HALCYON R743 Square Low Glare Commercial Select 3K-4K Large Instruction Manual
- June 10, 2024
- HALCYON
Table of Contents
HALCYON R743 Square Low Glare Commercial Select 3K-4K Large
RISK OF FIRE – Required clearance from structural members and building elements Side Clearance to building element (eg timber, joist or Batten) (SCB): 50mm Height Clearance to building element (eg timber, joist or Batten) (HCB): 50mm
- Recessed Luminaire Classification: @700mA(CA 135)
- CA135 – building insulation that can safely be continuously exposed to 135°C allowed to abut the luminaire.
- Definition: Can abut the luminaire but NOT cover.
- RISK OF FIRE – Required clearance from structural members and building elements
- Side Clearance to building element (eg timber, joist or Batten) (SCB): 50mm
- Height Clearance to building element (eg timber, joist or Batten) (HCB): 50mm
- Recessed LuminaireClassification: @1050mA(NON IC)
- NON-IC -A luminaire shall under no circumstances be covered or abutted with building insulation.
- Definition: Building insulation must not cover or come into contact with any part of the luminaire. For indoor use only.
- If the external flexible cable or cord of this luminaire is damaged, it shall be exclusively replaced by the manufacturer or his service agent or a similar qualified person in order to avoid a hazard.
- The light source of this luminaire is not replaceable; when the light source reaches its end of life the whole luminaire shall be replaced
- This luminaire must be installed by a qualified Registered Electrician to prevent damage to the luminaire and maintain electrical safety.
- The light source of this luminaire is not replaceable; when the light source reaches its end of life the whole luminaire shall be replaced
- DO NOT INSTALL THROUGH JOIST, BEAM, RAFTER OR CEILING BATTEN
- Note: Side/Height Clearance is measured from Heat Sink
Installation instructions
CLASSIFICATION SHEET
- Manufacturer/ Supplier: Halcyon Lighting Ltd
- Product Code: R743
- Product Type: LED Recessed Luminaire
- Secondary Voltage: 700mA (CA135) or 1050mA (NON IC) Constant Current DC
- Wattage: 33W (@700mA) or48.5W (@1050mA)
- Ingress Protection Rating: IP54
DO NOT INSTALL THROUGH JOIST, BEAM, RAFTER OR CEILING BATTEN
R743@700mA
Classification
CA 135 – Building insulation that can safely be continuously exposed to 135°C allowed to abut the luminaire. Definition: Can abut the luminaire but NOT cover.
R7 43 @ 1050mA
- Classification NON IC – A luminaire shall under no circumstances be covered or abutted with building insulation.
- Caution: Recessed luminaires and their associated equipment may pose a risk of fire or damage to property if not installed and maintained correctly.
- Halcyon Non-IC rated luminaires are completely safe to install in sarked timber ceiling
- linings with a gauge of less than 20mm. Halcyon accepts no responsibility if the timber used is not treated correctly and dries out, crack or warps over time due to the constant low heat from the aforementioned “Non IC Rated” LED recessed lighting.
- This data sheet contains the information necessary to ensure compliance with New Zealand
- Electrical Code of Practice for Installation and Maintenance of Recessed Luminaires and Associated Equipment AS/NZS 60598.2.2:2001