PENTAIR Aurora 7710 IntelliBoost Constant Pressure Variable Speed Booster Systems Installation Guide
- June 10, 2024
- Pentair
Table of Contents
- PENTAIR Aurora 7710 IntelliBoost Constant Pressure Variable Speed Booster
- Multiple Pump Controllers -maximum (4) VFD’s:
- VFD Operation:
- VFD Parameters and Communication Settings:
- BASIC DESCRIPTION AND OPERATION OF BOOSTER CONTROLLER
- Normal Operation (Auto On ‐ VFD)
- Select number of pumps to be operated by Controller
- BASIC DESCRIPTION AND OPERATION OF BOOSTER CONTROLLER
- Relay Outputs can choose to indicate:
- BASIC DESCRIPTION AND OPERATION OF BOOSTER CONTROLLER
- BASIC DESCRIPTION AND OPERATION OF BOOSTER CONTROLLER
- BASIC DESCRIPTION AND OPERATION OF BOOSTER
- BASIC DESCRIPTION AND OPERATION OF BOOSTER
- BASIC DESCRIPTION AND OPERATION OF BOOSTER
- Controller:
- Additional I/O Connections:
- IntelliBoost System for PLC 570
- | (Hex)| Description| 16 ‐bit| Read| Write
- Troubleshooting Guide
- Motor Protection
- OPERATION
- **** WARNING! Risk of electric shock.
- CAUTION! Risk of flooding.
- CHECKING DIRECTION OF ROTATION
- WARNING! Risk of electric shock.
- STARTING
- WARNING!
- WARNING! Risk of electrical shock and possible unexpected starts.
- Danfoss Drive Preventive Maintenance Instruction
- APPLI CATI ONS ENGINEERING NEWSLETTER
- OPERATION
- Priming
- Troubleshooting
- WARRANTY
- Read More About This Manual & Download PDF:
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
PENTAIR Aurora 7710 IntelliBoost Constant Pressure Variable Speed Booster
Multiple Pump Controllers -maximum (4) VFD’s:
The controller will have a power OFF/ON selector switch to power up system. The normal operation of the controller as well as the staging of the pumps is controlled by an independent processor. The VFD(s) act as “signal follower” and do not independently control the speed of the pumps in “Auto On” mode. For initial setup and in the event of a system failure, the VFD(s) can run the pumps in “Hand On” control at a user selected fixed speed, ignoring all signals from the pump controller.
VFD Operation:
2‐4 drives operate in the same manner. Hand On, Off, Auto On and Reset is the basic operations for the Local Control Panel. “Hand On” selection required for independent drive manual operation. Off will turn off VFD, stopping pump rotation. Auto On is selected when PLC is ready for testing and operation. Reset in case of VFD fault, refer to operation manual.
VFD Parameters and Communication Settings:
VFD parameters set as described below should be entered when VFD is in the Off position. PLC and VFD are master slave configured using Mod Bus RTU communication. Loss of communication will stop drive after Timeout. Each drive shares same parameter set except where drive name is required (Drive1 = 2, Drive2 = 3, Drive3 = 4, Drive4 = 5). A Master Local Control Panel, LCP, is used to Copy and Download parameters from VFD to VFD.
PARAMETER | DESIGNATION | DEFAULT |
---|---|---|
0‐01 | Language | US English |
0‐02 | Motor Speed Units, RPM or Hz | Hz |
0‐03 | Regional Settings | North America |
1‐03 | Torque Characteristics | Auto EnergyOptim VT |
1‐23 | Motor Frequency | Nameplate |
1‐24 | Motor Current | Nameplate |
1‐25 | Motor Speed | Nameplate |
3‐03 | Maximum Reference | 60Hz |
3‐41 | Ramp Up Time | 2 sec. |
3‐42 | Ramp Down Time | 2 sec. |
4‐14 | Motor High Speed Limit | 60Hz |
4‐19 | Maximum Output Frequency | 60.1Hz |
4‐12 | Motor Speed Low Limit | 0Hz |
5‐12 | Terminal 27 | No Operation |
8‐01 | Control Site | Control Word Only |
8‐03 | Control Time Out | Limit 3.0 sec. |
8‐04 | Control Time Out Function | Stop |
8‐10 | Control Word Profile | FC Profile |
8‐30 | Protocol | Modbus RTU |
8‐31 | Addresses | Drive1 = 2, Drive2 = 3, Drive3 = 4, Drive4 = 5 |
8‐32 | FC Port Baud Rate | 19200 |
8‐33 | Parity | Even Parity, 1 Stop Bit |
8‐42 | PCD Write, Configuration: | [0], [1685] FC Port CTW 1 |
[1], [1686] FC Port Ref 1 | ||
8‐43 | PCD Read, Configuration: | [0], [1603] Status Word |
[1], [1603] Main Actual Valve | ||
[2], [1614] Motor Current | ||
[3], [1618] Motor Thermal | ||
[4], [1500] Operating Hours | ||
[5], [1501] Running Hours | ||
[6], [1610] Power [KW] | ||
[7], [1634] Heatsink Temp | ||
[8], [1502] Kwh Counter | ||
[9], [1692] Warning Word | ||
[10], [1693] Warning Word 2 | ||
[11], [1690] Alarm Word | ||
[12], [1691] Alarm Word 2 | ||
[13], [1612] Motor Voltage | ||
[14], [1616] Torque (Nm) | ||
8‐50 | 50 Thru 56 | Bus |
0‐50 | LCP Copy | All To LCP – After Drive successfully |
programmed
0‐50| LCP Down Load| Download all from LCP – Use existing LCP,
download to drive
BASIC DESCRIPTION AND OPERATION OF BOOSTER CONTROLLER
Normal Operation (Auto On ‐ VFD)
The Pump Controller receives a system pressure signal from the Discharge
Pressure Transducer. The signal is compared to the Set point and the pump(s)
speed is adjusted.
Set point: Desired system pressure.
Minimum Set point: Desired minimum system pressure.
Home: Default Screen on power‐up. Shows real-time system operation, status,
settings and hardware. Horn & Lt Enable/Disable and active Alarms can be
viewed and reset
PLC screen operates with touch response.
Flashing Green = Optional Active Communication RS = Ramp Speed, limits speed
when Red
NF = No Flow, when Red
OC = Overcurrent/Minimum Suction, when Red
Remote Active displays when Remote operation is turned on. Continue to Setup:
Touch Menu on screen
Menu = the base of navigation. May be Password Protected, refer to Basic Setup
4.
If activated, Password Entry Basic screen will display when Menu button
touched. When correct Pin is entered, Menu screen will display. If incorrect,
returns to screen with message “Incorrect
Password”. Reenter correct Pin or ESC.
See Password Disable/Enable Set Password/Pin Number screen.
Basic Setup screens need to be completed by Factory and/or End User before
operation.
To set Time, Date and Year ‐ Touch SET, enter information. Set Discharge and
Minimum Discharge Set points.1
Minimum Discharge Set point ‐ Minimum system allowable pressure
Select number of pumps to be operated by Controller
Select number of pumps to be operated by Controller.
Timed Pump Rotation by Hours of Operation: Lead pump will rotate on every
start and changes to next lead pump when continuous Hours of Operation Timed
is timed out. Lag pump turns on and off as called for.
Same Lead Pump for all Starts: Same Lead pump turns on for every start.
If Lead pump is disabled in anyway, Lead Pump will shift to next available
pump. Lag pump turns on and off as needed
Transducer Failure Settings, when in Auto mode: Select Alarm or Fault. Alarm
allows continued operation when system is in Auto Mode, will run at Speed
entered in Setting. If no flow detected, drives will stop. Periodic starts
will determine if flow is established. Fault will stop all drives.
Password Setup: When Enabled, enter up to (4) numbers to be stored as
Password/Pin.
Screensaver: When ON, input mins of inactivity (minimum 2mins).
Review Selections. If need adjusting, use Back or Start Basic Setup Over button. Press Finish when done.
BASIC DESCRIPTION AND OPERATION OF BOOSTER CONTROLLER
DC signal supplied by controller. Inputs selectable as: Unused, Alarm, Fault,
Fault Reset or For Relay Out. Input 1 may be selected to Stop Pumps. 4 Inputs
standard, additional 4 can be added as an option.See IntelliBoost Electrical
Drawing
If Alarm is selected, press Alarm Button to configure. Input Alarm
Configuration screen will display. See Input Alarm Configuration screen.
Once alarm has been pressed from previous screen, continue with configuration.
Setup Input 1,2,3,4 will allow multiple alarms to cause a fault. Inputs 5‐8
Alarm Configuration allowed, if available.
Alarms are recorded. Number of Alarms is a set value not to be exceeded. If
exceeded within a set time period, a Fault will occur and system will stop
operating. Fault restart requires Operator assistance. Fault must be cleared
or disabled for continued operation.
The output relays are form C contacts rated 240Vac 6A. 4 Relay Outputs are standard, additional 4 can be added as an option. See IntelliBoost Electrical Drawing
Relay Outputs can choose to indicate:
System On Auto Flow
Alarm High
System On Manual Flow
Fault High
Pump Running All
Alarms
VFD Alarm
All Faults
Discharge Pressure System Alarm Low Digital In 1
Discharge Pressure System Fault Low Digital In 2
Discharge Pressure System Alarm High Digital In 3
Discharge Pressure System Fault High Digital In 4
Suction Pressure System Alarm Low Digital In 5
Suction Pressure System Fault Low Digital In 6
Suction pressure System Alarm High Digital In 7
Suction pressure System Fault High Digital In 8
Flow Alarm Low
Maintenance Alarm
BASIC DESCRIPTION AND OPERATION OF BOOSTER CONTROLLER
Equipment Maintenance Alarm based on Hours of Operation and Starts. To disable
Alarms, enter ‐1 at Default.
Maintenance Alarms indicated and Reset on Home screen.
Maintenance grouped:
First line ‐ Number of operations/hours. Zeros upon Alarm reset. Second line ‐
Default setting for Maintenance Alarm.
Third line ‐ Total accumulation. Can’t be modified.
An alarm is activated when First line’s number equals or exceeds Alarm
Default. A marker will appear at the default when alarm activates on the
Maintenance Alarm screen. A Maintenance Alarm will be flashing on Home Screen.
If alarm in Alarm Group is acknowledged, then Maintenance Alarm will stop
flashing and number (counts) will stay active. If alarm is reset, then the
number or counts will be reset to zero. Default will stay the same and Total
will continue to accumulate throughout the life of PLC.
Defaults can be modified.
Alarm records can be retrieved in Fault and Alarm History.
COM – Optional functions: SD Card and Ethernet with Web Server:
SD Card: Can copy Settings and Values from PLC to SD Card or saved Values on
SD Card to PLC.
Webserver: Ethernet Web Server, SD Card included and must be in installed in
the Controller for operation.
Remote Operation ‐ Enable/Disable via Modbus Control. Ethernet, Port 3, if
available: Modbus IP Bridge Access. PLC Name ‐ If Network requires.
RS 485 ID ‐ Modbus Bridge Access.
Active Communication ‐ Flashing Green = Active.
Real-time Drive information and Controls. HMI Drive controls allow basic drive
operation without using the Local Control Panel at VFD. Drive screens monitors
basic Drive Parameters, Speed in Hz, and VFD On/Off. VFD must be in Auto Mode
for this screen operation. On Auto Test and on Transducer failure this screen
will go into Manual Control.
BASIC DESCRIPTION AND OPERATION OF BOOSTER CONTROLLER
Complete history of all Alarms and Faults.
Advanced Menu may be Password Protected, refer to Password Entry Advanced
screen.
If Password Protection for Advanced Menu is enabled, Password Entry Advanced
screen will display when Advanced Menu button touched. When correct
Password/Pin is entered Menu screen will display. If incorrect, returns to
screen with message “Incorrect
Password”. Reenter correct Password/Pin or ESC.
Menu = the base of navigation. May be Password Protected, refer to Basic Setup
4.
If activated, Password Entry Basic screen will display when Menu button touched. When correct Pin is entered, Menu screen will display. If incorrect, returnsto screen with message “Incorrect Password”. Reenter correct Pin or ESC. See Password Disable/Enable Set Password/Pin Number screen.
Basic Setup screens need to be completed by Factory and/or End
User before operation. To set Time, Date and Year ‐ Touch SET, enter
information.
Set Discharge and Minimum Discharge Set points.
Minimum Discharge Set point ‐ Minimum system allowable pressure
BASIC DESCRIPTION AND OPERATION OF BOOSTER
HMI Manual Max Speed (Hz) ‐ Max speed (Hz) the VFD’s can operate whenset used
as Manual Control operation via HMI.
Note – VFD keypad must be in Auto On for manual control through HMI.
Max and Min Speed VFDs ‐ Maximum speed VFD can operate when in
Auto On mode and Controller is in operation.
Reduce Speed on No Flow: If ON and no flow is detected, will stop pumps under
normal operation.
Reduce Speed on Pump Limit: If ON and when pump is unable to reach pressure
and in no flow, then set pressure will reduce until pressure is met and pumps
turn Off. ? ‐ Will take you to Information Screen
Auto Detect is factory default and preferred operation
Stop and Start Set points are set to minimum predicted speed when pump is no
longer working efficiently.
Stop and Start Delay ‐ Adjusted for system operation
Manual Start Speed, must be set before Manual Stop Set point.
Manual Stop Set point must be = < Manual Start Speed.
Speed to Start Lag must be set no > 59.5Hz Speed
Start Lag must be set = > Start Speed. ? ‐ Will take you to Information
Screen.
Ramp speeds set at Factory. Minimum adjustment for system operation may be
necessary to fine tune system operation.
Ramp Limit ON- Lead and Lag Ramp Decel/Accel: Modifies ramp speed when sudden
low or high demand occurs. Lead and Lag set to same level in normal
operations.
Current Limit ON ‐ Deceleration on Limits will be activated when current or
min suction has been exceeded. Once activated, it will reduce power to pump
from Drive.
Motor FLA and Min. Suction for pump operation.
Time Delays to Reduce Speed: Delays Lead and Lag normal pump turn off
sequence.
Reaction Time: PLC Real-time delay for operations.
Lead Pump Decel must be = > Lag Ramp Decel. Lead
Ramp Accel must be = > Lag Ramp Accel. ? ‐ Will take you to Information
Screen.
Current values will indicate settings as tested at Factory.
Setpoint = Discharge set point taken from Basic Screen 1.
Min to Start = Minimum Discharge Setpoint, Basic Screen 1.
Max Setpoint ‐ Adjusts for Suction changes.
Adj SP ‐ Adjusts for Suction changes.
Adj Min to Start ‐ Adjusted for system variables running outside of normal
conditions.
? ‐ Will take you to Information Screen.
BASIC DESCRIPTION AND OPERATION OF BOOSTER
Auto-Commission – To commission your Intelliboost system you must have
the Main Discharge Isolation Valve turned in the off position to ensure the
booster is in a “no flow” condition. (Suction Main Isolation Valve remains
open). No Flow Test or No Flow Adjust, required a means to ensure no flow can
occur. Remote Operation, if available, must be Disabled. Booster pressure
needs to be reduced during test, if necessary, through discharge pressure
gauge valve.
Stop will cancel No Flow Test or No Flow Adjust Test at any time.
No Flow Adjust may be changed manually. NOTE: Before pressing Start, Zero out
values present in No Flow Adjust columns.
No Flow Test:
No Flow Adjust:
VFDs for Pumps being tested must be in Auto. VFDs for Pumps being
tested must be in Auto.
Press Start, changes to Running while testing, returns to Start upon
completion.
Reduce Discharge flashes when booster’s
pressure needs to be reduced, reduce until Reduce Discharge stops flashing.
First Low and then High Hz kW Set-points will be determined for each drive in
while testing is performed .
Pressure Drop to Start Lead: If Discharge or Suction drop is > entered value
and is < a sec. Lead Pump will start.
Suction Drop to Start Lead in No Flow ‐ Updates system timers and set points.
Min. To Discharge to Start ‐ Basic Setup 1.
Intervals to Start when No Flow ‐ When system is inactive, a timed interval
start will occur. Updates system timers and set points.
Discharge and Suction Transducers Range ‐ Enter range marked on Transducer in
PSI. Set at Factory.
Alarms to Fault – A number of Alarms activated per Alarm setting in assigned
amount of hours will cause system to Fault and pumps will stop operating
Alarms and Faults – Alarms are set values to warn of conditions that may be
harmful or undesirable for system. Alarms Reset when system returns to desired
operational values. Alarm is recorded in Number of Alarms. Faults are set
values not to be exceeded. If exceeded, system will stop operating. Fault
restart requires Operator assistance. Fault must be cleared or disabled for
continued operation.
Alarm records can be retrieved in Fault and Alarm History.
BASIC DESCRIPTION AND OPERATION OF BOOSTER
Bypass Password Protection. Basic and Advanced Passwords may be accessed from
Home screen.
To Access
Go to Home Screen
Touch the Time once (in right‐hand upper corner) Touch PENTAIR logo three
times
Touch Discharge PSI text once
Controller:
Description: 16”h x 12”w x 8”d, NEMA 4 Enclosure (Optional NEMA 4X Clear
Cover)
Power : 100‐240 VAC 50/60 Hz
Operator Controls: Audible/Visual Alarm Control Connections :
RS485 Communication Port 1 to VFDs
RS485 Communication Port 2, See Modbus Slave Address Table Discharge Pressure
Transducer (4‐20 mA) Suction Pressure Transducer (4‐20 mA)
External Fault and Alarm inputs, (4) ‐ User defined
Relay Outputs (6 amp, form ‘C’) fault and alarm, (4) ‐ User defined
Additional I/O Connections:
External Fault and Alarm Inputs, maximum (8 total) – User defined Additional
Relay Outputs (6 amp, form ‘C’), maximum (8 total) ‐ User defined Additional
Options:
SD Card for application settings (Copy To and From SD Card) Ethernet, See
Modbus Slave Address Table Ethernet Webserver ‐ Home Screen and Maintenance
Alarm Screens
IntelliBoost System for PLC 570
Modbus Slave Address Table
Booster Communication: Ethernet Modbus TCP IP Slave, Port 502
Data: All packed values stored as most significant byte
Host IP Address: . . . , Subnet Mask: . . . Gateway: . . .
Connection: Port 3, RJ45
Booster Communication: Serial Modbus RS 485 Slave, ID 1
COM 2, 9600, 8, N, 1 (1/2 Duplex)
Connection: Port 2, RJ12 on side of PLC Pin 1 (A+), Pin 6 (B‐)
Int| Addr| Function|
| (Hex)| Description| 16 ‐bit| Read| Write
1| 640| PLC Mode (Off/Auto) 0=Off, 1=Auto| X| X|
2| 641| Alarm Active ‐ 0=None, 1=Active| X| X|
3| 642| Maintenance Alarm Active ‐ 0=None, 1=Active| X| X|
4| 643| Fault Active ‐ 0=None, 1=Active| X| X|
5| 644| Drive 1 Fault ‐ 0=None, 1=Active| X| X|
6| 645| Drive 2 Fault ‐ 0=None, 1=Active| X| X|
7| 646| Drive 3 Fault ‐ 0=None, 1=Active| X| X|
8| 647| Drive 4 Fault ‐ 0=None, 1=Active| X| X|
9| 648| Pump 1 Status (ON/OFF) 0=No Operation, 1=In Operation| X| X|
10| 649| Pump 2 Status (ON/OFF) 0=No Operation, 1=In Operation| X| X|
11| 64A| Pump 3 Status (ON/OFF) 0=No Operation, 1=In Operation| X| X|
12| 64B| Pump 4 Status (ON/OFF) 0=No Operation, 1=In Operation| X| X|
13| 64C| Pump 1 Comm Status (OK/Error) 0=OK, 1=Error ‐ VFD to PLC| X| X|
14| 64D| Pump 2 Comm Status (OK/Error) 0=OK, 1=Error ‐ VFD to PLC| X| X|
15| 64E| Pump 3 Comm Status (OK/Error) 0=OK, 1=Error ‐ VFD to PLC| X| X|
16| 64F| Pump 4 Comm Status (OK/Error) 0=OK, 1=Error ‐ VFD to PLC| X| X|
17| 650| All Status Bits (1‐16), Most significant byte first| X| X|
18| 651| VFD 1 Mode ‐ 0=Auto, 1=Local, 2=HMI Manual, 3=Transducer Failure| X|
X|
19| 652| VFD 2 Mode ‐ 0=Auto, 1=Local, 2=HMI Manual, 3=Transducer Failure| X|
X|
20| 653| VFD 3 Mode ‐ 0=Auto, 1=Local 2=HMI Manual, 3=Transducer Failure| X|
X|
21| 654| VFD 4 Mode ‐ 0=Auto, 1=Local 2=HMI Manual, 3=Transducer Failure| X|
X|
22| 655| Discharge PSI (Set Point) – 4 Digits, 1 Dec (999.9 PSI)| X| X|
23| 656| Discharge PSI (Scaled Transducer Value) – 4 Digits, 1 Dec (999.9
PSI)| X| X|
24| 657| Flow GPM (Set Point) – 4 Digits (9999 GPM)| X| X|
25| 658| Flow GPM (Scaled Transducer Value) – 4 Digits (9999 GPM)| X| X|
26| 659| Suction PSI (Scaled Transducer Value) – 4 Digits, 1 Dec (999.9 PSI)|
X| X|
27| 65A| Drive 1 Speed (99.9 Hz)| X| X|
28| 65B| Drive 2 Speed (99.9 Hz)| X| X|
29| 65C| Drive 3 Speed (99.9 Hz)| X| X|
30| 65D| Drive 4 Speed (99.9 Hz)| X| X|
27| 65E| Drive 1 KW (99.99 KW)| X| X|
28| 65F| Drive 2 KW (99.99 KW)| X| X|
29| 660| Drive 3 KW (99.99 KW)| X| X|
30| 661| Drive 4 KW (99.99 KW)| X| X|
31| 662| Discharge PSI (Set Point) – 4 Digits, 1 Dec (999.9 PSI)| X| X| X
32| 663| Flow GPM (Set Point) – 4 Digits (9999 GPM)| X| X| X
33| 664| PLC Mode (Off/Auto) 0=Off, 1=Auto| X| X| X
Troubleshooting Guide
**** Field Wiring
**** All wiring connections and wiring sizes must meet National Electrical Code and local requirements.
Motor Protection
**** See the motor nameplate for electrical connection/wiring diagram. Aurora® pumps must be used with the proper size and type of motor starter to ensure protection against damage from low voltage, phase failure, current imbalances, and overloads. The overload should be sized to trip at the full- load current rating of the motor.
OPERATION
Priming WARNING! Risk of explosion and scalding.
Do not run the pump with the discharge valve closed; the water in the pump
may boil, causing risk of explosion and steam burns to anyone nearby.
**** WARNING! Risk of electric shock.
Can shock, burn or kill. Disconnect all power to the pump before
servicing or working on the pump. Make sure that the power is locked out and that the pump cannot be accidentally started.
NOTICE : Under no circumstances should the pump be operated without
flow through the pump. Never operate the pump dry.
Operation of closed system or open system with the liquid level above the
pump priming plug.
- Close the discharge isolating valve and loosen the needle valve located in the assembly in the pump head (figure below). Do not remove the needle
NOTICE: On PVM(X)2/4 models, remove the couple guard for access to the vent plug.
CAUTION! Risk of flooding.
Can cause personal injury and/or property damage. Watch the direction of
the priming plug and make sure that the liquid escaping from it does not
injure persons nearby
or damage the motor or other components. In hot water installations, pay
particular attention to the risk of injury from scalding hot water.
- Slowly open the isolation valve in the suction pipe until a steady stream of liquid runs out the vent in the priming
- Tighten needle valve to 25 inch-pounds. Completely open isolation
NOTICE: Please see to “Starting” before proceeding any further.
Operation of open systems with the liquid level below the top of the pump:
**NOTICE: The suction pipe requires a check valve or isolation valve.**
- Close to discharge isolation
- Remove the vented priming
- Pour liquid through the priming port until the suction pipe and the pump are completely filled with
- Replace the vented priming plug and tighten it
- Repeat steps 1 – 4 until the pump is
NOTICE: Please see “Starting” before proceeding any further
CHECKING DIRECTION OF ROTATION
**NOTICE:** Do not disconnect the motor from the shaft to check the
direction of rotation. If you remove the coupling, then you must adjust the
shaft position when you reinstall it. This must be done before starting the
pump.
Arrows on the pump head show the correct direction of rotation. When seen
from the motor fan, the pump should rotate counterclockwise . For
pump motors without a fan, remove one of the coupling guards and look at the
coupling to determine the direction of rotation. Turn off the pump and replace
coupling guard.
NOTICE: Do not check the directions of rotation until the pump has been filled with liquid. See “Priming” above.
- Switch power
- Remove the coupling guard and rotate the pump shaft to be certain it can turn freely. Replace the coupling
- Verify that the electrical connections are in accordance with the wiring diagram on the
- If the fan is visible, turn on and off to verify
- To reverse the direction of rotation, first switch OFF the power
- On three phase motors, switch 2 of the 3 power leads on the load side of the starter. On single phase motors, see the connection diagram on the motor Change the wiring as indicated.
WARNING! Risk of electric shock.
Can shock, burn or kill. Ground the pump motor correctly before
connecting to power supply per article 250-80 of National Electric Code (NEC) in the U.S., or the Canadian Electrical Code (CEC), as applicable.
- Switch the power supply and recheck the direction of motor
STARTING
-
If a suction line isolation valve has been installed, check to be sure that it is completely
-
For initial starting, the isolation valve in the discharge pipe should be almost
-
Start the
-
When the piping system has been filled with liquid, slowly open the discharge isolation until it is completely Opening the valve too fast may result in water hammer in the discharge pipe. If the pump or system starts to rattle, the pump is cavitating; to avoid damage to the pump, reduce the flow through the discharge isolation valve until the rattling stops. If this does not give adequate flow for your installation, call your installer or system designer.
-
Record the voltage and amperage of the Adjust the motor overloads if required
-
If pressure gauges have been installed, check and record operating
-
Check all controls for proper
WARNING!
If motor is nameplated for hazardous locations, do not run motor without
all of the grease or drain plugs installed.
Service Conditions
| NEMA Frame Size
---|---
140-180| 210-360| 400-510
1800 RPM
and less
| Over 1800 RPM| 1800 RPM
and less
| Over 1800 RPM| 1800 RPM
and less
| Over 1800 RPM
Standard| 3 years| 6 months| 2 years| 6 months| 1 year| 3 months
Severe| 1 year| 3 months| 1 year| 3 months| 6 months| 1 month
Season| 1. For Motors nameplated as “belted duty only”, divide the above
intervals by 3
2. Lubricate at the beginning of the season. Then follow service schedule above.
WARNING! Risk of electrical shock and possible unexpected starts.
Disconnect all power to the pump before servicing or working on pump.
Make sure that power is locked out and that pump cannot be accidentally started.
Problem | Cause |
---|---|
1. Motor does not run when started | A. Power failure |
B. Fuses blown
C. Motor starter overload has tripped out
D. Main contacts in motor starter are not making contact or the coil is
faulty.
F. Motor is defective
2. Motor starter overload trips out immediately when power supply is switched
on| A. One fuse has blown
B. Contacts in motor overload relay are faulty
C. Cable connections are loose or faulty
D. Motor winding is defective
E. Pump is mechanically blocked
F. Overload setting is too low
3. Motor starter overload trips out occasionally| A. Overload setting is too
low
B. Low voltage at peak times
4. Motor starter has not tripped out but the motor does not run| A. Power
failure
B. Fuses blown
C. Main contacts in motor starter are not making contact or the coil faulty
D. Control circuit fuses are defective
5. Pump capacity is not constant| A. Pump inlet pressure is too low
B. Suction pipe/pump is blocked
C. Pump is sucking air
6. Pump runs but gives no water.| A. Suction pipe/pump is blocked
B. Foot or nonreturn valve is blocked in closed position
C. Leakage in suction pipe
D. Air in suction pipe or pump
E. Motor rotates in the wrong direction
7. Pumps runs backward when switched off| A. Leakage in suction pipe
B. Foot or nonreturn valve is defective
C. Foot valve is blocked in open or partly open position
D. Nonreturn valve leaks or is blocked in open or partly open position
E. Discharge valve is defective
8. Leakage from shaft seal| A. Pump shaft position is incorrect
B. Shaft seal is defective
9.Noise| A. Cavitation is occurring in the pump
B. Pump does not rotate freely (that is, there is increased frictional
resistance) because of incorrect shaft position
NOTICE: The suction pipe requires a check valve or isolation valve.
- Close to discharge isolation
NOTICE: Please see “Starting” before proceeding any further.
CHECKING DIRECTION OF ROTATION
NOTICE: Do not disconnect the motor from the shaft to check the direction of rotation. If you remove the coupling, then you must adjust the shaft position when you reinstall it. This must be done before starting the pump.
Danfoss Drive Preventive Maintenance Instruction
PM Checklist
- Vacuum dust and dirt from heat sink fins
- Clean or replace as conditions require intake air filters (125 Hp constant torque models, 150 Hp variable torque models and larger have filters located behind the intake louver panels)
- Check ventilation fans for proper operation and clean as
- Confirm VFD’s ventilation clearances have not been obstructed
- Check electrical connections and re-torque as If possible, perform an IR thermal scan of the VFD’s power input and power output.
- Check line voltage
- Check motor & output phase balance
- Inspect DC buss capacitors (older drives)
- Record the VFD’s parameter settings using MCT-10
- Confirm the VFD doors and covers are in place and properly closed
2. Clean the drive’s interior.
- Dirt coating drive circuit boards and other components can interfere with proper cooling and even provide a path for electricity to short out along unintended paths. This can cause erratic operation and possibly damage to drive
- Corroded electrical connections can cause excess heat build-up, short circuits, erratic drive operation, and even component
- This should be done after the installation of the drives is complete and before power is applied to the drive. The main point here is to ensure that no metal filings or other installation-related dirt are inside the drive or its option
- If the drive is installed in an area where a lot of construction work will be performed, it is best to keep the drive covered while it is not in operation. Of course, if it is being used, the drive must be uncovered so that cooling air can be freely supplied to it. After the construction is complete it will be important to clean the interior of the drive. Low pressure, clean, dry air or similar commercial products can be used to clean dirt off of circuit boards. While a vacuum cleaner can be used to collect falling dirt, it is important to ensure that circuit boards are not damaged by the use of a powerful vacuum cleaner on the Inspect drive connectors for dirt or corrosion.
- In a normal environment, the drive’s interior should be inspected annually and cleaned, if necessary. In dirty environments, more frequent inspection is The level of dirt found inside the drive can be used to dictate the frequency of inspections and cleanings that is required.
3. Clean air filters (if any).
- Many VLT drives have no air However, some sizes and enclosure styles do use air filters in conjunction with their fan cooling systems. For these drives it is important to periodically inspect and clean or replace the filter element.
- Because the loading of the air filters can vary dramatically from one installation to another, it is important to initially check the air filters frequently to establish the required inspection interval
4. Check the tightness of connections.
Intelliboost™ Water Booster System
Basic Operation Manual
- Loose power connections can cause extra heating and/or arcing. The heating reduces efficiency and can actually melt down The arcing can cause intermittent currents and electrical noise. These can disrupt the operation of the drive.
- Loose or corroded ground connections can cause electrical noise problems. All of the VLT drives have some degree of electrical noise Some of this electrical noise is sunk to earth ground. Without a reliable ground connection the noise filters cannot operate as designed. In addition, a poor ground connection can become a safety issue.
- Loose control wires can cause intermittent operation of Loose or missing shielding for signal wires can cause erratic operation of the drive. In a extreme case this can even cause the drive to trip off.
- The preventive maintenance procedure would involve first turning off power to the drive and waiting until the DC bus capacitors have discharged to a safe Then all of the accessible connections should be inspection for corrosion and checked for tightness. It should not be necessary to disassemble the drive to perform this operation.
- This should be performed once the drive is installed and at least annually If the drive is subjected to vibration or wide temperature variations, it should be checked more frequently.
5. Check cooling fans.
- Cooling fans are used to remove heat from the drive. Proper operation of the cooling fans helps ensure long drive life by keeping the drive’s components cool. The cooling system should be inspected at least annually, more frequently when the drive is exposed to extreme
- Inspect the heat sinks, air inlets, and air outlets to ensure that there is an open path for air
- The cooling fans in many VLT drives will turn themselves off when the drive’s temperature is low enough to not require forced ventilation. To check for proper fan operation if the fans are not running, remove power from the When power is reapplied the fans should start and run for a few seconds.
- Listen for unusual noises from the fans when they are
- The VLT drives use a heat sink temperature sensor to help indicate if there is a problem with the cooling system. If the drive issues a HEAT SINK warning or alarm, check the cooling system carefully.
6. Check bus capacitors for voltage balance and/or physical damage.
- The large DC bus capacitors in the drives are subject to deterioration over an extended period of time. It generally takes a significant number of years before any problems occur, although high ambient temperatures and other factors can accelerate this process.
- Problems with the DC bus capacitors generally first show up as a large “AC ripple voltage” being superimposed on the DC bus. The VLT 6000 continually monitors for excessive DC bus ripple, so it will generally provide an early warning of bus capacitor If the drive gives a MAINS PHASE LOSS warning or alarm and a check of the input AC power line shows it to be balanced under loaded conditions, the DC bus capacitors should be checked carefully.
- On drives with an input power line voltage of 380 V AC or larger, the DC bus capacitors are connected as two banks that are in series with each other. With power applied to the drive, the voltage across the positive half should be within 10% of the voltage across the negative
- With power removed from the drive, a physical inspection of the capacitors should not show any deformation of the cases of the capacitors or liquid leaking from them.
- Low voltage capacitor testers are of no use in checking DC bus capacitors. The main concern is to ensure that the capacitors don’t have excessive leakage current when the DC bus voltage is applied to it. This cannot be tested at a low
- If one capacitor on the DC bus is found to be weak or damaged, it is important to replace the entire capacitor A capacitor with an excessive amount of leakage current places excessive stress on other capacitors in the bank.
- If it is convenient to access the two halves of the DC bus capacitors, the inspection technique given in “c” and “d” can be performed annually. Otherwise, it is best to simply let the drive’s internal monitoring circuitry described in “b” provide an indication of possible
Danfoss Drive Preventive Maintenance Instruction
- PM Checklist
Check box
Preventative Maintenance Step
Vacuum dust and dirt from heat sink fins
Clean or replace as conditions require intake air filters (125 Hp constant
torque models, 150 Hp variable torque models and larger have filters located
behind the intake louver panels)
Check ventilation fans for proper operation and clean as needed. Confirm VFD’s
ventilation clearances have not been obstructed
Check electrical connections and re-torque as needed. If possible, perform an
IR thermal scan of the VFD’s power input and power output.
Check line voltage
Check motor & output phase balance Inspect DC buss capacitors (older drives)
Record the VFD’s parameter settings using MCT-10
Confirm the VFD doors and covers are in place and properly closed
-
Clean the drive’s
-
Dirt coating drive circuit boards and other components can interfere with proper cooling and even provide a path for electricity to short out along unintended This can cause erratic operation and possibly damage to drive components.
-
Corroded electrical connections can cause excess heat build-up, short circuits, erratic drive operation, and even component
-
This should be done after the installation of the drives is complete and before power is applied to the drive. The main point here is to ensure that no metal filings or other installation-related dirt are inside the drive or its option
-
If the drive is installed in an area where a lot of construction work will be performed, it is best to keep the drive covered while it is not in operation. Of course, if it is being used, the drive must be uncovered so that cooling air can be freely supplied to it. After the construction is complete it will be important to clean the interior of the drive. Low pressure, clean, dry air or similar commercial products can be used to clean dirt off of circuit boards. While a vacuum cleaner ca be used to collect falling dirt, it is important to ensure that circuit boards are not damaged by the use of a powerful vacuum cleaner on the boards. Inspect drive connectors for dirt or
-
In a normal environment, the drive’s interior should be inspected annually and cleaned, if In dirty environments, more frequent inspection is required. The level of dirt found inside the drive can be used to dictate the frequency of inspections and cleanings that is required.
-
Clean air filters (if any).
-
Many VLT drives have no air However, some sizes and enclosure styles do use air filters in conjunction with their fan cooling systems. For these drives it is important to periodically inspect and clean or replace the filter element.
-
Because the loading of the air filters can vary dramatically from one installation to another, it is important to initially check the air filters frequently to establish the required inspection
-
Check the tightness of
-
Loose power connections can cause extra heating and/or arcing. The heating reduces efficiency and can actually melt down The arcing can cause intermittent currents and electrical noise. These can disrupt the operation of the drive.
-
Loose or corroded ground connections can cause electrical noise problems. All of the VLT drives have some degree of electrical noise Some of this electrical noise is sunk to earth ground. Without a reliable ground connection the noise filters cannot operate as designed. In addition, a poor ground connection can become a safety issue.
-
Loose control wires can cause intermittent operation of equipment. Loose or missing shielding for signal wires can cause erratic operation of the In a extreme case this can even cause the drive to trip off.
-
The preventive maintenance procedure would involve first turning off power to the drive and waiting until the DC bus capacitors have discharged to a safe level. Then all of the accessible connections should be inspection for corrosion and checked for tightness. It should not be necessary to disassemble the drive to perform this operation.
-
This should be performed once the drive is installed and at least annually If the drive is subjected to vibration or wide temperature variations, it should be checked more frequently.
-
Check cooling
-
Cooling fans are used to remove heat from the drive. Proper operation of the cooling fans helps ensure long drive life by keeping the drive’s components cool. The cooling system should be inspected at least annually, more frequently when the drive is exposed to extreme
-
Inspect the heat sinks, air inlets, and air outlets to ensure that there is an open path for air
-
The cooling fans in many VLT drives will turn themselves off when the drive’s temperature is low enough to not require forced To check for proper fan operation if the fans are not running, remove power from the drive. When power is reapplied the fans should start and run for a few seconds.
-
Listen for unusual noises from the fans when they are
-
The VLT drives use a heat sink temperature sensor to help indicate if there is a problem with the cooling system. If the drive issues a HEAT SINK OVERTEMP. warning or alarm, check the cooling system
-
Check bus capacitors for voltage balance and/or physical
-
The large DC bus capacitors in the drives are subject to deterioration over an extended period of It generally takes a significant number of years before any problems occur, although high ambient temperatures and other factors can accelerate this process.
-
Problems with the DC bus capacitors generally first show up as a large “AC ripple voltage” being superimposed on the DC bus. The VLT 6000 continually monitors for excessive DC bus ripple, so it will generally provide an early warning of bus capacitor If the drive gives a MAINS PHASE LOSS warning or alarm and a check of the input AC power line shows it to be balanced under loaded conditions, the DC bus capacitors should be checked carefully.
-
On drives with an input power line voltage of 380 V AC or larger, the DC bus capacitors are connected as two banks that are in series with each other. With power applied to the drive, the voltage across the positive half should be within 10% of the voltage across the negative
-
With power removed from the drive, a physical inspection of the capacitors should not show any deformation of the cases of the capacitors or liquid leaking from
-
Low voltage capacitor testers are of no use in checking DC bus capacitors. The main concern is to ensure that the capacitors don’t have excessive leakage current when the DC bus voltage is applied to This cannot be tested at a low voltage.
-
If one capacitor on the DC bus is found to be weak or damaged, it is important to replace the entire capacitor bank. A capacitor with an excessive amount of leakage current places excessive stress on other capacitors in the
-
If it is convenient to access the two halves of the DC bus capacitors, the inspection technique given in “c” and “d” can be performed Otherwise, it is best to simply let the drive’s internal monitoring circuitry described in “b” provide an indication of possible problems.
APPLI CATI ONS ENGINEERING NEWSLETTER
Bearing Lubrication Instructions for 300 Series End Suction Frame Mounted
Pumps
Grease lubrication is s tandard for the Aurora End Suction Frame Mounted Pumps
. Regreaseable bearings will require lubrication replacement and this can be
accomplis hed by us ing the lubrication fitting at each bearing. Lubricate the
bearings at regular intervals us ing high quality greas e. The initial bearing
lubrication at Aurora uses Chevron SRI Grease NLGI 2 (polyurea thickener). We
recommend this grease for follow-up relubrication. Most major brands of Grade
No. 2 ball bearing grease are satisfactory for pump operation in both wet and
dry applications. Be aware that mixing of different brands ofgrease should be
avoided due to possible chemical reactions between the brands that could
damage the bearings. A thorough flus hing of the old grease with the new is
highly recommended to minimize this potential incompatibility. Avoid greas e
of vegetable or animal base that can develop acids , as well as greas e
containing rosin, graphite, talc or other impurities . Under no circumstances
should grease be reus ed.
In dry locations , each bearing will need lubrication at least every 4,000 hours ofrunning time or every 6 to 12 months, whichever is more frequent. In wet locations the bearings should be lubricated at least after every 2,000 hours ofrunning time or every 4 to 6 months, whichever is more frequent. A unit is considered to be installed in a wet location if the pump and motor are exposed to dripping water, to the weather, or to heavy condensation such as found in unheated and poorly ventilated underground locations .
To lubricate, inject greas e into the lubrication fitting at the bearing cap near the coupling and also at the top of the bearing frame. Two to three shots of grease from a s tandard grease gun should be sufficient. The exces s grease will drop into the frame.
Note : Aurora Pump Distribution Center s tocks Chevron SRI #2 grease in 14 oz. tubes for grease guns under Aurora Part Number 384-0002-639.
OPERATION
Priming
Risk of explosion and scalding. Do not run the pump with the discharge
valve closed; the water in the pump may boil, causing risk of explosion and
steam burns to anyone nearby.
Risk of electric shock. Can shock, burn or kill. Disconnect all power to
the pump before servicing or working on the pump. Make sure that the power is
locked out and that the pump cannot be accidentally started.
NOTICE : Under no circumstances should the pump be operated without
flow through the pump. Never operate the pump dry.
Operation of closed systems or open systems with the liquid level above
the pump priming plug:
- Close the discharge isolating valve and loosen the needle valve located in the assembly in the pump IFBE (FJHVSF 8). %P OPU SFNPWF UIF OFFEMF
NOTICE : On BVMI(X)2/4 models, remove the coupling guard for access to
the vent plug.
Risk of flooding. Can cause personal injury and/or property damage. Watch
the direction of the priming plug and make sure that the liquid escaping from
it does not injure persons nearby or damage the motor or other components. In
hot water installations, pay particular attention to the risk of injury from
scalding hot water.
Vented
- Slowly open the isolation valve in the suction pipe until a steady stream of liquid runs out the vent in the priming
- Tighten needle valve to 25 inch-pounds. Completely open isolation
NOTICE : Please turn to Starting before proceeding any further.
Operation of open systems with the liquid level below the top of the
pump:
NOTICE : The suction pipe requires a check valve or isolation valve.
- Close the discharge isolation
- Remove the vented priming
- Pour liquid through the priming port until the suction pipe and the pump are completely filled with
- Replace the vented priming plug and tighten it
- Repeat steps 1-4 until the pump is primed. NOTICE : Please turn to Starting before proceeding any
Checking Direction of Rotation NOTICE : Do not disconnect the motor from the shaft to check the direction of rotation. If you remove the coupling, then you must adjust the shaft position
when you reinstall it. This must be done before starting the pump.
Arrows on the pump head show the correct direction of rotation. When seen from
the motor fan, the pump should rotate counterclockwise ( ). FPS QVNQ
NPUPST without a fan remove one of the coupling guards and look at the
coupling to determine the direction of
rotation. Turn off the pump and replace coupling guard. NOTICE : Do not
check the direction of rotation until the pump has been filled with liquid.
See “Priming”, at left
and above.
- Switch power
- Remove the coupling guard and rotate the pump shaft to be certain it can turn Replace the coupling guard.
- Verify that the electrical connections are in accordance with the wiring diagram on the
- If the fan is visible, turn on and off to verify
- 5P SFWFSTF UIF EJSFDUJPO PG SPUBUJPO, GJSTU TXJUDI 0FF
the power supply.
- On three-phase motors, switch 2 of the 3 power leads on the load side of the On single-phase motors, see the connection diagram on the motor
Priming
Plug
Drain Plug
Back off needle valve to vent air. Retighten to 25 in.-lbs. when vent
port runs a steady stream of water.
nameplate. Change the wiring as indicated.
Risk of electric shock. Can shock, burn or kill. Ground the pump motor
correctly before connecting to power supply per article 250-80 of National
Electrical Code (NEC) in the U.S., or the Canadian Electrical Code (CEC), as
applicable.
- Switch on the power supply and recheck the direction of motor
Troubleshooting
Risk of electrical shock and possible unexpected starts. Disconnect all power to the pump before servicing or working on pump. Make sure that power is locked out and that pump cannot be accidentally started.
Problem | Cause |
---|
1. Motor does not run when started
| A. Power failure
B. FVTFT CMPXO
C. Motor starter overload has tripped out
D. Main contacts in motor starter are not making contact or the coil is faulty
E. Control circuit fuses are defective
F. .PUPS JT EFGFDUJWF
2. Motor starter overload trips out immediately when power supply is switched on
| A. One fuse has blown
B. Contacts in motor overload relay are faulty
C. Cable connections are loose or faulty
D. Motor winding is defective
E. Pump mechanically blocked
F. 0WFSMPBE TFUUJOH JT UPP MPX
3. Motor starter overload trips out occasionally| A. Overload setting is too
low
B. Low voltage at peak times
4. Motor starter has not tripped out but the motor does not run| A. Check 1
A), B), D,) and E)
5. Pump capacity is not constant
| A. Pump inlet pressure is too low
B. Suction pipe/pump partly blocked
C. Pump is sucking air
6. Pump runs but gives no water
| A. Suction pipe/pump blocked
B. FPPU PS OPO-SFUVSO WBMWF JT CMPDLFE JO DMPTFE QPTJUJPO
C. Leakage in suction pipe
D. Air in suction pipe or pump
E. Motor rotates in the wrong direction
7. Pump runs backwards when switched off
| A. Leakage in suction pipe
B. FPPU PS OPO-SFUVSO WBMWF JT EFGFDUJWF
$. FPPU WBMWF JT CMPDLFE JO PQFO PS QBSUMZ PQFO QPTJUJPO
D. Non return valve leaks or is blocked in open or partly open position
E. Discharge valve is defective
8. Leakage from shaft seal| A. Pump shaft position is incorrect
B. Shaft seal is defective
9. Noise
| A. Cavitation is occurring in the pump
B. Pump does not rotate freely (That is, there is increased frictional
resistance) because of incorrect shaft position
WARRANTY
Seller warrants equipment (and its component parts) of its own manufacture
against defects in materials and workmanship under normal use and service for
one (1) year from the date of installation or start-up, or for eighteen (18)
months after the date of shipment, whichever occurs first. Seller does not
warrant accessories or components that are not manufactured by Seller;
however, to the extent possible, Seller agrees to assign to Buyer its rights
under the original manufacturer’s warranty, without recourse to Seller. Buyer
must give Seller notice in writing of any alleged defect covered by this
warranty (together with all identifying details, including the serial number,
the type of equipment, and the date of purchase) within thirty (30) days of
the discovery of such defect during the warranty period. No claim made more
than 30 days after the expiration of the warranty period shall be valid.
Guarantees of performance and warranties are based on the use of original
equipment manufactured (OEM) replacement parts. Seller assumes no
responsibility or liability if alterations, non-authorized design
modifications and/or non-OEM replacement parts are incorporated If requested
by Seller, any equipment (or its component parts) must be promptly returned to
Seller prior to any attempted repair, or sent to an authorized service station
designated by Seller, and Buyer shall prepay all shipping expenses. Seller
shall not be liable for any loss or damage to goods in transit, nor will any
warranty claim be valid unless the returned goods are received intact and
undamaged as a result of shipment. Repaired or replaced material returned to
customer will be shipped F.O.B., Seller’s factory. Seller will not give Buyer
credit for parts or equipment returned to Seller, and will not accept delivery
of any such parts or equipment, unless Buyer has obtained Seller’s approval in
writing. The warranty extends to repaired or replaced parts of Seller’s
manufacture for ninety (90) days or for the remainder of the original warranty
period applicable to the equipment or parts being repaired or replaced,
whichever is greater. This warranty applies to the repaired or replaced part
and is not extended to the product or any other component of the product being
repaired. Repair parts of its own manufacture sold after the original warranty
period are warranted for a period of one (1) year from shipment against
defects in materials and workmanship under normal use and service. This
warranty applies to the replacement part only and is not extended to the
product or any other component of the product being repaired. Seller may
substitute new equipment or improve part(s) of any equipment judged defective
without further liability. All repairs or services performed by Seller, which
are not covered by this warranty, will be charged in accordance with Seller’s
standard prices then in effect.
THIS WARRANTY IS THE SOLE WARRANTY OF SELLER AND SELLER HEREBY EXPRESSLY
DISCLAIMS AND BUYER WAIVES ALL OTHER WARRANTIES EXPRESSED, IMPLIED IN LAW OR
IMPLIED IN FACT, INCLUDING ANY WARRANTIES
OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. Seller’s sole
obligation under this warranty shall be, at its option, to repair or replace
any equipment (or its component parts) which has a defect covered by this
warranty, or to refund the purchase price of such equipment or part. Under the
terms of this warranty, Seller shall not be liable for (a) consequential,
collateral, special or liquidated losses or damages; (b) equipment conditions
caused by normal wear and tear, abnormal conditions of use, accident, neglect,
or misuse of said equipment; (c) the expense of, and loss or damage caused by,
repairs or alterations made by anyone other than the Seller; (d) damage caused
by abrasive materials, chemicals, scale deposits, corrosion, lightning,
improper voltage, mishandling, or other similar conditions; (e) any loss,
damage, or expense relating to or resulting from installation, removal or
reinstallation of equipment; (f) any labor costs or charges incurred in
repairing or replacing defective equipment or parts, including the cost of
reinstalling parts that are repaired or replaced by Seller; (g) any expense of
shipment of equipment or repaired or replacement parts; or (h) any other loss,
damage or expense of any nature.
The above warranty shall not apply to any equipment which may be separately
covered by any alternate or special warranties.
PERFORMANCE: In the absence of Certified Pump Performance Tests, equipment
performance is not warranted or guaranteed. Performance curves and other
information submitted to Buyer are approximate and no warranty or guarantee
shall be deemed to arise as a result of such submittal. All testing shall be
done in accordance with Seller’s standard policy under Hydraulic Institute
procedures.
LIABILITY LIMITATIONS: Under no circumstances shall the Seller have any
liability under the Order or otherwise for liquidated damages or for
collateral, consequential or special damages or for loss of profits, or for
actual losses or for loss of production or progress of construction,
regardless of the cause of such damages or losses. In any event, Seller’s
aggregate total liability under the Order or otherwise shall not exceed the
contract price.
ACTS OF GOD: Seller shall in no event be liable for delays in delivery of the
equipment or other failures to perform caused by fires, acts of God, strikes,
labor difficulties, acts of governmental or military authorities, delays in
transportation or procuring materials, or causes of any kind beyond Seller’s
control.
COMPLIANCE WITH LAW: Seller agrees to comply with all United States laws and
regulations applicable to the manufacturing of the subject equipment. Such
compliance shall include: The Fair Labor Standards Acts of 1938, as amended;
Equal Employment Opportunity clauses of Executive Order 11246, as amended;
Occupational Safety and Health Act of 1970 and the standards promulgated
thereunder, if applicable. Since compliance with the various Federal, State,
and Local laws and regulations concerning occupational health and safety,
pollution or local codes are affected by the use, installation and operation
of the equipment and other matters over which Seller has no control, Seller
assumes no responsibility for compliance with those laws and regulations,
whether by way of indemnity, warranty, or otherwise. It is incumbent upon the
Buyer to specify equipment which complies with local codes and ordinances.
Read More About This Manual & Download PDF:
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>