MITSUBISHI HEAVY INDUSTRIES THERMAL SYSTEMS RM-CGW-E1 M-Access Gateway Installation Guide
- June 10, 2024
- MITSUBISHI HEAVY INDUSTRIES THERMAL SYSTEMS
Table of Contents
Installation Manual for M-ACCESS Gateway RM-CGW-E1
PSZ012D051
202204
RM-CGW-E1 M-Access Gateway
- This installation manual describes installation procedure and precautions for the gateway.
- Please also refer to the indoor unit’s manual, outdoor unit’s manual and other supplied manuals.
- For proper gateway installation, please read this manual carefully before starting installation work.
- The gateway must be installed in accordance with national wiring regulations.
- The gateway is precision equipment, so please handle it with enough care to prevent damage due to falling and being stepped on.
- For other languages, download from Web site.
https://www.mhi-mth.co.jp/en/products/detail/air- conditioner_users_manual.html
Safety Precautions
-
Before starting the installation work, please read these “Safety Precautions” and follow them properly. All of the following are important and must be observed strictly.
WARNING: Failure to follow these instructions properly may result in serious consequences such as death and severe injury.
CAUTION: Failure to follow these instructions properly may cause injury or property damage. There could be serious consequences depending on the circumstances. -
The following pictograms are used in the text.
Never do.| Always follow the instructions given.
---|--- -
After the installation, please make a test run and confirm no abnormalities occur during the test run.
-
Please explain the operation method to the customers according to the user’s manual and product specifications.
-
Keep this manual in a safe place where users can consult it whenever needed. Show this manual to installers when moving or repairing the gateway. When the ownership of the gateway is transferred, this manual should be given to the new owner.
WARNING
-
Consult your dealer or a professional contractor to install the gateway.
Improper installation done on your own may cause electric shock, fire or breakdown. -
Installation work should be performed properly according to this installation manual.
Improper installation work may result in electric shock, fire or breakdown. -
Be sure to use accessories and specified parts for installation work.
Use of unspecified parts may result in falls, fire or electric shock. -
Choose an installation location inside a locked enclosure.
Otherwise, electric shock or incorrect operation may result. -
The electrical work should be performed by a qualified electrical engineer, according to electrical standards, local electrical safety regulations and wiring specifications.
Incomplete installation work may cause electric shock or fire. -
Turn off the power supply before starting electrical work or repairing/inspecting the gateway.
Otherwise, electric shock, injury, breakdown or malfunction may result. -
When wiring, ensure solid connections and fasten specified cables securely so that terminal connections may not be subject to external forces from cables.
Incomplete connection or improper connection of terminal wiring may cause electric shock or fire. -
Do not modify the gateway.
Otherwise, electric shock, fire or breakdown may result. -
Do not install the gateway in a special environment or where inflammable gas could generate, flow in, accumulate or leak.
If the gateway is used in places where air contains dense oil mist, steam, organic solvent vapor, corrosive gas ammonia, sulfuric compounds, acid, etc.) or where acidic or alkaline solutions, special sprays, etc., are used, electric shock, breakdown, smoke or fire may result due to corrosion or significant deterioration of the performance. -
Do not install the gateway where excessive water vapor is generated or condensation occurs.
Otherwise, electric shock, fire or breakdown may result. -
Do not use the gateway in a place where it can get wet, such as a laundry room.
Otherwise, electric shock, fire or breakdown may result. -
Do not operate the gateway with wet hands.
Otherwise, electric shock may result. -
Do not wash the gateway with water.
Otherwise, electric shock, fire or breakdown may result. -
This appliance is not intended for use by persons (including children) with reduced physical, sensory ormental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. Children should be supervised to ensure that they do not play with the appliance.
If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or similarly qualified persons in order to avoid a hazard. -
Cleaning and user maintenance shall not be made by children without supervision.
CAUTION
-
Please perform grounding work.
Please do not connect the ground wire to gas pipes, water pipes, a lightning rod or a telephone ground wire.
Incomplete grounding work may cause electric shock or fire if electric leakage or breakdown occurs. -
Be sure to install a leakage breaker at the installation location.
If a leakage breaker is not installed, electric shock may result. -
The primary and secondary wires must be reinforced insulated.
Keep the wires at least 5 mm apart or add a protective tube to the wires. -
Make sure to remove static electricity before connecting terminals.
Use an antistatic wristband or touch the metal part on the back of the device to remove static electricity from your body before connecting the terminals.
If static electricity removal is incomplete, it may cause a malfunction. -
Do not install the gateway in the following places.
(1) Damage to or breakdown or malfunction of the gateway may result.-
Where it is exposed to direct sunlight
-
Where the ambient temperature becomes 0 °C or below, or 40 °C or above
-
Where the surface is not flat
-
Where the soundness of the installation area is insufficient
-
Where dust tends to accumulate, such as on the floor
(2) Abnormality in the control system or abnormal operation may result. -
Where machinery generates radio waves.
-
Accessories
Gateway main unit, Installation manual, round-type crimp-style terminals (Large: 2, Small: 4), termination resistors (2)
Installation Work
Installation location
The installation location should be a cool place indoors with enough cooling air circulation.
Parts procured on site
Before installing the gateway, prepare the following parts.
– Main body installation screws (M4) ×4
– Wiring (Refer to “4. Wiring”.)
– Leakage breaker (Cut-off device with a contact gap of 3 mm or more according
to overvoltage category III)
Installation procedure
Install the gateway in the orientation shown in the figure below and so that
letters can be read correctly.
Any other orientation may cause cooling failure of internal parts that may
result in a malfunction or breakdown.
Installation clearances
For cooling and service work, provide the following clearances above and below
and to the right and left.
Bottom clearance Min. 100 mm (Recommended length of 200 mm or more)・・・Space
for wiring and service
Top clearance
Left clearance
Right clearance| Min. 30 mm
Min. 30 mm
Min. 30 mm| Space for cooling
---|---|---
Precautions for installation locations
- When using wireless LAN, communication may not be possible if the product is surrounded by metal, or if the product is installed near an object that does not allow radio waves to pass through, such as metal or reinforced concrete.
- Communication may not be possible if this product is placed near a device that emits radio waves such as a microwave oven. Install this product as far away from such devices as possible.
Wiring
-
Use the supplied round-type crimp-style terminals (large) when connecting wires to the power supply terminal block.
-
Do not use any supply cord lighter than one specified in below.
- Ordinary tough rubber sheathed cord (code designation 60245 IEC 53)
-
Do not turn on the power supply (power switch) until all of the work is completed.
-
Wait at least two minutes after the indoor and outdoor units are turned on before turning on the power supply.
-
Except for the accessories, all of the components are obtained at the site.
-
Before connecting the wires, remove the cover of the terminal block.
After the work is completed, return the cover of the terminal block to its original position.
The cover is used to prevent electric shock from accidental contact. -
Perform grounding work. Wire the ground for the power supply to Grounding point ①, shown in the diagram for “3.4 Installation clearances”.
-
Use the Wiring clamp beside the power LED to fasten the wires connected to the power supply terminal block.
-
When pulling out wires from the enclosure, secure or cover the wires with conduit to prevent tension from being applied to the terminals.
Superlink signal line
Shielded wire (MVVS 2 core) 0.75 mm 2 – 1.25 mm 2
Max. 1000 m per line (Max. distance: 1000 m, Total wire length: 1000 m)
Wire the ground for the Superlink system to Grounding point ②, shown in the
diagram for “3.4 Installation clearances”.
(Note 1) When the gateway is used, use a shielded wire as the Superlink signal
wire. Ground both ends of the shielded wire. Wire the ground of the gateway to
Grounding point ②, shown in the diagram for “3.4 Installation clearances”.
(Note 2) If the indoor and outdoor units connected to the network are all
compatible with the new Superlink, a total wire length of 1500 m per line is
possible (maximum distance: 1000 m). However, be sure to use wire with a
diameter of 0.75 mm 2 if the total wire length exceeds 1000 m. For further
information, please contact your sales representative or dealer.
(Note 3) Be sure to use the supplied round-type crimp-style terminals (small)
when connecting wires to the terminal block.
Remote terminal board communication wire
Shielded wire (MVVS 2 core) 0.75 mm 2 – 1.25 mm 2
Max. 1000 m per line (Max. distance: 1000 m, Total wire length: 1000 m)
Wire the ground for the remote terminal board communication wire to Grounding
point ② in the diagram for “3.4
Installation clearances”.
(Note 1) When the gateway is used, use a shielded wire as the remote terminal
board communication wire. Wire the ground of the gateway to Grounding point ②
shown in the diagram for “3.4 Installation clearances”.
(Note 2) Be sure to use the supplied round-type crimp-style terminals (small)
when connecting wires to the terminal block.
Remote control operation prohibition input wiring
0.75 mm 2 – 1.25 mm 2
For safety reasons, use the round-type crimp-style terminals with insulated
sleeves for connecting all wires to terminal blocks.
Install an external switch that prohibits remote operation so that the user
can block remote control in an emergency.
LAN cable
10BASE-T or 100BASE-TX compatible products
Wire as shown below.
-
Upper tier of terminal block
*1 When connecting a CO2 heat pump water heater/refrigerator, connect the remote terminal board communication wire.
For the connection method, refer to “Connecting the remote terminal board communication wire” described later. -
Lower tier of terminal block
*2 Connect to a router or an existing network.
For the detailed connection method and settings, refer to the installation manual.
Connecting the remote terminal board communication wire
Perform the electrical wiring work according to the wiring diagram below.
- For safety reasons, use the round-type crimp-style terminals with insulated sleeves for connecting all wires to the main unit.
- Do not connect the ground wire with gas pipes, water pipes, a lightning rod, or a telephone ground wire.
- Do not turn on the power until all work is completed.
(Note 1) Communication wire ⑥ has polarity. Correctly connect A1(+), B1(-),
A2(+), and B2(-) of Gateway ① with the + and – polarities of the remote
terminal PWB ④ as shown in the above diagram.
Use the supplied Round-type crimp-style terminal (S) for connecting the
Communication wire ⑥ to the Gateway ①.
Use the equivalent of N1.25-4 (RAP1.25-4: Made by JST Mfg. Co., Ltd.) for
connecting the Communication wire ⑥ to the Remote terminal PWB ④.
Regarding the round-type crimp-style terminal for the shield ground, use M3 on
the Gateway ① and M5 on the Remote terminal PWB ④.
Be sure to tighten the termination resistors attached to the place where the
communication wire ⑥ is connected to the Gateway ①.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>