HALCYON R602 LED Recessed Luminaire Instruction Manual
- June 10, 2024
- HALCYON
Table of Contents
HALCYON R602 LED Recessed Luminaire
Installation Directions
- Switch off the mains power supply
- Connect Dimmable Driver to the mains voltage cable (L, N) Do not connect the downlight to the driver if the driver is live. Inrush current from the live driver will cause instant downlight failure. Do not switch the secondary side.
- Carefully install downlight into Precut 130-140mm hole.
- Turn on the mains power and switch on the lighting circuit.
Approved Clearances
Note: 0mm is required but 25mm is always recommended for optimum product lifespan through effective heat dissipation.
Example 1
0mm Approved Height Clearance. Building element abutting rear, insulation
abutting sides of fitting.
Example 2
0mm Approved Side Clearance. Building element abutting side of fitting,
insulation abutting and covering fitting.
Driver is designed to be covered and abutted with IC / IC-F / IC-4 approved insulation.
Cutting of holes prior to receiving goods is entirely at the risk of the
installer.
10 Basalt Place, East Tamaki, Auckland, PO Box 58-501, Botany, Manukau 2163,
Auckland, New Zealand Ph (0064 9) 273-9177 Fax (0064 9) 273 9155 Email:
sales@halcyon.co.nz Web:
www.halcyonlights.co.nz
CLASSIFICATION SHEET
- Manufacturer I Supplier: Halcyon Lighting Ltd
- Product Code: R602 W3K / R602 83K R602 W3KHO / R602 W4KHO
- Product Type: LED Recessed Luminaire
- Primary Voltage: 220-240V~50/60Hz
- Secondary Voltage: 260mA 36VDC Constant Current 500mA 36VDC Constant Current
- Wattage: 12W 20W
- Ingress Protection Rating: IP54
Classification
- IC-F – building insulation that can safely be continuously exposed to 90°C allowed to abut and cover the luminaire.
- IC-4 – building insulation that can safely be M continuously exposed to 90°C allowed to abut and cover the luminaire.
In the vicinity of the recessed luminaire, use an insulation product that:
- Maintains its dimensions and structural integrity when exposed to a temperature of 90°C; and
- Withstands a 30-second needle flame test carried out in accordance with AS/NZS 60695.11.5 with the flame applied to all surfaces of the sample.
Rear of fitting may abut structural members and building elements.
Do not install through or directly into joist, beam, rafter or ceiling batten.
- Recessed luminaires and their associated equipment may pose a risk of fire or damage to property if not installed and maintained correctly. Halcyon recommends a clearance of 25mm to building elements for optimum lifespan.
- Halcyon IC-F-rated luminaires are completely safe to install in sarked timber ceiling linings. Halcyon accepts no responsibility if the timber used is not treated correctly and dries out, crack or warps over time due to the constant low heat from the aforementioned “IC-F Rated” LED recessed lighting.
- This data sheet contains the information necessary to ensure compliance with the New Zealand Electrical Code of Practice for Installation and Maintenance of Recessed Luminaires and Associated Equipment AS/NZS 60598.2.2:2001