DESCRIPTION
The nVent RAYCHEM RTD3CS and RTD10CS are three-wire platinum RTD (resistance
temperature detectors) typically used with monitoring and control systems,
such as our RAYCHEM 910 controller, when accurate temperature control is
required.
The RTD3CS and RTD10CS can be installed directly to the controller using the
supplied ½ inch conduit fitting or to an RTD junction box where RTD extension
wire is used.
TOOLS REQUIRED
- 3.5-mm flat-blade screwdriver
ADDITIONAL MATERIALS REQUIRED
- nVent RAYCHEM AT-180 aluminum tape
APPROVALS
Approvals associated with control device, however not to be used in Div. 1 locations.
SPECIFICATIONS
KIT CONTENTS
⚠ WARNING:
This component is an electrical device. It must be installed correctly to
ensure proper operation and to prevent shock or fire. Read these important
warnings and carefully follow all the installation instructions. Component
approvals and performance are based on the use of specified parts only. Do not
use substitute parts or vinyl electrical tape to make connections.
POSITIONING THE SENSOR
Position the RTD sensor in the lower quadrant of the pipe as shown in the diagram. Place the RTD sensor at least 3 feet (1 m) from pipe supports, valves, or other heat sinks. Tape the RTD firmly to the pipe with AT-180 aluminum tape, making sure there is no air space between the RTD and the pipe. Do not use the same piece of AT-180 tape to overlap the RTD and heat-trace cable.
INSTALLATION WITH HEATING CABLE
Electrical Wiring Guidelines: Most electrical codes (such as NEC 725.15)
permit Class 1 circuits to occupy the same cable, enclosure, or raceway
without regard to whether the individual circuits are alternating current or
direct current, providing all conductors are insulated for the maximum voltage
of any conductors in the cable, enclosure or raceway.
Additional Materials Required · nVent RAYCHEM JBS-100-A or other power
connection kit · Pipe straps
WIRING INFORMATION
The length of RTD extension wires is determined by the wire gauge used. To reduce the likelihood that electrical noise will affect temperature measurement, keep RTD extension wires as short as possible. Use shielded instrument cable such as nVent RAYCHEM MONI-RTD-WIRE (22AWG, PVC insulation, 30°F to 140°F, 20°C to 60°C) or Belden 83553 (22AWG, FEP insulation, 95°F to 395°F, 70°C to 200°C).
RTD DIRECT CONNECTION TO CONTROLLER
(Distance from sensor bulb to controller must be less than 10 feet)
The RTD3CS and RTD10CS can be terminated directly at the controller using the
supplied ½ inch NPT fitting. In this configuration, no additional extension
wire is required.
(Distance from sensor bulb to controller greater than 3 feet for the RTD3CS and 10 feet for the RTD10CS)
RTD3CS AND RTD10CS WIRING
Connect the wires as shown.
Note: Ground RTD extension wire shield at one end only, preferably at RAYCHEM
electronics end.
North America
Tel +1.800.545.6258
Fax +1.800.527.5703
thermal.info@nVent.com
Europe, Middle East, Africa
Tel +32.16.213.511
Fax +32.16.213.604
thermal.info@nVent.com
Asia Pacific
Tel +86.21.2412.1688
Fax +86.21.5426.3167
cn.thermal.info@nVent.com
Latin America
Tel +1.713.868.4800
Fax +1.713.868.2333
thermal.info@nVent.com
©2022 nVent. All nVent marks and logos are owned or licensed by nVent Services
GmbH or its affiliates. All other trademarks are the property of their
respective owners. nVent reserves the right to change specifications without
notice.
RAYCHEM-IM-H56989-RTD3CSRTD10CS-EN-2211
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>