HALCYON R951 LED Recessed Luminaire Instruction Manual
- June 10, 2024
- HALCYON
Table of Contents
R951 Installation
RISK OF FIRE — Required clearance from structural members and building
elements
R951 LED Recessed Luminaire
Side Clearance to building element (eg timber, joist or Batten) (SCB): 0mm
Height Clearance to building element (eg timber, joist or Batten) (HCB): 0mm
Minimum Insulation Clearance to building element (MIC): 0mm
Approved clearances
Note: 0mm required but 25mm always recommended for optimum product
lifespan through effective heat dissipation.
DO NOT INSTALL THROUGH JOIST, BEAM, RAFTER OR CEILING BATTEN
Note: Side/Height Clearance is measured from heat sink.
Recessed Luminaire Classification: IC-F — building insulation that can safely
be continuously exposed to 90°C allowed to abut and cover the luminaire.
For indoor use.
Luminaire must be installed by a Registered Electrician.
CONSTANT CURRENT WIRE IN SERIES.
-
Switch off mains power supply
-
These fittings have been designed to be installed at approximately 300mm above finished floor level, it is recom- mended to trial the install height to get the desired effect on the floor before cutting the holes. Cut out 70 x 35mm. Cut holes with extra caution (small rim). Cutting of holes prior to receiving goods is entirely at the risk of the installer.
-
Connect driver to mains voltage cable (L, N). Do not connect light to driver if driver is live. Inrush current from live driver will cause instant light failure. Do not switch secondary side.
Halcyon UID driver can be utilised and installed under insulation, driver install above one driver per R951 we of mini drivers are designed to fit through codes begin with DRDMACC, please refer to options. Halcyon UID are able to be if using a standard insulation.
NOTE: if using do have a range available that the cut out. Their DRMACC or our website for CHECK MINIMUM LOAD OF DRIVER.
CLASSIFICATION SHEET / IC-F
Manufacturer / Supplier | Halcyon Lighting Ltd |
---|---|
Product Code | R951 |
Product Type | LED Recessed Luminaire |
Secondary Voltage | 350mA Constant Current |
Wattage | 1.05W |
Ingress Protection Rating | IP40 |
Classification |
exposed to 90°C allowed to abut and cover the luminaire.
---|---|---
In the vicinity of the recessed luminaire, use an insulation product that:
(a) Maintains its dimensions and structural integrity when exposed to a
temperature of 90°C; and
(b) Withstands a 30-second needle flame test carried out in accordance with
AS/NZS 60695.11.5 with the flame applied to all surfaces of the sample
Rear of fitting may abut structural members and building elements.
Do not install through or directly into joist, beam, rafter or ceiling batten.
Side Clearance from heatsink to building element (e.g. timber, joist or
batten)| SCB: 0mm
---|---
Height Clearance from heatsink to building element (e.g. timber, joist or
batten)| HCB: 0mm
Minimum insulation clearance to building element| MIC: 0mm
Recessed luminaires and their associated equipment may pose a risk of fire or
damage to property if not installed and maintained correctly. Halcyon
recommends a clearance of 25mm to building elements for optimum lifespan.
Halcyon IC rated luminaires are completely safe to install in sarked timber
ceiling linings. Halcyon accepts no responsibility if the timber used is not
treated correctly and dries out, crack or warps over time due to the constant
low heat from the aforementioned 1C Rated” LED recessed lighting.
This data sheet contains information necessary to ensure compliance with the
New Zealand Electrical Code of Practice for Installation and Maintenance of
Recessed Luminaires and Associated Equipment AS/NZS 60598.2.2:2001
10 Basalt Place, East Tamaki, Auckland,
PO Box 58-501, Botany, Manukau 2163, Auckland, New Zealand Ph (0064 9)
273-9177
Fax (0064 9) 273 9155
Email: sales@halcyon.co.nz
Web: www.halcyonlights.co.nz