 52126-1 |
Condenser Fan Relay | 55762-1 |
Thermal Expansion Value TXV | HC201: 32008-1 |
Compressor | HC201: 31040-1 |
Compressor Thermal Overload | Internal |
Gasket Installation Kit | 71405-HC20 |
Evaporator Fan | 41062-2-1 |
Condenser Fan | 41060-2-1 |
Filter Media | 44013-1 |
Capacitor | HC201: 54006-1 |
Contactor Relay | 55765-1 |
Safety Information
Unit is carefully designed to restrict access to movable parts to minimize any
potential injury. This Air Conditioner has been tested by UL to meet the
safety requirements of the UL484 specification. When working with the Thermal
Edge Air Conditioner always makes sure shroud is installed. Verify proper
voltage is applied to unit as specified in the UL label of the Air
Conditioner. In the event of a field service repair, power down unit using the
power on/off switch and disconnect power from unit. It is always recommended
to use a licensed Air Conditioner Technician for internal diagnostics and
repairs issues.
Contact Thermal Edge technical support for further details on opening the unit
and troubleshooting tips.
Troubleshooting Guide
The following guide provides a flow chart to identify a problem, determine the
root cause and identify the action needed to correct an issue.
*3Note : Refer to Electrical Schematics for further diagnostics.
Physical Dimensions
480 VAC Models
Electrical Schematics
System Schematic
Digital Controller Schematic Note: Schematics applies to all voltages; optional accessories wiring not provided in this document. If you require electrical schematic with options contact our technical support and provide your model number.
Warranty Information
Thermal Edge products are warranted to be free of defects in workmanship,
materials and components.
The warranty period applies from date of shipment for one year.
The above warranty applies when the equipment is operated under the following
conditions:
- Ambient temperature not in excess of performance rating in normal atmosphere or as stated on product nameplate
- Voltage variation no greater than ± 10% from nameplate rating
- Frequency variation no greater than ± 3Hz from nameplate rating
- Maximum cooling load no higher than air conditioner nameplate rating
- Waiting five minutes before restarting air conditioner after intentional or accidental shutoff
- Compliance to all other installation, maintenance and operating instructions, as supplied
Thermal Edge cannot assume responsibility for misapplication of its products
or the erroneous selection of an inappropriate product by a non-authorized
Thermal Edge representative. Our applications engineers will gladly assist in
the selection of the proper product provided all required details of the
application are furnished.
Thermal Edge assumes no liability beyond the repair or replacement of its own
product. This Warranty does not cover:
- Labor or reimbursement of labor for evaluation, removal, installation, repair, or cost of any warranted part, except at the Thermal Edge factory in Dallas, Texas
- Use of equipment for other than its designed purpose or operating conditions
- Operation in harsh, oily, corrosive or other abnormal environmental conditions, without the proper filtration, sealing, protective coatings and/or weather protection
- Damage to hermetic system resulting from continuous operation with dirty or clogged air filters or improper or negligent maintenance
- Use of refrigerant other than designated
- Customer modification or abuse
- Shipping damage or other accident
- Repair or service by unauthorized personnel.
Cracked or broken hermetic tubing or brazed joints caused by shipping damage
or mishandling are not covered under the Warranty. Claims for shipping damage
are the responsibility of the Consignee. Timely claims must be filed with the
freight carrier.
The purchaser assumes the responsibility of grounding the unit and installing
it in accordance with local electrical and safety codes, as well as the 2008
National Electric Code (NEC) and OSHA.
THIS WARRANTY CONSTITUTES THE ENTIRE WARRANTY WITH RESPECT TO THE PRODUCT AND
IS IN LIEU OF ALL OTHERS, EXPRESSED OR IMPLIED, INCLUDING ANY WARRANTY OF
MERCHANTABILITY AND WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE AND IN NO
EVENT IS THERMAL EDGE RESPONSIBLE FOR ANY CONSEQUENTIAL DAMAGES OF ANY NATURE
WHATSOEVER.
Return Material Authorization (RMA) Procedure
All returns require a Return Material Authorization (RMA) number for warranty
or non-warranty repair, rotation of stock, damage or any other reason.
IMPORTANT
Returns without an RMA number will be refused and returned. Improper packaging
may void warranty. Air Conditioners shipped laying down will void the
warranty. Collect shipments will be refused. Returns received after 60days
will be refused and RMA will be canceled.
Please be ready to provide:
- Purchase Order Number & Date
- Product Description & Reason for Request
- Model Number & Serial Number
- Customer name and contact info (email, phone number and address)
- Shipping method
Pack unit in a suitable packing for shipment, preferably the original packaging if available.
- If suitable packing is not available, arrange for packaging to be shipped to you.
- Air Conditioners must be returned in an upright position properly secured to a pallet.
- Tip unit to empty water from the evaporator and boil off pans.
- Clearly mark the RMA number on the box.
- Customer will pay all freight charges.
Out of Warranty Repair
If your Thermal Edge air conditioner is out of warranty and requires repair,
simply call Thermal Edge Customer Service at (888)-580-0202 for an RMA number.
Customer Service will help you determine what repairs or parts are needed and,
if possible, an estimate of the cost.
After the unit is received and diagnosed, you will receive a ship estimate on
the work and parts needed. The repairs and test process may uncover other
issues for which you will be informed and given quotes for the work needed.
1751 Hurd Drive
Irving, Texas 75038
972-580-0200
888-580-0202
Fax 972-580-0277
URL: www.thermal-edge.com
Email: thermaledgeinfo@thermal-edge.com
SP-ENG-211-000-11 Rev 1.0