Autonics TCD220050AB DPU3 Series Single-Phase-3-Phase Digital Power Controllers Instruction Manual

June 10, 2024
Autonics

Autonics TCD220050AB DPU3 Series Single-Phase-3-Phase Digital Power

Controllers

Autonics-TCD220050AB-DPU3-Series-Single-Phase-3-Phase-Digital-Power-
Controllers-PRODUCT

Product Information

The Transparent Guide Single-Phase / 3-Phase Digital Power Controllers DPU1 / DPU3 Series are electronic devices designed to control power supply to machinery and equipment. These units are available in different models with varying rated current capacity and power supply options. The product also supports RS485 communication and remote display options. The device is equipped with fail-safe features that ensure safe operation of the machinery and equipment connected to it. The product is designed for industrial use and must be installed following the safety instructions provided in the manual.

Product Usage Instructions

Before using the DPU1 / DPU3 digital power controllers, read the user manual carefully and follow the safety instructions to ensure safe and reliable operation.

  1. Install the device on a panel and ground separately to prevent electric shock or fire.
  2. Connect the unit within the rated specifications to prevent fire or product damage.
  3. Use a dry cloth to clean the device and avoid using water or organic solvents which may cause electric shock or fire.
  4. Avoid exposing the device to flammable/explosive/corrosive gas, high humidity, direct sunlight, radiant heat, vibration, impact or salinity which may result in explosion or fire.
  5. Check the connections before wiring to avoid fire or product damage.
  6. Do not connect, repair, or inspect the unit while connected to a power source to avoid electric shock or fire.
  7. Do not disassemble or modify the unit to avoid electric shock or fire.
  8. Since leakage current still flows right after turning off the power or in the output OFF status, do not touch the load terminal to avoid electric shock or burn due to high temperature of the surface.

Follow the ordering information provided in the manual to select the specified model. Download the installation file and the manuals from the Autonics website. Use DAQMaster, the comprehensive device management program for Autonics’ products, to manage the device parameters and data.

Thank you for choosing our Autonics product. Read and understand the instruction manual and manual thoroughly before using the product. For your safety, read and follow the below safety considerations before using. For your safety, read and follow the considerations written in the instruction manual, other manuals and Autonics website. Keep this instruction manual in a place where you can find easily. The specifications, dimensions, etc. are subject to change without notice for product improvement. Some models may be discontinued without notice. Follow Autonics website for the latest information.

Safety Considerations

  • Observe all ‘Safety Considerations’ for safe and proper operation to avoid hazards.
  • symbol indicates caution due to special circumstances in which hazards may occur.

Warning Failure to follow instructions may result in serious injury or death.

  1. Fail-safe device must be installed when using the unit with machinery that may cause serious injury or substantial economic loss.(e.g. nuclear power control, medical equipment, ships, vehicles, railways, aircraft, combustion apparatus, safety equipment, crime/disaster prevention devices, etc.) Failure to follow this instruction may result in personal injury, economic loss or fire.
  2. Do not use the unit in the place where flammable/explosive/corrosive gas, high humidity, direct sunlight, radiant heat, vibration, impact or salinity may be present. Failure to follow this instruction may result in explosion or fire.
  3. Install on a device panel, and ground separately. Failure to follow this instruction may result in fire or electric shock.
  4. Do not connect, repair, or inspect the unit while connected to a power source. Failure to follow this instruction may result in fire or electric shock.
  5. Do not disassemble or modify the unit. Failure to follow this instruction may result in fire or electric shock.
  6. Check ‘Connections’ before wiring. Failure to follow this instruction may result in fire

Caution Failure to follow instructions may result in injury or product damage

  1. Use the unit within the rated specifications. Failure to follow this instruction may result in fire or product damage.
  2. Use a dry cloth to clean the unit, and do not use water or organic solvent. Failure to follow this instruction may result in fire or electric shock.
  3. Keep the product away from metal chip, dust, and wire residue which flow into the unit. Failure to follow this instruction may result in fire or product damage.
  4. Since leakage current still flows right after turning off the power or in the output OFF status, do not touch the load terminal. Failure to follow this instruction may result in electric shock.
  5. Since leakage current still flows right after turning off the power or in the output OFF status, do not touch the load terminal. Failure to follow this instruction may result in burn due to high temperature of the surface.

Cautions during Use

  • Follow instructions in ‘Cautions during Use’. Otherwise, it may cause unexpected accidents.

  • Use the product, after 3 sec of supplying power.

  • Before use, set the mode and function according to the specification. Since changing the mode / parameter during operation may result in malfunction, set the mode and function after disconnecting load output.

  • Re-supply the power to the unit after 3 sec of turning off the power. Failure to follow this instruction may result in malfunction.

  • To ensure the reliability of the product, install the product on the panel or metal surface vertically to the ground.

  • Install the unit in the well ventilated place.

  • While supplying power to the load or right after turning off the power of the load, do not touch the body and heat sink. Failure to follow this instruction may result in a burn due to the high temperature.

  • Install a power switch or circuit breaker in the easily accessible place for supplying or disconnecting the power.

  • Do not wire to terminals which are not used.

  • Use twisted pair wire for communication line.

  • Do not use near the equipment which generates strong magnetic force or high frequency noise.

  • Since inter element can be damaged when using with coil load, inductive load, etc.,
    the inrush current must be under the rated load current.

  • To prevent product malfunction due to noise, wire power, control input,
    communication, and load cables separately.

  • For stable operation, use shield wire for control, alarm, and communication wires.
    Use a ferrite core on the shield wire to cope with EMC.

  • This unit may be used in the following environments.

    • Indoors (in the environment condition rated in ‘Specifications’)
    • Altitude max. 2,000 m
    • Pollution degree 2
    • Installation category III

Ordering Information

This is only for reference, the actual product does not support all combinations. For selecting the specified model, follow the Autonics website.

Control phase

  • 1 : Single-phase
  • 3 : 3-phase

Power supply

  1. 110 VAC
  2. 220 VAC
  3. 380 VAC
  4. 440 VAC

Size (rated current capacity)

| DPU1| DPU3
---|---|---
A| 0 to 70 A| 0 to 50 A
B| 80 to 200 A| 70 to 200 A
C| 250 to 350 A
D| 400 to 600 A

Rated current capacity
Number: Rated current capacity (unit: A)

Option

  • R : RS485 communication
  • D : Remote display
  • A : Remote display + RS485 communication
  • N : None

Product Components

  • Product
  • Bolt × 4
  • Instruction manual
  • Terminal × 1

Software

Download the installation file and the manuals from the Autonics website.

DAQMaster
It is the comprehensive device management program for Autonics’ products, providing parameter setting, monitoring and data management

Manual
For proper use of the product, refer to the manuals and be sure to follow the safety considerations in the manuals. Download the manuals from the Autonics website

Display

Indicator

Indicator Color Descriptions

R / S / T

|

Green

| [DPU3 model]

Turns ON by display value of display part E.g.) R, S ON → R-S line voltage display

RUN| Green| Turns ON for RUN, turns OFF of STOP
AUTO| Green| Turns ON for AUTO, turns OFF of MANUAL
EVT| Red| Turns ON for Digital input ON, flashes for alarm output ON

Display part (red)

  • RUN mode : Displays depending the front display setting
  • Setting mode : Displays parameter and setting value
  • Unit indicator
Indicator Descriptions
V Turns ON for voltage display
A Turns ON for current display

V + A

| Turns ON for power display,

turns OFF for resistance and input value display

Output BAR (green)
Turns on the current output (voltage / current / power) in a ratio of 0 to 100 % relative to the input.

Setting keys

Key Descriptions
  [MODE] To enter monitoring / operation setting 1, 2 mode and to move

between parameters
[▲ / ▼]| To move setting modes and to set parameters.
  [RET]| To return to RUN mode from monitoring / operation setting 1, 2 / alarm setting mode

Unit Descriptions

Configurations may vary by model depending on supported specifications.

DPU1 Series

Autonics-TCD220050AB-DPU3-Series-Single-Phase-3-Phase-Digital-Power-
Controllers-FIG-2

DPU3 Series

Autonics-TCD220050AB-DPU3-Series-Single-Phase-3-Phase-Digital-Power-
Controllers-FIG-3

  1. Mounting holes
  2. Display
  3. Case screw
  4. Cooling fan 01)
  5. Heatsink
  6. Load wiring input hole
  7. Load wiring output hole
  8. Ground wiring hole
  9. Internal adjuster
  10. AUTO / MANUAL select switch
  11. Control input (voltage / current) connector
  12. Control input (contact) / RS485 communication connector
  13. DPU1: alarm output connector
  14. DPU3 : control power (FAN) / alarm output connector

DPU1 Series 25 / 40 / 50 A models do not have attached a Fan.

Specifications

Series DPU1 DPU3
Control phase Single-phase 3-phase
Rated frequency 50 / 60 Hz (auto recognition), allowable frequency range: ± 2

Hz
Display method| 4 digit 7 segment, Output BAR

Indicators

| Operation / manual control indicator

(green)

DI, alarm / unit (V, A) indicator (red)

| R, S, T indicator (green)

Operation / manual control indicator

(green)

DI, alarm / unit (V, A) indicator (red)

Auto control input

| • Current 01): 4 – 20 mA, 0 – 20 mA

• Voltage 02): 0 – 5 VDCᜡ, 1 – 5 VDCᜡ, 0 – 10 VDCᜡ

• Contact (non-voltage): ON / OFF

• Contact (voltage): 0 / 12 VDCᜡ (24 VDCᜡ)

• Communication: RS485

Manual control input| Internal adjuster (10 kΩ), external adjuster (3 to 10 kΩ, ≥ 2 W)
Digital input (DI)| AUTO / MAN selectable, RUN / STOP selectable, RESET, HOLD, Setting Point 1 to 6
Display content| Control input, load voltage, load current, load power, load resistance, power

supply frequency

Min. display output| Min. 2.5 % of rated voltage / current
Approval| ᜢ, ᜧ, ᜫ
SCCR Rating| 80 kA (UL certification)

  1. Input impedance = 100 Ω
  2. Input impedance = 25 Ω
Control method Phase control Cycle control ON / OFF control

Control mode

| Normal /

constant current feedback / constant voltage feedback / constant power feedback

|

Fixed cycle /

variable cycle 01)

|

Applied load| Resistance / inductive load| Resistance load| Resistance load
Output range| 0 to 98 %| 0 to 100 %| 0 to 100 %

Output accuracy of phase control

| • Normal : Within ± 10 % F.S. of rated load voltage

• Constant current feedback: Within ± 3 % F.S. of rated load current

(within variable 1 to 10 times of rated resistance)

• Constant voltage feedback: Within ± 3 % F.S. of rated load voltage

(within variable ± 10 % F.S. of rated voltage)

• Constant power feedback: Within ± 3 % F.S. of rated load power

(within variable ±10% F.S. of rated power and within variable 1 to 10 times of rated resistance)

DPU1 only

Series DPU1 DPU3

Power supply

|

110 / 220 / 380 / 440 VACᜠ model

| 110 / 220 / 380 / 440 VACᜠ model

(fan and control power 220 VACᜠ 50 / 60 Hz separately)

Allowable voltage range| 90 to 110 % of power supply| 85 to 115 % of power supply
Min. load current| 1 A
Power consumption| ≤ 40 W (control power)| ≤ 60 W (control power)
Insulation resistance| ≥ 200 MΩ (500 VDCᜡ megger)
Dielectric strength| Between input terminal and power terminal: 2000 VACᜠ 50 / 60 Hz for 1 min
Vibration| 0.75 mm double amplitude at frequency of 5 to 55 Hz (for 1 min) in each X, Y, Z

direction for 2 hours

Noise immunity| ±2 kV square wave noise (pulse width: 1 ㎲) by the noise simulator
Ambient temp.| -10 to 50 ℃, storage: -20 to 80 ℃ (no freezing or condensation)
Ambient humidity| 5 to 90 %RH, storage: 5 to 90 %RH (no freezing or condensation)
Unit weight (packaged)| DPU1| DPU3
---|---|---
A| ≈ 3.0 kg (≈ 3.2 kg)| ≈ 6.5 kg (≈ 7.6 kg)
B| ≈ 3.0 kg (≈ 5.6 kg)| ≈ 11.5 kg (≈ 13.0 kg)
C| ≈ 11.0 kg (≈ 12.1 kg)| ≈ 20.0 kg (≈ 21.1 kg)
D| ≈ 11.0 kg (≈ 19.3 kg)| ≈ 30.8 kg (≈ 35.7 kg)

Communication Interface

RS485

Comm. protocol Modbus RTU
Application standard Compliance with EIA RS485
Max. connection 31-unit (address: 01 to 64)
Comm. synchronous method Asynchronous
Comm. method 2-wire half duplex
Comm. distance ≤ 800 m
Comm. speed 4,800 / 9,600 / 19,200 / 38,400 (default) bps
Comm. response time 5 to 99 ms
Data bit 8-bit (fixed)
Parity bit Even (fixed)
Stop bit 1-bit (fixed)

Initial Display When Power is ON

  • When power is supplied, after all display will flash for 1 sec, device version > rated voltage > rated current are displayed sequentially. After this, enter into RUN mode.
  • Example of DPU 2A-050 model,

| 1. Display part| 2. Device version| 3. Rated voltage| 4. Rated current| 5. RUN mode
---|---|---|---|---|---
DPU1| )))0| DP20| 220| 50| 10)3
DPU3| )))0| DP30| 220| 50| 10)3

Alarm

  • Parameter setting is available to set alarm delay time, alarm channel, etc.
  • For details on parameter setting, refer to the product manual
Alarm Display Operation Alarm release 01)
Overcurrent O-C

Stop (SCR OFF)

|

• Re-supply power.

• Press [RET]. 02)

• Switch to STOP mode

Overvoltage| O-V

Fuse break 03)

|

FUSE

| • DPU1: Stop (SCR OFF)

• DPU3: when 1-phase break, it maintains output when 2-phase break, it stops output.

Heatsink over

heat

|

TEMP

|

Stop (SCR OFF)

SCR error 03)| SCR
Heater break|

H-BK

| Continues operation| Automatically released within the setting range

  1. If the alarm occurrence condition is not removed, the alarm is re-occur even if the alarm release method is applied.
  2. The power is reapplied.
  3. If the alarm is not released after power is applied again, replace the fuse or check whether the SCR element is abnormal.

Replacement of Fuse

  • To prevent accident, replace a fuse every two years.
  • Must turn off the power before removing the fuse.
  • If using a fuse not supplied by Autonics, the performance of the product is not guaranteed. When replacing the fuse, use a fuse of the recommended specification.

Fuse position
After loosening the case screws, there is a fuse on the side of the product.

[DPU1]

Autonics-TCD220050AB-DPU3-Series-Single-Phase-3-Phase-Digital-Power-
Controllers-FIG-4

Among R, S, T inputs, R and S have a built-in fuse, but T does not have an internal fuse. If a fuse is required, install a fuse of the following or equivalent performance outside the product separately.

Device

size

| Fuse fixed bolt
---|---
DPU1| DPU3
A| M5| M6
B| M8
C| M8
D| M12

Fuse recommended specifications
Rated short circuit test is evaluated as a recommended fuse

Rated load current [A]| DPU1| | DPU3|
---|---|---|---|---
Rec. fuse| Manufacturer| Rec. fuse| Manufacturer
25| 50FE| | 50FE|
40| 63ET| | 63ET|
| | BUSSMANN| |
50| 80ET| | 80ET|
70| 100FE| | 170M1367|
80| 660GH-125| | 170M1368|
100| 660GH-160| | 170M1369|
120| 660GH-160| | 170M1369|
| | HINODE|
150| 660GH-200| | 170M1370| BUSSMANN
180| 660GH-250| | 170M1370|
200| 660GH-250| | 170M1372|
250| 170M2620| | 170M2620|
| | BUSSMANN|
350| 170M2621| | 170M2621|
400| A60X500-4(TA)| | 170M3471|
500| A60X600-4(TA)| MERSEN| 170M4466|
600| A60X600-4(TA)| | 170M4466|

Connections
Terminal configuration by model may differ depending on the supported spec.

DPU1 Series

Autonics-TCD220050AB-DPU3-Series-Single-Phase-3-Phase-Digital-Power-
Controllers-FIG-5

DPU3 Series

Autonics-TCD220050AB-DPU3-Series-Single-Phase-3-Phase-Digital-Power-
Controllers-FIG-6

Suitable specification
The following connectors can be used with equivalent or substitute

| Connector configuration|
---|---|---
Connector type| | | Manufacturer
| DPU1| DPU3|
Control input (current, voltage)| TS 05 515B| TS 05 515B|
Alarm output /

control power (DPU3)

| TS 04 515B| TS 06 515B|

ANYTEK

Control input (contact) / RS485 communication| TS 09 515B| TS 09 515B|

Cautions during Wiring

  • DI input switch: For low current, ON resistance: 20Ω or less (including wiring resistance).
  • Do not arbitrarily replace the display – main body connector of the remote display model.
  • For crimp terminals of load input/output connectors, use the following UL approved terminals. Be sure to use crimp terminals with an insulating sleeve (tube).

Device size| DPU1/3 wire thickness| Crimp terminal spec.| Bolt tightening torque
---|---|---|---
A| ≥ 25 mm2| 25-S6 (1)| 5.6 to 6.0 Nm
B| ≥ 95 mm2| 95-8 (1)| 13.6 to 14.5 Nm
C| ≥ 2 × 70 mm2| 70-8 (2)| 13.6 to 14.5 Nm
D| ≥ 2 × 185 mm2| 185-12 (2)| 47.0 to 50.0 Nm

Cautions during Installation

High Temperature Caution
While supplying power to the load or right after turning off the power of the load, do not touch the body and heatsink. Failure to follow this instruction may result in a burn due to the high temperature

Mount space
When installing multiple power controllers, keep space between power controllers for heat radiation.

  • Horizontal : ≥ 80 mm
  • vertical : ≥ 100 mm

Dimensions

Unit : mm, For the detailed drawings, follow the Autonics website.

DPU1 Series
The figure is based on the B size.

Autonics-TCD220050AB-DPU3-Series-Single-Phase-3-Phase-Digital-Power-
Controllers-FIG-9

Size d R W1 W2 H1 H2 H3 H4 H5 w1 w2 h1 h2 h3 h4
A 6 135° 82 97 40 150 233 01) 230 3 154 80 90 110 170.3 209.5
B 6 135° 127 140 50 150 283 250 3 222 120 101.5 121.5 174 241.5
C 7 160° 193 213 50 200 342 300 4 368 185.6 131 132 179 244
D 7 160° 261 278 40 200 422 380 4 497 252.7 138 156 212 296

Rated current capacity 70 A model: 263

DPU3 Series
The figure is based on the C size

Autonics-TCD220050AB-DPU3-Series-Single-Phase-3-Phase-Digital-Power-
Controllers-FIG-10

Size d W1 W2 H1 H2 H3 H4 H5 H6 H7 H8 H9
A 6 127 140 63.5 150 309 H4 + H5 = 29 H6 + H7 + H8 = 277
B 7 195 213 40 200 367 3.5 40 280 40
C 7 261 278 40 200 457 3.3 40 45 280 45 40
D 8.5 405 427 66.5 330 536 4 32.5 H6 + H7 + H8 + H9 = 495.5
Size R w1 w2 h1 h2 h3 h4
--- --- --- --- --- --- --- ---
A 160° 244 122.6 138 200 239 116
B 160° 366 185.6 176 217 278 126
C 160° 497 252.6 173 227.5 311 125
D 160° 755 385.6 204.5 275.5 405 204.5

Remote display
Unit

Autonics-TCD220050AB-DPU3-Series-Single-Phase-3-Phase-Digital-Power-
Controllers-FIG-11

Mode Setting

Autonics-TCD220050AB-DPU3-Series-Single-Phase-3-Phase-Digital-Power-
Controllers-FIG-12

18, Bansong-ro 513Beon-gil, Haeundae-gu, Busan, Republic of Korea, 48002 www.autonics.com | +82-2-2048-1577 | sales@autonics.com

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Autonics User Manuals

Related Manuals