RLE TH140 Temperature And Humidity Sensor Installation Guide
- June 10, 2024
- RLE
Table of Contents
- FMS to TH140/TH140D Integration
- FMS to T120D Integration
- FMS to HEW3MSTA Integration
- CT120/CT300/CT800/CT2400 FMS Integration
- PFM FMS Integration
- GD100 FMS Integration
- AFS-(WM/DM) F200 Integration
- AFS-D FMS Integration
- MD3 FMS Integration
- SMK FMS Integration
- HD150 & HD150-2 FMS Integration
- KPO Falcon Integration
- FMS BAPI Temperature/Humidity Falcon Integration
- FMS HW2XA2A Temperature/Humidity Integration
- FMS Dwyer Temperature/Humidity Falcon Integration
- FMS WIRED-TH Temperature/Humidity Integration
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
RLE TH140 Temperature And Humidity Sensor Installation Guide
FMS to TH140/TH140D Integration
Figure 1.1: FMS Wiring with the TH140/TH140D
SETUP
- Set the switch position to mA. Set the temperature range to 50-95 or 32-122. The Sensor is shipped from the factory with the switch in the volts position and the temperature range is set for 50-95F. The switch position must be set to the mA position.
- Wire the sensor as shown
- Configure the Falcon Input channel (temperature) for “Analog 4-20mA” and enter the Gain and Offset values. For the 50-95F range use Gain 11.25, Offset 38.75. For 32-122F range use Gain 22, Offset 10
- Configure the Falcon Input Channel (humidity) for “Analog 4- 20mA” and enter the Gain of 25 and Offset of -25
- . Verify the “Calc” Value displays the correct room temperature. The temperature can also be viewed on the Falcon main page
Figure 1.2: Temperature Setup 50 – 95 Degree F Range
Figure 1.3: Humidity Setup
TROUBLESHOOTING
-
Calculate the TH140 Output current for temperature Formula for calculating the correct RAW value ( (Actual temp – Sensor Low) / (Sensor High – Sensor Low)) x 16 + 4 Example if Room Temp is 70F and your sensor has a range of 50-95 (70 – 50) / (95 – 50)) x 16 + 4 = 11.11
-
. Measure the current flowing into the Falcon Ch- terminal with a current meter. Verify that it is close to the calculated current (+/-1%)
-
If measured current current does not match calculated current then check wiring and check TH140/TH140D jumper and switch settings.
-
. Compare the measured current matches the current reading in the Falcon. 5.
-
Check the wiring if the Falcon current reading does not match
the measured current reading. -
If the Falcon current reading matches the measured current and the Falcon calculated value does not match the room temperature then the offset and gain values are wrong. Double check the Gain and Offset values
-
If the temperature displayed in the Falcon is 1 or 2 degrees above or below the room temperature then adjust the offset by 1 or 2. Do not adjust the gain. Only tweak the offset once the previous troubleshooting steps have been performed.
-
If the Falcon still does not display the correct temperature contact RLE Technologies technical support at 970.484.6510.
-
Use similar troubleshooting procedure except use the following formula to calculate the humidity mA output
FMS to T120D Integration
Figure 2.1 : FMS Wiring with the T120D
SETUP
- Set the switch position to mA. Set the temperature range to 50-95 or 32-122. The sensor is shipped from the factory with the switch in the volts position and the temperature range is set for 50-95F. The switch position must be set to the mA position
- Wire the sensor to the CH # being used
- Configure the Falcon Input channel (temperature) for “Analog 4-20mA” and enter the Gain and offset values. For the 50-95F range use Gain 11.25, Offset 38.75. For 32-122F range use Gain 22, Offset 10.
- . Verify the “Calc” value displays the correct room temperature. The temperature can also be viewed on the Falcon main page.
Figure 2.2: 50-95F Range Setup
Figure 2.3: 32-122F Range Setup
TROUBLESHOOTING
-
Calculate the T120D Output current for temperature Formula for calculating the correct RAW value ( (Actual temp – Sensor Low) / (Sensor High – Sensor Low)) x 16 + 4 Example if Room Temp is 70F and your sensor has a range of 50-95 (70 – 50) / (95 – 50)) x 16 + 4 = 11.11
-
Measure the current flowing into the Falcon Ch- terminal with a current meter. Verify that it is close to the calculated current (+/- 1%)
-
If measured current does not match calculated current then check wiring and check T120D jumper and switch settings.
-
Compare the measured current matches the current reading in the Falcon.
-
Check the wiring if the Falcon current reading does not match
the measured current reading. -
If the Falcon current reading matches the measured current and the Falcon Calculated value does not match the room temperature then the offset and gain values are wrong. Double check the Gain and Offset values.
-
If the temperature displayed in the Falcon is 1 or 2 degrees above or below the room temperature then adjust the offset by 1 or 2. Do not adjust the gain. Only tweak the offset once the previous troubleshooting steps have been performed.
-
If the Falcon still does not display the correct temperature contact RLE Technologies technical support at 970.484.6510.
FMS to HEW3MSTA Integration
Figure 3.1: FMS Wiring with the HEW3MSTA
SETUP
- The temperature range is 50-95 degF
- Wire the sensor as shown. Orange wires are polarity independent
- Configure the Falcon Input channel (temperature) for “Analog 4-20mA” and enter the Gain and Offset values. For the 50-95F range use Gain 11.25, Offset 38.75
- Verify the “Calc” Value displays the correct room temperature. The temperature can also be viewed on the Falcon main page
Figure 4.2: Temperature Setup 50 – 95 Degree F Range
- Calculate the output current for temperature Formula for calculating the correct RAW value ( (Actual temp – Sensor Low) / (Sensor High – Sensor Low)) x 16 + 4 Example if Room Temp is 70F and your sensor has a range of 50-95 ( (70 – 50) / (95 – 50)) x 16 + 4 = 11.11
- Measure the current flowing into the Falcon Ch- terminal with a current meter. Verify that it is close to the calculated current (+/-1%)
- If measured current current does not match calculated current then check wiring.
- Compare the measured current matches the current reading in the Falcon
- Check the wiring if the Falcon current reading does not match the measured current reading
- If the Falcon current reading matches the measured current and the Falcon calculated value does not match the room temperature then the offset and gain values are wrong. Double check the Gain and Offset values.
- If the temperature displayed in the Falcon is 1 or 2 degrees above or below the room temperature then adjust the offset by 1 or 2. Do not adjust the gain. Only tweak the offset once the previous troubleshooting steps have been performed
- f the Falcon still does not display the correct temperature contact RLE Technologies technical support at 970.484.6510.
CT120/CT300/CT800/CT2400 FMS Integration
Figure 5.1: FMS Wiring
Figure 5.2: FMS Input Configuration Interface
FMS Configuration
- Set Input Type to an Analog 4-20 mA Input.
- For a 0-100 Amp setting, use a gain of 25 and an offset of -25.
- For other settings, use the integrated gain/offset calculator.
PFM FMS Integration
Figure 6.1: FMS Wiring
FMS Input Configuration Interface
FMS Configuration
Set Input Type to a Digital NO Input type for each PFM Relay Output wired into the Falcon.
GD100 FMS Integration
Figure 7.1: FMS Wiring
**FMS Input Configuration Interface
**
FMS Configuration
Set Input Type to a Digital NO
AFS-(WM/DM) F200 Integration
Figure 8.1: FMS Wiring
- Set Jumper Switches on AFS-XX to appropriate settings. Output Selection SW1: 4-20mA Output Working Range SW2: 0-2000 Ft/Min Range 0-3000 Ft/Min Range 0-4000 Ft/Min Range Response Time SW3: Fast Slow
- Set FMS Input Channel to an Analog 4-20 mA. 3. For a 0-2000 Ft/Min Range, use a gain of 500 and an offset of -500. 4. For other settings, use the integrated gain/offset calculator.
FMS Configuration
FMS AFS-xx Input Configuration Interface
AFS-D FMS Integration
Figure 9.1: FMS Wiring
FMS Configuration
Set Input Type to a NC Digital Contact for each AFS-D wired into the Falcon. Assign an on/ off label for each sensor connected.
MD3 FMS Integration
Figure 10.1: FMS Wiring
FMS Input Configuration Interface
FMS Configuration
Set Input Type to a Digital NC Input Type for each MDS wired into the Falcon.
SMK FMS Integration
Figure 12.1: FMS Wiring
FMS Input Configuration Interface
FMS Configuration
Set Input Type to a NO Digital Contact for each SMK wired into the Falcon.
HD150 & HD150-2 FMS Integration
Figure 13.1: FMS Wiring
FMS Input Configuration Interface
FMS Configuration
Set Input Type to a Digital NO Input type for each HD150/HD150-2 Relay Output wired into the Falcon.
KPO Falcon Integration
Figure 14.1: FMS Wiring with KPO
FMS Configuration
Enter in Keypad users and corresponding codes in the Falcon’s Keypad/DTMF
Access User Configuration menu.
FMS BAPI Temperature/Humidity Falcon Integration
Figure 15.1: Falcon Wiring with the BAPI Temperature/Humidity sensor
SETUP
- Wire the sensor as shown
- . Configure the Falcon Input channel (temperature) for “Analog 4-20mA” and enter the gain and offset values. For the 32- 120F range use Gain 22, Offset -10
- For other temperature ranges, use the Calculator function on T the webpage
- Configure the Falcon Input Channel (humidity) for “Analog 4- 20mA” and enter the Gain of 25 and Offset of -25.
- Verify the “Calc” Value displays the correct room temperature. The temperature can also be viewed on the Falcon main page.
Temperature Setup 2 – 120 Degree F Range
Humidity Setup
TROUBLESHOOTING
- Calculate the BAPI Output current for temperature ( (Actual temp – Sensor Low) / (Sensor High – Sensor Low)) x 16 + 4 Example if Room Temp is 70F and your sensor has a range of 32-120 ( (70 – 32) / (120 – 32)) x 16 + 4 = 10.90
- Measure the current flowing into the Falcon Ch- terminal with a current meter. Verify that it is close to the calculated current (+/-1%)
- If measured current current does not match calculated current then check wiring and check the BAPI switch settings.
- Compare the measured current matches the current reading in the Falcon
- Check the wiring if the Falcon current reading does not match the measured current reading
- If the Falcon current reading matches the measured current and the Falcon calculated value does not match the room temperature then the offset and gain values are wrong. Double check the Gain and Offset values.
- If the temperature displayed in the Falcon is 1 or 2 degrees above or below the room temperature then adjust the offset by 1 or 2. Do not adjust the gain. Only tweak the offset once the previous troubleshooting steps have been performed.
- If the Falcon still does not display the correct temperature contact RLE Technologies technical support at 970.484.6510.
- Use similar troubleshooting procedure except use the following formula to calculate the humidity mA output
FMS HW2XA2A Temperature/Humidity Integration
Figure 16.1: Falcon Wiring with the HW2XA2A Temperature/Humidity sensor
SETUP
- Wire the sensor as shown
- Configure the Falcon Input channel (temperature) for “Analog 4-20mA” and enter the gain and offset values. For the 32- 122F range use Gain 22.5, Offset 9.5.
- For other temperature ranges, use the Calculator function on the webpage
- Configure the Falcon Input Channel (humidity) for “Analog 4- 20mA” and enter the Gain of 25 and Offset of -25.
- Verify the “Calc” Value displays the correct room temperature. The temperature can also be viewed on the Falcon main page
Temperature Setup 32 – 122 Degree F Range
Humidity Setup
TROUBLESHOOTING
- Calculate the output current for temperature (Actual temp – Sensor Low) / (Sensor High – Sensor Low)) x 16 + 4 Example if Room Temp is 70F and your sensor has a range of 32-122 (70 – 32) / (122 – 32)) x 16 + 4 = 10.75
- Measure the current flowing into the Falcon Ch- terminal with a current meter. Verify that it is close to the calculated current (+/-1%)
- If measured current current does not match calculated current then check wiring.
- Compare the measured current matches the current reading in the Falcon.
- Check the wiring if the Falcon current reading does not match the measured current reading.
- If the Falcon current reading matches the measured current and the Falcon calculated value does not match the room temperature then the offset and gain values are wrong. Double check the Gain and Offset values.
- If the temperature displayed in the Falcon is 1 or 2 degrees above or below the room temperature then adjust the offset by 1 or 2. Do not adjust the gain. Only tweak the offset once the previous troubleshooting steps have been performed.
- If the Falcon still does not display the correct temperature contact RLE Technologies technical support at 970.484.6510.
- Use similar troubleshooting procedure except use the following formula to calculate the humidity mA output
FMS Dwyer Temperature/Humidity Falcon Integration
Figure 16.1: Falcon Wiring with the Dwyer Temperature/Humidity sensor
SETUP
- Wire the sensor as shown
- Configure the Falcon Input channel (temperature) for “Analog 4-20mA” and enter the gain and offset values. For the -40 – 140F range use Gain 45, Offset -8
- For other temperature ranges, use the Calculator function on the webpage
- Configure the Falcon Input Channel (humidity) for “Analog 4- 20mA” and enter the Gain of 25 and Offset of -25
- Verify the “Calc” Value displays the correct room temperature. The temperature can also be viewed on the Falcon main page
Temperature Setup -40 – 140 Degree F Range
Humidity Setup
TROUBLESHOOTING
-
Calculate the Dwyer Output current for temperature. ample if Room Temp is 70F and your sensor has a range of -40 – 140 ( (Actual temp – Sensor Low) / (Sensor High – Sensor Low)) x 16 + 4 ( (70 – -40) / (140 – -40)) x 16 + 4 = 13.77
-
Measure the current flowing into the Falcon Ch- terminal with a current meter. Verify that it is close to the calculated current (+/-1%)
-
If measured current current does not match calculated current then check wiring.
-
Compare the measured current matches the current reading in the Falcon.
-
Check the wiring if the Falcon current reading does not match
the measured current reading. -
If the Falcon current reading matches the measured current and the Falcon calculated value does not match the room temperature then the offset and gain values are wrong. Double check the Gain and Offset values.
-
If the temperature displayed in the Falcon is 1 or 2 degrees above or below the room temperature then adjust the offset by 1 or 2. Do not adjust the gain. Only tweak the offset once the previous troubleshooting steps have been performed.
-
If the Falcon still does not display the correct temperature contact RLE Technologies technical support at 970.484.6510.
-
Use similar troubleshooting procedure except use the following formula to calculate the humidity mA output
FMS WIRED-TH Temperature/Humidity Integration
Figure 16.1: Falcon Wiring with the WIRED-TH Temperature/Humidity sensor
SETUP
- Wire the sensor as shown
- Configure the Falcon Input channel (temperature) for “Analog 4-20mA” and enter the gain and offset values. For the -20- 140F range use Gain 40.0, Offset 60.0
- For other temperature ranges, use the Calculator function on the webpage
- Configure the Falcon Input Channel (humidity) for “Analog 4- 20mA” and enter the Gain of 25 and Offset of -25
- Verify the “Calc” Value displays the correct room temperature. The temperature can also be viewed on the Falcon main page
Temperature Setup -20 – 140 Degree F Range
TROUBLESHOOTING
-
Calculate the output current for temperature ( (Actual temp – Sensor Low) / (Sensor High – Sensor Low)) x 16 + 4 ( (70 – -20) / (140 – -20)) x 16 + 4 = 13.0
-
Measure the current flowing into the Falcon Ch- terminal with a current meter. Verify that it is close to the calculated current (+/-1%) 3. If measured current current does not match calculated current then check wiring.
-
Compare the measured current matches the current reading in the Falcon.
-
Check the wiring if the Falcon current reading does not match
the measured current reading. -
If the Falcon current reading matches the measured current and the Falcon calculated value does not match the room temperature then the offset and gain values are wrong. Double check the Gain and Offset values.
-
If the temperature displayed in the Falcon is 1 or 2 degrees above or below the room temperature then adjust the offset by 1 or 2. Do not adjust the gain. Only tweak the offset once the previous troubleshooting steps have been performed.
-
If the Falcon still does not display the correct temperature contact RLE Technologies technical support at 970.484.6510.
-
Use similar troubleshooting procedure except use the following formula to calculate the humidity mA output
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>