solinved 6.5KW Solar Inverter Charger User Manual
- June 9, 2024
- solinved
Table of Contents
6.5KW Solar Inverter Charger
error
{
“error”: {
“message”: “You exceeded your current quota, please check your plan and
billing details.”,
“type”: “insufficient_quota”,
“param”: null,
“code”: null
}
}
the following is the text from the user manual / instructions:
User Manual
6.5KW / 8KW SOLAR INVERTER / CHARGER
Version: 1.4
Table of Contents
ABOUT THIS MANUAL …………………………………………………………………………………………………………………….. 1
Purpose………………………………………………………………………………………………………………………………………… 1 Scope
…………………………………………………………………………………………………………………………………………… 1
SAFETY INSTRUCTIONS………………………………………………………………………………………………………………….. 1
INTRODUCTION ………………………………………………………………………………………………………………………………. 2
ABOUT THIS MANUAL Purpose
This manual describes the assembly, installation, operation and
troubleshooting of this unit. Please read this manual carefully before
installations and operations. Keep this manual for future reference.
Scope
This manual provides safety and installation guidelines as well as information
on tools and wiring.
SAFETY INSTRUCTIONS
WARNING: This chapter contains important safety and operating instructions.
Read and keep this manual for future reference.
1. Before using the unit, read all instructions and cautionary markings on
the unit, the batteries and all appropriate sections of this manual.
3. Do not disassemble the unit. Take it to a qualified service center when
service or repair is required. Incorrect re-assembly may result in a risk of
electric shock or fire.
4. To reduce risk of electric shock, disconnect all wirings before attempting
any maintenance or cleaning. Turning off the unit will not reduce this risk.
size. It’s very important to correctly operate this inverter/charger. 8. Be
very cautious when working with metal tools on or around batteries. A
potential risk exists to drop
a tool to spark or short circuit batteries or other electrical parts and could
cause an explosion. 9. Please strictly follow installation procedure when you
want to disconnect AC or DC terminals. Please
refer to INSTALLATION section of this manual for the details. 10. Fuses are
provided as over-current protection for the battery supply. 11. GROUNDING
INSTRUCTIONS -This inverter/charger should be connected to a permanent
grounded
wiring system. Be sure to comply with local requirements and regulation to
install this inverter. 12. NEVER cause AC output and DC input short circuited.
Do NOT connect to the mains when DC input
short circuits. 13. Warning!! Only qualified service persons are able to
service this device. If errors still persist after
following troubleshooting table, please send this inverter/charger back to
local dealer or service center for maintenance.
14. WARNING: Because this inverter is non-isolated, only three types of PV
modules are acceptable:
single crystalline, poly crystalline with class A-rated and CIGS modules. To
avoid any malfunction, do not connect any PV modules with possible current
leakage to the inverter. For example, grounded PV modules will cause current
leakage to the inverter. When using CIGS modules, please be sure NO grounding.
15. CAUTION: It’s required to use PV junction box with surge protection.
Otherwise, it will cause damage on inverter when lightning occurs on PV
modules.
User Manual
6.5KW / 8KW SOLAR INVERTER / CHARGER
Version: 1.4
Table of Contents
ABOUT THIS MANUAL …………………………………………………………………………………………………………………….. 1
Purpose………………………………………………………………………………………………………………………………………… 1 Scope
…………………………………………………………………………………………………………………………………………… 1
SAFETY INSTRUCTIONS………………………………………………………………………………………………………………….. 1
INTRODUCTION ………………………………………………………………………………………………………………………………. 2
Features ……………………………………………………………………………………………………………………………………….. 2 Basic System
Architecture ………………………………………………………………………………………………………………. 2 Product
Overview…………………………………………………………………………………………………………………………… 3 Unpacking and
Inspection ………………………………………………………………………………………………………………. 4 Mounting the Unit
…………………………………………………………………………………………………………………………… 4 Preparation
…………………………………………………………………………………………………………………………………… 5 Battery Connection
………………………………………………………………………………………………………………………… 5 AC Input/Output Connection
……………………………………………………………………………………………………………. 6 PV Connection
………………………………………………………………………………………………………………………………. 8 Final
Assembly…………………………………………………………………………………………………………………………….. 10 DC Output
Connectors………………………………………………………………………………………………………………….. 10 Communication
Connection…………………………………………………………………………………………………………… 11 Dry Contact Signal
……………………………………………………………………………………………………………………….. 12
OPERATION…………………………………………………………………………………………………………………………………… 13 Power ON/OFF
……………………………………………………………………………………………………………………………. 13 Operation and Display
Panel …………………………………………………………………………………………………………. 13 LCD Display Icons
……………………………………………………………………………………………………………………….. 14 LCD
Setting…………………………………………………………………………………………………………………………………. 16 LCD Display
………………………………………………………………………………………………………………………………… 32 Operating Mode
Description ………………………………………………………………………………………………………….. 38 Faults Reference
Code …………………………………………………………………………………………………………………. 42 Warning Indicator
…………………………………………………………………………………………………………………………. 43 CLEARANCE AND MAINTENANCE
FOR ANTI-DUST KIT…………………………………………………………………. 44 Overview
…………………………………………………………………………………………………………………………………….. 44 Clearance and
Maintenance ………………………………………………………………………………………………………….. 44 BATTERY EQUALIZATION
……………………………………………………………………………………………………………… 45 SPECIFICATIONS
…………………………………………………………………………………………………………………………… 46 Table 1 Line Mode
Specifications ……………………………………………………………………………………………………. 46 Table 2 Inverter
Mode Specifications ………………………………………………………………………………………………. 47 Table 3 Charge
Mode Specifications………………………………………………………………………………………………… 48 Table 4 General
Specifications………………………………………………………………………………………………………… 49 TROUBLE SHOOTING
……………………………………………………………………………………………………………………. 50 Appendix I: Parallel function
………………………………………………………………………………………………………….. 51 Appendix II: BMS Communication
Installation………………………………………………………………………………… 64 Appendix III: The Wi-Fi
Operation Guide…………………………………………………………………………………………. 70
ABOUT THIS MANUAL Purpose
This manual describes the assembly, installation, operation and
troubleshooting of this unit. Please read this manual carefully before
installations and operations. Keep this manual for future reference.
Scope
This manual provides safety and installation guidelines as well as information
on tools and wiring.
SAFETY INSTRUCTIONS
WARNING: This chapter contains important safety and operating instructions.
Read and keep this manual for future reference.
1. Before using the unit, read all instructions and cautionary markings on
the unit, the batteries and all appropriate sections of this manual.
2. CAUTION To reduce risk of injury, charge only deep-cycle lead acid type
rechargeable batteries. Other types of batteries may burst, causing personal
injury and damage.
3. Do not disassemble the unit. Take it to a qualified service center when
service or repair is required. Incorrect re-assembly may result in a risk of
electric shock or fire.
4. To reduce risk of electric shock, disconnect all wirings before attempting
any maintenance or cleaning. Turning off the unit will not reduce this risk.
5. CAUTION Only qualified personnel can install this device with battery.
6. NEVER charge a frozen battery. 7. For optimum operation of this
inverter/charger, please follow required spec to select appropriate cable
size. It’s very important to correctly operate this inverter/charger. 8. Be
very cautious when working with metal tools on or around batteries. A
potential risk exists to drop
a tool to spark or short circuit batteries or other electrical parts and could
cause an explosion. 9. Please strictly follow installation procedure when you
want to disconnect AC or DC terminals. Please
refer to INSTALLATION section of this manual for the details. 10. Fuses are
provided as over-current protection for the battery supply. 11. GROUNDING
INSTRUCTIONS -This inverter/charger should be connected to a permanent
grounded
wiring system. Be sure to comply with local requirements and regulation to
install this inverter. 12. NEVER cause AC output and DC input short circuited.
Do NOT connect to the mains when DC input
short circuits. 13. Warning!! Only qualified service persons are able to
service this device. If errors still persist after
following troubleshooting table, please send this inverter/charger back to
local dealer or service center for maintenance.
14. WARNING: Because this inverter is non-isolated, only three types of PV
modules are acceptable:
single crystalline, poly crystalline with class A-rated and CIGS modules. To
avoid any malfunction, do not connect any PV modules with possible current
leakage to the inverter. For example, grounded PV modules will cause current
leakage to the inverter. When using CIGS modules, please be sure NO grounding.
15. CAUTION: It’s required to use PV junction box with surge protection.
Otherwise, it will cause damage on inverter when lightning occurs on PV
modules.
1
INTRODUCTION
This is a multi-function inverter, combining functions of inverter, solar
charger and battery charger to offer uninterruptible power support in a single
package. The comprehensive LCD display offers user-configurable and easy-
accessible button operations such as battery charging current, AC or solar
charging priority, and acceptable input voltage based on different
applications.
Features
Pure sine wave inverter Customizable status LED ring with RGB lights Touchable
button with 5″ colored LCD Built-in Wi-Fi for mobile monitoring (APP is
required) Supports USB On-the-Go function Built-in anti-dusk kit Reserved
communication ports for BMS (RS485, CAN-BUS, RS232) Configurable input voltage
ranges for home appliances and personal computers via LCD control panel
Configurable output usage timer and prioritization Configurable charger source
priority via LCD control panel Configurable battery charging current based on
applications via LCD control panel Compatible to utility mains or generator
power
Basic System Architecture
The following illustration shows basic application for this unit. It also
required the following devices to have a complete running system:
Generator or Utility mains. PV modules Consult with your system integrator for
other possible system architectures depending on your requirements. This
inverter can power various appliances in home or office environment, including
motor-type appliances such as tube light, fan, refrigerator and air
conditioners.
Figure 1 Basic hybrid PV System Overview
2
Product Overview
NOTE: For parallel installation and operation, please check Appendix I. 1. RGB
LED ring (refer to LCD Setting section for the details) 2. LCD display 3.
Touchable function keys 4. PV connectors 5. AC input connectors 6. AC output
connectors (Load connection) 7. Battery connectors 8. Current sharing port 9.
Parallel communication port 10. Power switch 11. Dry contact 12. USB port as
USB communication port and USB function port 13. RS-232 communication port 14.
BMS communication port: CAN, RS-485 or RS-232 15. DC output connectors 16.
Power switch for DC output
3
INSTALLATION
Unpacking and Inspection
Before installation, please inspect the unit. Be sure that nothing inside the
package is damaged. You should have received the following items inside of
package:
Inverter unit Manual software CD RS-232 cable Parallel communication cable
Current sharing cable
DC Fuse
Cable gland x 4 pcs PV connectors x 2 sets Mounting bracket Mounting ear x 2 M5 screw x 6 pcs
Mounting the Unit
Consider the following points before selecting where to install: Do not mount
the inverter on flammable construction
materials. Mount on a solid surface Install this inverter at eye level in
order to allow the LCD
display to be read at all times. The ambient temperature should be between 0°C
and 55°C
to ensure optimal operation. The recommended installation position is to be
adhered to
the wall vertically. Be sure to keep other objects and surfaces as shown in
the
right diagram to guarantee sufficient heat dissipation and to
have enough space for removing wires.
SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.
Please follow below steps to install the inverter on the wall.
Step 1: Install the mounting Step 2: Install the mounting ears
bracket by fixing six pieces of M5 on the back of the unit with four
screws.
supplied M5 screws.
Step 3: Raise the inverter and place it over the mounting bracket.
4
Step 4: Removing bottom cover with six screws as shown below chart.
Step 5: Fix the inverter to mounting bracket by screwing two supplied M5 screws as shown below chart.
Step 6: Assemble the bottom cover back to original position.
Preparation
Before connecting all wirings, please take off wiring cover by removing six
screws. When removing the bottom cover, be carefully to remove two cables as
shown below.
Battery Connection
CAUTION: For safety operation and regulation compliance, it’s requested to install a separate DC over-current
protector or disconnect device between battery and inverter. It may not be requested to have a disconnect
device in some applications, however, it’s still requested to have over- current protection installed. Please refer
to typical amperage in below table as required fuse or breaker size.
Ring terminal:
WARNING! All wiring must be performed by a qualified personnel.
WARNING! It’s very important for system safety and efficient operation to use
appropriate cable for battery connection. To reduce risk of injury, please use
the proper recommended cable and terminal size as below.
Recommended battery cable and terminal size:
Model
Typical Amperage
Battery capacity
Wire Size
6.5KW
153A
250AH
1*2/0AWG
8KW
182.2A
250AH
1*2/0AWG
Cable mm2
67
67.4
Ring Terminal Dimensions
D (mm) L (mm)
8.4
51
8.4
51
Torque value
5 Nm 5 Nm
5
Please follow below steps to implement battery connection: 1. Assemble battery
ring terminal based on recommended battery cable and terminal size. 2. Fix two
cable glands into positive and negative terminals. 3. Insert the ring terminal
of battery cable flatly into battery connector of inverter and make sure the
nuts are
tightened with torque of 5 Nm. Make sure polarity at both the battery and the
inverter/charge is correctly connected and ring terminals are tightly screwed
to the battery terminals.
WARNING: Shock Hazard Installation must be performed with care due to high
battery voltage in series.
CAUTION!! Do not place anything between the flat part of the inverter terminal
and the ring terminal. Otherwise, overheating may occur. CAUTION!! Do not
apply anti-oxidant substance on the terminals before terminals are connected
tightly. CAUTION!! Before making the final DC connection or closing DC
breaker/disconnector, be sure positive (+) must be connected to positive (+)
and negative (-) must be connected to negative (-).
AC Input/Output Connection
CAUTION!! Before connecting to AC input power source, please install a
separate AC breaker between inverter and AC input power source. This will
ensure the inverter can be securely disconnected during maintenance and fully
protected from over current of AC input. CAUTION!! There are two terminal
blocks with “IN” and “OUT” markings. Please do NOT mis-connect input and
output connectors.
WARNING! All wiring must be performed by a qualified personnel. WARNING! It’s very important for system safety and efficient operation to use appropriate cable for AC input connection. To reduce risk of injury, please use the proper recommended cable size as below. Suggested cable requirement for AC wires
Model
Gauge
Torque Value
6.5KW
4 AWG
1.4~ 1.6Nm
8KW
8 AWG
1.4~ 1.6Nm
Please follow below steps to implement AC input/output connection: 1. Before
making AC input/output connection, be sure to open DC protector or
disconnector first. 2. Remove insulation sleeve 10mm for six conductors. And
shorten phase L and neutral conductor N 3 mm. 3. Fix two cable glands into
input and output sides. 4. Insert AC input wires according to polarities
indicated on terminal block and tighten the terminal screws.
Be sure to connect PE protective conductor ( ) first.
Ground (yellow-green) LLINE (brown or black) NNeutral (blue)
6
WARNING: Be sure that AC power source is disconnected before attempting to
hardwire it to the unit. 5. Then, insert AC output wires according to
polarities indicated on terminal block and tighten terminal screws. Be sure to
connect PE protective conductor ( ) first. Ground (yellow-green) LLINE (brown
or black) NNeutral (blue)
6. Make sure the wires are securely connected. CAUTION: Important Be sure to
connect AC wires with correct polarity. If L and N wires are connected
reversely, it may cause utility short-circuited when these inverters are
worked in parallel operation. CAUTION: Appliances such as air conditioner
requires at least 2~3 minutes to restart because it’s required to have enough
time to balance refrigerant gas inside of circuits. If a power shortage occurs
and recovers in a short time, it will cause damage to your connected
appliances. To prevent this kind of damage, please check manufacturer of air
conditioner if it’s equipped with time-delay function before installation.
Otherwise, this inverter/charger will be trigger overload fault and cut off
output to protect your appliance but sometimes it still causes internal damage
to the air conditioner.
7
PV Connection
CAUTION: Before connecting to PV modules, please install separately DC circuit
breakers between inverter and PV modules. NOTE1: Please use 600VDC/30A circuit
breaker. NOTE2: The overvoltage category of the PV input is II. Please follow
the steps below to implement PV module connection:
WARNING: Because this inverter is non-isolated, only three types of PV modules
are acceptable: single crystalline and poly crystalline with class A-rated and
CIGS modules. To avoid any malfunction, do not connect any PV modules with
possible current leakage to the inverter. For example, grounded PV modules
will cause current leakage to the inverter. When using CIGS modules, please be
sure NO grounding. CAUTION: It’s required to use PV junction box with surge
protection. Otherwise, it will cause damage on inverter when lightning occurs
on PV modules. Step 1: Check the input voltage of PV array modules. This
system is applied with two strings of PV array. Please make sure that the
maximum current load of each PV input connector is 18A. CAUTION: Exceeding the
maximum input voltage can destroy the unit!! Check the system before wire
connection. Step 2: Disconnect the circuit breaker and switch off the DC
switch. Step 3: Assemble provided PV connectors with PV modules by the
following steps. Components for PV connectors and Tools: Female connector
housing
Female terminal Male connector housing
Male terminal Crimping tool and spanner
Prepare the cable and follow the connector assembly process: Strip one cable 8
mm on both end sides and be careful NOT to nick conductors.
Insert striped cable into female terminal and crimp female terminal as shown
below.
Insert assembled cable into female connector housing as shown below.
Insert striped cable into male terminal and crimp male terminal as shown
below.
Insert assembled cable into male connector housing as shown below.
Then, use spanner to screw pressure dome tightly to female connector and male
connector as shown below.
8
Step 4: Check correct polarity of connection cable from PV modules and PV input connectors. Then, connect positive pole (+) of connection cable to positive pole (+) of PV input connector. Connect negative pole (-) of connection cable to negative pole (-) of PV input connector.
WARNING! For safety and efficiency, it’s very important to use appropriate cables for PV module connection.
To reduce risk of injury, please use the proper cable size as recommended below.
Model
Wire Size
Cable mm2
8KW
10~12 AWG
4~6
CAUTION: Never directly touch the terminals of inverter. It might cause lethal electric shock.
Recommended Panel Configuration When selecting proper PV modules, please be
sure to consider the following parameters: 1. Open circuit Voltage (Voc) of PV
modules not to exceed maximum PV array open circuit voltage of the
inverter. 2. Open circuit Voltage (Voc) of PV modules should be higher than
the start-up voltage.
INVERTER MODEL
6.5KW
8KW
Max. PV Array Power
8000W
Max. PV Array Open Circuit Voltage
250Vdc
500Vdc
PV Array MPPT Voltage Range
90Vdc~230Vdc
90Vdc~450Vdc
Start-up Voltage (Voc)
80Vdc
Recommended solar panel configuration for 6.5KW model:
Solar Panel Spec. (reference) – 330Wp – Vmp: 33.7Vdc – Imp: 9.79A – Voc: 39.61Vdc – Isc: 10.4A – Cells: 60
SOLAR INPUT 1
SOLAR INPUT 2
Min in series: 3pcs, per input Max. in series:6pcs, per input
3pcs in series
x
x
3pcs in series
6pcs in series
x
x
6pcs in series
6pcs in series
6pcs in series
6pcs in series, 2 strings
x
Q’ty of panels
3pcs 3pcs 6pcs 6pcs 12pcs 12pcs
x
6pcs in series, 2 strings
12pcs
6pcs in series, 2 strings 6pcs in series, 2 strings
24pcs
Total Input Power
990W 990W 1980W 1980W 3960W 3960W 3960W 7920W
9
Recommended solar panel configuration for 8KW model:
Solar Panel Spec.
SOLAR INPUT 1
SOLAR INPUT 2
(reference)
Min in series: 4pcs, per input
Q’ty of panels
– 250Wp
Max. in series: 12pcs, per input
– Vmp: 30.7Vdc
4pcs in series
x
4pcs
– Imp: 8.3A – Voc: 37.7Vdc – Isc: 8.4A – Cells: 60
x 12pcs in series
x 6pcs in series
4pcs in series x
12pcs in series 6pcs in series
4pcs 12pcs 12pcs 12pcs
6pcs in series, 2 strings
x
12pcs
x
6pcs in series, 2 strings
12pcs
8pcs in series, 2 strings
x
16pcs
x
8pcs in series, 2 strings
16pcs
9pcs in series, 1 string 9pcs in series, 1 string
18pcs
10pcs in series, 1 string 10pcs in series, 1 string
20pcs
12pcs in series, 1 string 12pcs in series, 1 string
24pcs
6pcs in series, 2 strings 6pcs in series, 2 strings
24pcs
7pcs in series, 2 strings 7pcs in series, 2 strings
28pcs
8pcs in series, 2 strings 8pcs in series, 2 strings
32pcs
Total Input Power
1000W 1000W 3000W 3000W 3000W 3000W 3000W 4000W 4000W 4500W 5000W 6000W 6000W
7000W 8000W
Final Assembly
After connecting all wirings, re-connect two cables and then put bottom cover
back by fixing six screws as shown below.
DC Output Connectors
These DC output connectors are used to provide emergency power backup to all
kinds of DC-powered equipment such as routers, modems, set-top box, VOIP phone
systems, surveillance system, alarm system, access control system and many
critical telecom equipment. There are 3 channels (current limit at 3A for each
channel), which could be activated/disabled manually either through LCD
operation or power switch beside the DC jacks. Supplied dimension of DC jack
(male) is OD 5.5mm, ID 2.5mm.
10
Communication Connection
Follow below chart to connect all communication wiring.
RS-232 communication to PC
USB communication to PC
BMS communication
Serial Connection Please use the supplied serial cable to connect between the
inverter and your PC. Install the monitoring software from the bundled CD and
follow the on-screen instructions to complete your installation. For detailed
software operation, refer to the software user manual on the bundled CD.
Wi-Fi Connection This unit is equipped with a Wi-Fi transmitter. Wi-Fi
transmitter can enable wireless communication between off-grid inverters and
monitoring platform. Users can access and control the monitored inverter with
downloaded APP. You may find “WatchPower” app from the Apple® Store or
“WatchPower Wi-Fi” in Google® Play Store. All data loggers and parameters are
saved in iCloud. For quick installation and operation, please refer to
Appendix III – The Wi-Fi Operation Guide for details.
BMS Communication Connection It is recommended to purchase a special
communication cable if you are connecting to Lithium-Ion battery banks. Please
refer to Appendix II – BMS Communication Installation for details.
11
Dry Contact Signal
There is one dry contact (3A/250VAC) available on the rear panel. It could be
used to deliver signal to external device when battery voltage reaches warning
level.
Unit Status
Condition
Power Off Power On
Unit is off and no output is powered.
Output is
Program 01 Battery voltage < Low DC
powered
set as USB warning voltage
from Battery (utility first) Battery voltage > Setting
power or
or SUB (solar value in Program 13 or
Solar energy. first)
battery charging reaches
floating stage
Program 01 Battery voltage < Setting
is set as SBU value in Program 12
(SBU priority) Battery voltage > Setting
value in Program 13 or
battery charging reaches
floating stage
Dry contact port:
NC & C Close
NO & C Open
Open
Close
Close
Open
Open
Close
Close
Open
12
OPERATION
Power ON/OFF
Once the unit has been properly installed and the batteries are connected
well, simply press power switch to turn on the unit.
Operation and Display Panel
The operation and the LCD module, shown in the chart below, includes one RGB
LED ring, one power switch, four touchable function keys and a LCD display to
indicate the operating status and input/output power information.
RGB LED ring
LCD display Touchable function keys
Power switch
Touchable Function Keys Function Key ESC Access USB setting mode Up Down Enter
Description To exit the setting To enter USB setting mode To last selection To
next selection To confirm/enter the selection in setting mode
13
LCD Display Icons
Battery Information
Indicates battery level by 0-24%, 25-49%, 50-74% and 75-100% in battery
mode and charging status in line mode.
When battery is charging, it will present battery charging status.
Status
C.C. mode C.V. mode
Battery voltage <2V/cell 2 ~ 2.083V/cell
2.083 ~ 2.167V/cell
2.167 V/cell
LCD Display 4 bars will flash in turns. The right bar will be on and the other
three bars will flash in turns. The right two bars will be on and the other
two bars will flash in turns.
The right three bars will be on and the left bar will
flash.
Floating mode. Batteries are fully charged. 4 bars will be on.
In battery mode, it will present battery capacity.
Load Percentage Battery Voltage
LCD Display
< 1.85V/cell
Load >50%
1.85V/cell ~ 1.933V/cell 1.933V/cell ~ 2.017V/cell
2.017V/cell
< 1.892V/cell
Load < 50%
1.892V/cell ~ 1.975V/cell 1.975V/cell ~ 2.058V/cell
2.058V/cell Load Information
Indicates overload.
Indicates the load level by 0-24%, 25-49%, 50-74% and 75-100%.
14
Charger Source Priority Setting Display
Indicates setting program 16 “Charger source priority” is selected as “Solar
first”.
Indicates setting program 16 “Charger source priority” is selected as “Solar
and Utility”.
Indicates setting program 16 “Charger source priority” is selected as “Solar
only”. Output source priority setting display
Indicates setting program 01 “Output source priority” is selected as “Utility
first”.
Indicates setting program 01 “Output source priority” is selected as “Solar first”.
Indicates setting program 01 “Output source priority” is selected as “SBU”.
AC Input Voltage Range Setting Display
Indicates setting program 03 is selected as ”
“. The acceptable
AC input voltage range will be within 170-280VAC for 8KW and 90-
140VAC for 6.5KW.
Indicates setting program 03 is selected as ”
“. The acceptable
AC input voltage range will be within 90-280VAC for 8KW and 80-
140VAC for 6.5KW.
Operation Status Information
Indicates unit connects to the mains.
Indicates unit connects to the PV panel.
Indicates battery type. Indicates parallel operation is working. Indicates
unit alarm is disabled. Indicates Wi-Fi transmission is working. Indicates USB
disk is connected.
15
LCD Setting
General Setting
After pressing and holding ” ” button for 3 seconds, the unit will enter the
Setup Mode. Press ” ” or ” ” button to select setting programs. Press ” ”
button to confirm you selection or ” ” button to exit.
Setting Programs:
Program
Description
Selectable option Escape
00
Exit setting mode
Utility first (default)
Solar first
Output source priority:
01
To configure load power
source priority
SBU priority
Maximum charging current: 60A (default)
To configure total charging
current for solar and utility
02
chargers.
(Max. charging current =
utility charging current +
solar charging current)
16
Utility will provide power to the loads as first priority. Solar and battery
energy will provide power to the loads only when utility power is not
available.
Solar energy provides power to the loads as first priority. If solar energy is
not sufficient to power all connected loads, Utility energy will supply power
to the loads at the same time.
Solar energy provides power to the loads as first priority. If solar energy is
not sufficient to power all connected loads, battery energy will supply power
to the loads at the same time. Utility provides power to the loads only when
battery voltage drops to either lowlevel warning voltage or the setting point
in program 12.
Setting range is from 10A to 120A for 6.5KW model and from 10A to 150A for 8KW
model. Increment of each click is 10A.
Appliances (default)
03
AC input voltage range
UPS
AGM (default)
If selected, acceptable AC input voltage range will be within 90-280VAC for
8KW and 80-140VAC for 6.5KW..
If selected, acceptable AC input voltage range will be within 170-280VAC for
8KW and 90-140VAC for 6.5KW.
Flooded
05
Battery type
User-Defined PylonTech battery WECO battery Soltaro battery
17
If “User-Defined” is selected, battery charge voltage and low DC cut-off
voltage can be set up in program 26, 27 and 29.
If selected, programs of 02, 26, 27 and 29 will be automatically set up. No
need for further setting.
If selected, programs of 02, 12, 26, 27 and 29 will be auto-configured per
battery supplier recommended. No need for further adjustment.
If selected, programs of 02, 26, 27 and 29 will be automatically set up. No
need for further setting.
05
Battery type
LIb-protocol compatible battery 3rd party Lithium battery
Select “LIb” if using Lithium battery compatible to Lib protocol. If selected, programs of 02, 26, 27 and 29 will be automatically set up. No need for further setting. If selected, programs of 02, 26, 27 and 29 will be automatically set up. No need for further setting. Please contact the battery supplier for installation procedure.
Restart disable (default)
Restart enable
06
Auto restart when overload occurs
Restart disable (default)
07
Auto restart when over temperature occurs
Restart enable
09
Output frequency
50Hz (default for 8KW model)
60Hz (default for 6.5KW model)
Available options for 6.5KW model
110V
120V (default)
10
Output voltage
127V
18
Available options for 8KW model
220V
230V (default)
10
Output voltage
240V
Maximum utility charging current
30A (default)
Note: If setting value in
11
program 02 is smaller than
that in program in 11, the
inverter will apply charging
current from program 02
for utility charger.
46V (default)
Setting voltage point back
12
to utility source when selecting “SBU” (SBU
priority) in program 01.
Setting range is from 2A, then 10A to 120A. Increment of each click is 10A.
Setting range is from 44V to 51V. Increment of each click is 1V.
Setting range is FUL and from 48V to 62V. Increment of each
click is 1V.
Battery fully charged Setting voltage point back
54V (default)
to battery mode when 13
selecting “SBU” (SBU
priority) in program 01.
If this inverter/charger is working in Line, Standby or Fault
mode, charger source can be programmed as below:
Solar first
Solar energy will charge
Charger source priority:
battery as first priority.
16
To configure charger
Utility will charge battery only
source priority
when solar energy is not
available.
19
Solar and Utility (default)
Solar energy and utility will charge battery at the same time.
Charger source priority:
16
To configure charger
source priority
Only Solar
Solar energy will be the only charger source no matter utility is available or not.
18
Alarm control
Alarm on (default)
Alarm off
19
Auto return to default display screen
Return to default display screen (default)
If selected, no matter how users switch display screen, it will automatically return to default display screen after no button is pressed for 1 minute.
Stay at latest screen
If selected, the display screen will stay at latest screen user finally switches.
20
Backlight control
Backlight on (default)
Backlight off
20
Alarm on (default)
22
Beeps while primary source is interrupted
Alarm off
Bypass disable (default)
Overload bypass:
When enabled, the unit will
23
transfer to line mode if
overload occurs in battery
mode.
Record enable (default)
25
Record Fault code
Bypass enable Record disable
26
Bulk charging voltage (C.V voltage)
56.4V (default)
If user-defined is selected in program 5, this program can be set up. Setting range is from 48.0V to 62.0V. Increment of each click is 0.1V.
54V (default)
27
Floating charging voltage
If user-defined is selected in program 5, this program can be set up. Setting range is from 48.0V to 62.0V. Increment of each click is 0.1V.
Single: This inverter is used in Parallel: This inverter is
single phase application.
operated in parallel system.
AC output mode
*This setting is only
28
available when the inverter
is in standby mode (Switch
off).
21
When the inverter is operated in 3-phase application, set up
inverter to be operated in specific phase.
L1 phase:
L2 phase:
L3 phase:
AC output mode *This setting is only
When the inverter is operation in split phase application, set up
28
available when the inverter inverter to be operated in specific phase. These options are only
is in standby mode (Switch available for 6.5KW model. off).
L1 for split phase:
L2 for split phase:
(120° phase difference)
L2 for split phase: (180° phase difference)
Low DC cut-off voltage:
42.0V (default)
If battery power is only
power source available,
inverter will shut down.
If PV energy and
battery power are
29
available, inverter will
charge battery without
AC output.
If PV energy, battery power
and utility are all available,
inverter will transfer to line
mode
22
If user-defined is selected in program 5, this program can be set up. Setting range is from 42.0V to 48.0V. Increment of each click is 0.1V. Low DC cutoff voltage will be fixed to setting value no matter what percentage of load is connected.
Battery equalization
Battery equalization disable (default)
30
Battery equalization
If “Flooded” or “User-Defined” is selected in program 05, this
program can be set up.
58.4V (default)
Setting range is from 48.0V to
62.0V. Increment of each click is
0.1V.
31
Battery equalization voltage
60min (default)
33
Battery equalized time
Setting range is from 5 min to 900 min. Increment of each click is 5 min.
120min (default)
34
Battery equalized timeout
Setting range is from 5 min to 900 min. Increment of each click is 5 min.
35
Equalization interval
30days (default)
Setting range is from 0 to 90 days. Increment of each click is 1 day
36
Equalization activated immediately
Enable
Disable (default)
23
If equalization function is enabled in program 30, this program
can be set up. If “Enable” is selected in this program, it’s to activate
battery equalization immediately and LCD main page will
show ” “. If “Disable” is selected, it will cancel equalization function until next activated equalization time arrives based on
program 35 setting. At this time, ” ” will not be shown in LCD
main page.
Not reset(Default)
Reset
Reset all stored data for PV
37
generated power and
output load energy
Disable (Default)
If selected, battery discharge protection is disabled.
41
Maximum battery discharging current
30A 150A
The setting range is from 30 A to 150 A. Increment of each click is 10A. If discharging current is higher than setting value, battery will stop discharging. At this time, if the utility is available, the inverter will operate in bypass mode. If no utility is available, the inverter will shut down output after 5-minute operation in battery mode.
Enable (default) On/Off control for 12V DC 82 output
83
Erase all data log
Not reset (Default)
Disable Reset
24
3 minutes
5 minutes
10 minutes (default)
Data log recorded interval
*The maximum data log
84
number is 1440. If it’s over
1440, it will re-write the
first log.
30 minutes
20 minutes 60 minutes
85
Time setting Minute
86
Time setting Hour
87
Time setting Day
88
Time setting Month
For minute setting, the range is from 0 to 59.
For hour setting, the range is from 0 to 23.
For day setting, the range is from 1 to 31.
For month setting, the range is from 1 to 12.
25
89
Time setting Year
Enabled (default)
On/Off control for RGB LED
91
*It’s required to enable this
setting to activate RGB LED
lighting function.
Low
For year setting, the range is from 17 to 99. Disable
Normal (default)
92
Brightness of RGB LED
High
Low
93
Lighting speed of RGB LED
High
Normal (default)
94
RGB LED effects
Power cycling
26
Power wheel
94 RGB LED effects
Power chasing
Solid on (Default)
LED lighting portion will be changed
by the percentage of solar input
Solar input power in watt
power and nominal PV power.
If “Solid on” is selected in #94, LED
ring will light up with background
color setting in #96.
If “Power wheel” is selected in #94,
LED ring will light up in 4 levels.
If “cycling” or “chasing” is selected in
94, LED ring will light up in 12
levels.
Battery capacity percentage (Default)
LED lighting portion will be changed by battery capacity percentage. If “Solid on” is selected in #94, LED
ring will light up with background
Data Presentation of data
color setting in #96.
color
If “Power wheel” is selected in #94,
*Energy source (Grid-PV-
LED ring will light up in 4 levels.
Battery) and battery 95
charge/discharge status
If “cycling” or “chasing” is selected in #94, LED ring will light up in 12 levels.
only available when RGB
LED lighting portion will be changed by
LED effects is set to Solid on.
Load percentage.
load percentage. If “Solid on” is selected in #94, LED
ring will light up with background
color setting in #96.
If “Power wheel” is selected in #94,
LED ring will light up in 4 levels.
If “cycling” or “chasing” is selected in
94, LED ring will light up in 12
levels.
Energy source(Grid-PV-
Battery)
If selected, the LED color will be
background color setting in #96 in AC
mode. If PV power is active, the LED
color will be data color setting in #97.
If the remaining status occur, the LED
color will be set in #98.
27
Data Presentation of data Battery charge/discharge
color
status
*Energy source (Grid-PV-
Battery) and battery 95
charge/discharge status
only available when RGB
LED effects is set to Solid
on.
Pink
If selected, the LED color will be background color setting in #96 in battery
charging status. The LED color will be data color setting in #97 in battery
discharging status.
Orange
Yellow
Background color of RGB
96
Blue
LED
Purple
Green
Sky blue (Default)
Other: If selected, the background color is set by RGB via software.
Pink 97 Data Color for RGB LED
Orange
28
Yellow
Green
Blue 97 Data Color for RGB LED
Purple (Default)
Sky blue
Other: If selected, the data color is set by RGB via software.
Pink
Orange
Yellow
Background color of RGB
LED
*Only available when data
98
Blue
Presentation of data color
is set to Energy source
(Grid-PV-Battery).
Purple
Green
Sky blue (Default)
Other: If selected, the background color is set by RGB via software.
29
Timer Setting for Output Source Priority
Once access this program, it will show “OPP” in LCD. Press ” ” button
to select timer setting for output source priority. There are three timers
to set up. Press ” ” or ” ” button to select specific timer option.
Then, press ” ” to confirm timer option. Press ” ” or ” ” button
to adjust starting time first and the setting range is from 00 to 23.
Increment of each click is one hour. Press ” ” to confirm starting time setting.Next, the cursor will jump to right column to set up end
time. Once end time is set completely, press ” ” to confirmall setting.
Utility first timer
Solar first timer
99
SBU priority timer
Timer Setting for Charger Source Priority
Once access this program, it will show “CGP” in LCD. Press ” ” button to select timer setting for charger source priority. There are three
timers to set up. Press ” ” or ” ” button to select specific timer
option. Then, press ” ” to confirm timer option. Press ” ” or ” ” button to adjust starting time first and the setting range is from 00 to
23. Increment of each click is one hour. Press ” ” to confirm starting
time setting.Next, the cursor will jump to right column to set up end
time. Once end time is set completely, press ” ” to confirmall setting.
Solar first
Sloar and utility
100
Only solar
30
USB Function Setting
There are three USB function setting such as firmware upgrade, data log export and internal parameter re-
write from the USB disk. Please follow below procedure to execute selected USB function setting.
Procedure Step 1: Insert an OTG USB disk into the USB port (L).
LCD Screen
Step 2: Press ” ” button to enter USB function setting.
Step 3: Please select setting program by following the procedure.
Program#
Operation Procedure
After entering USB function setting, press ” ” button to enter
Upgrade
“upgrade firmware” function. This function is to upgrade inverter
firmware
firmware. If firmware upgrade is needed, please check with your
dealer or installer for detail instructions.
After entering USB function setting, press ” ” button to switch
Re-write
to “Re-write internal parameters” function. This function is to over-
internal
write all parameter settings (TEXT file) with settings in the USB
parameters disk from a previous setup or to duplicate inverter settings.
Please check with your dealer or installer for detail instructions.
After entering USB function setting, press ” ” button twice to
switch to “export data log” function and it will show “LOG” in the
LCD. Press ” ” button to confirm the selection for export data
log.
LCD Screen
Export data log
If the selected function is ready, LCD will display ” ” ” button to confirm the selection again.
“. Press
Press ” ” button to select “Yes” to export data log. “YES” will disappear
after this action is complete. Then, press ” ” button to return to main
screen.
Or press ” ” button to select “No” to return to main screen.
If no button is pressed for 1 minute, it will automatically return to main
screen.
Error message: Error Code Messages
No USB disk is detected.
USB disk is protected from copy.
Document inside the USB disk with wrong format.
If any error occurs, error code will only show 3 seconds. After 3 seconds, it will automatically return to display screen.
31
LCD Display
The LCD display information will be switched in turn by pressing the ” ” or ” ” button. The selectable information is switched as the following table in order.
Selectable information
LCD display
Input Voltage=230V, Input frequency=50Hz
Utility voltage/ Utility frequency
PV1 voltage=300V, PV1 current=2.0A, PV1 power=600W
Default Display Screen
PV voltage/ PV current/ PV power (PV1 and PV2 switch every 5 seconds)
PV2 voltage=300V, PV2 current=2.0A, PV2 power=600W
Battery voltage=50.4V, Bulk charging voltage=56.4V, Charging current=20A
Battery voltage, charging stage/ Configured battery parameters/ Charging or
discharging current
32
Battery voltage=53.9V, Floating charging voltage=54.0V, Charging current=1A
Battery voltage, charging stage/ Configured battery parameters/ Charging or discharging current
Battery voltage=50.4V, Low DC cut-off voltage=44.0V, Discharging current=48A
Default Display Screen
Output voltage=230V, Output frequency=50Hz
Output voltage, load in VA, load in Watt switch every 5 second/ Output frequency
Load in VA=2.4kVA, Output frequency=50Hz
33
Load in Watt=2.4kW, Output frequency=50Hz
Output voltage, load in VA, load in Watt switch every 5 second/ Output frequency
Default Display Screen
Real date Dec 14, 2020.
Real date.
Real time.
Real time 11:38.
PV energy generation today
PV energy generation today =888Wh.
34
PV energy generation this month =8.88kWh. PV energy generation this month
PV energy generation this year
PV energy generation this year =88.8kWh.
Total PV energy generation
Total PV energy generation =888kWh.
Load output energy today
Load output energy today =888Wh.
35
Load output energy this month
Load output energy this month =8.88kWh.
Load output energy this year
Load output energy this year =88.8kWh.
Total load output energy Main CPU version checking.
Total load output energy =888kWh. Main CPU version 00050.72.
36
Secondary CPU version 00022.01. Secondary CPU version checking.
Wi-Fi version checking
Wi-Fi version 00088.88.
37
Operating Mode Description
Operation mode
Description
LCD display Charging by utility and PV energy.
Charging by utility.
Standby mode Note: *Standby mode: The inverter is not turned on yet but at this time, the inverter can charge battery without AC output.
No output is supplied by the unit but it still can charge batteries.
Charging by PV energy.
No charging.
Fault mode Note: *Fault mode: Errors are caused by inside circuit error or external reasons such as over temperature, output short circuited and so on.
No charging at all no matter if grid or PV power is available.
Grid and PV power are available.
38
Operation mode
Description
LCD display Grid is available.
Fault mode Note: *Fault mode: Errors are caused by inside circuit error or external reasons such as over temperature, output short circuited and so on.
No charging at all no matter if grid or PV power is available.
PV power is available.
No charging.
Charging by utility and PV energy.
Line Mode
The unit will provide output power from the mains. It will also charge the battery at line mode.
Charging by utility.
39
Operation mode
Description
LCD display
If “SUB” (solar first) is selected as output source priority and solar energy
is not sufficient to provide the load, solar energy and the utility will
provide the loads and charge the battery at the same time.
Line Mode
The unit will provide output power from the mains. It will also charge the battery at line mode.
If either “SUB” (solar first) or “SBU” is selected as output source priority
and battery is not connected,
solar energy and the utility will provide the loads.
Power from utility
Battery Mode
Power from battery and PV energy.
The unit will provide output power from battery and/or PV power.
40
Operation mode
Description
LCD display PV energy will supply power to the loads and charge battery at the same time. No utility is available.
Battery Mode
Power from battery only.
The unit will provide output power from battery and/or PV power.
Power from PV energy only.
41
Faults Reference Code
Fault Code
Fault Event
01
Fan is locked when inverter is off.
02
Over temperature
03
Battery voltage is too high
04
Battery voltage is too low
05
Output short circuited.
06
Output voltage is too high.
07
Overload time out
08
Bus voltage is too high
09
Bus soft start failed
10
PV over current
11
PV over voltage
12
DCDC over current
13
Battery discharge over current
51
Over current
52
Bus voltage is too low
53
Inverter soft start failed
55
Over DC voltage in AC output
57
Current sensor failed
58
Output voltage is too low
Icon on
42
Warning Indicator
Warning Code
Warning Event
01
Fan is locked when inverter is on.
02
Over temperature
Audible Alarm Beep three times every second
None
03
Battery is over-charged
Beep once every second
04
Low battery
Beep once every second
Icon flashing
07
Overload
Beep once every 0.5 second
10
Output power derating
Beep twice every 3 seconds
15
PV energy is low.
Beep twice every 3 seconds
16
High AC input (>280VAC) during BUS soft start
None
32
Communication failure between inverter and display panel
None
Battery equalization
None
43
CLEARANCE AND MAINTENANCE FOR ANTI-DUST KIT Overview
Every inverter is already installed with anti-dusk kit from factory. This kit
keeps dusk from your inverter and increases product reliability in harsh
environment.
Clearance and Maintenance
Step 1: Please remove the screws on the sides of the inverter.
Step 2: Then, dustproof case can be removed and take out air filter foam as
shown in below chart.
Step 3: Clean air filter foam and dustproof case. After clearance, re-assemble
the dust-kit back to the inverter. NOTICE: The anti-dust kit should be cleaned
from dust every one month.
44
BATTERY EQUALIZATION
Equalization function is added into charge controller. It reverses the buildup
of negative chemical effects like stratification, a condition where acid
concentration is greater at the bottom of the battery than at the top.
Equalization also helps to remove sulfate crystals that might have built up on
the plates. If left unchecked, this condition, called sulfation, will reduce
the overall capacity of the battery. Therefore, it’s recommended to equalize
battery periodically. How to Apply Equalization Function You must enable
battery equalization function in monitoring LCD setting program 33 first.
Then, you may apply this function in device by either one of following
methods: 1. Setting equalization interval in program 37. 2. Active
equalization immediately in program 39. When to Equalize In float stage, when
the setting equalization interval (battery equalization cycle) is arrived, or
equalization is active immediately, the controller will start to enter
Equalize stage.
Equalize charging time and timeout In Equalize stage, the controller will
supply power to charge battery as much as possible until battery voltage
raises to battery equalization voltage. Then, constant-voltage regulation is
applied to maintain battery voltage at the battery equalization voltage. The
battery will remain in the Equalize stage until setting battery equalized time
is arrived.
However, in Equalize stage, when battery equalized time is expired and battery
voltage doesn’t rise to battery equalization voltage point, the charge
controller will extend the battery equalized time until battery voltage
achieves battery equalization voltage. If battery voltage is still lower than
battery equalization voltage when battery equalized timeout setting is over,
the charge controller will stop equalization and return to float stage.
45
SPECIFICATIONS
Table 1 Line Mode Specifications
MODEL Input Voltage Waveform Nominal Input Voltage
Low Loss Voltage
Low Loss Return Voltage
High Loss Voltage High Loss Return Voltage Max AC Input Voltage Max AC Input
Current Nominal Input Frequency Low Loss Frequency Low Loss Return Frequency
High Loss Frequency High Loss Return Frequency
Output Short Circuit Protection
Efficiency (Line Mode)
Transfer Time
Output power de-rating: For 8KW model, when AC input voltage under 170V the
output power will be derated. For 6.5KW model, when AC input voltage under
105V the output power will be derated.
6.5KW
8KW
Sinusoidal (utility or generator)
120Vac 90Vac±7V (UPS) 80Vac±7V (Appliances) 100Vac±7V (UPS); 90Vac±7V
(Appliances)
140Vac±7V
230Vac 170Vac±7V (UPS) 90Vac±7V (Appliances) 180Vac±7V (UPS); 100Vac±7V
(Appliances)
280Vac±7V
135Vac±7V
270Vac±7V
150Vac
300Vac
60A
50Hz / 60Hz (Auto detection)
40±1Hz
42±1Hz
65±1Hz
63±1Hz Line mode: Circuit Breaker (70A) Battery mode: Electronic Circuits >95% ( Rated R load, battery full charged )
10ms typical (UPS); 20ms typical (Appliances)
Output Power
Rated Power
50% Power
90V 170V 80V 105V
Input Voltage
280V 8K model 140V 6.5K model
46
Table 2 Inverter Mode Specifications
MODEL
6.5KW
8KW
Rated Output Power
6500W
8000W
Output Voltage Waveform
Pure Sine Wave
Output Voltage Regulation
120Vac±5%
230Vac±5%
Output Frequency
60Hz or 50Hz
Peak Efficiency
91%
93%
Overload Protection
Surge Capacity Low DC Warning Voltage @ load < 20%
@ 20% load < 50% @ load < 50% @ load 50%
100ms@205% load;5s@150% load; 10s@110%~150% load 2* rated power for 5 seconds
46.0Vdc 42.8Vdc
40.4Vdc
Low DC Warning Return Voltage @ load < 20%
@ 20% load < 50% @ load < 50% @ load 50% Low DC Cut-off Voltage @ load < 20%
@ 20% load < 50% @ load < 50% @ load 50%
48.0Vdc 44.8Vdc 42.4Vdc
44.0Vdc 40.8Vdc 38.4Vdc
High DC Recovery Voltage
64Vdc
High DC Cut-off Voltage
66Vdc
DC Voltage Accuracy
+/-0.3V@ no load
THDV DC Offset
<5% for linear load,<10% for non-linear load @ nominal voltage 100mV
No Load Power Consumption
<75W
47
Table 3 Charge Mode Specifications
Utility Charging Mode
MODEL
Charging Current (UPS) @ Nominal Input Voltage
Flooded
Bulk Charging Battery
Voltage
AGM / Gel
Battery
Floating Charging Voltage
Overcharge Protection
6.5KW 120A(@VI/P=120Vac)
Charging Algorithm
Battery Voltage, per cell
8KW 120A (@VI/P=230Vac)
58.4Vdc
56.4Vdc
54Vdc 66Vdc 3-Step
Charging Current, %
2.43Vdc (2.35Vdc) 2.25Vdc
Voltage
100%
Charging Curve
Solar Input MODEL Rated Power Max. PV Array Open Circuit Voltage PV Array MPPT
Voltage Range Max. Input Current Start-up Voltage
Power Limitation
50%
minimum 10mins, maximum 8hrs
Bulk (Constant Current)
Absorption (Constant Voltage)
Current
Maintenance (Floating)
Time
6.5KW 250Vdc 90Vdc~230Vdc
PV Current
8000W
18A x 2 80V +/- 5Vdc
8KW
500Vdc 90Vdc~450Vdc
18A
9A
75°
85°
MPPT temperature
48
Table 4 General Specifications
MODEL Safety Compliance Operating Temperature Range Storage temperature
Humidity Dimension (DWH), mm Net Weight, kg
6.5KW
8KW
UL
CE
-10°C to 40°C
-10°C to 50°C
-15°C~ 60°C
5% to 95% Relative Humidity (Non-condensing)
158.4x 503.6 x 530.8
20
Table 5 Parallel Specifications
Max parallel numbers
6
Circulation Current under No Load Condition
Max 2A
Power Unbalance Ratio
<5% @ 100% Load
Parallel communication
CAN
Transfer time in parallel mode
Max 50ms
Parallel Kit
YES
Note: Parallel feature will be disabled when only PV power is available.
49
TROUBLE SHOOTING
Problem Unit shuts down automatically during startup process.
No response after power on.
Mains exist but the unit works in battery mode.
LCD/LED/Buzzer LCD/LEDs and buzzer will be active for 3 seconds and then
complete off.
No indication.
Input voltage is displayed as 0 on the LCD and green LED is flashing.
Explanation / Possible cause
The battery voltage is too low (<1.91V/Cell)
1. The battery voltage is far too low. (<1.4V/Cell) 2. Battery polarity is
connected reversed.
Input protector is tripped
Green LED is flashing.
Insufficient quality of AC power. (Shore or Generator)
When the unit is turned on, internal relay is switched on and off repeatedly.
Green LED is flashing.
LCD display and LEDs are flashing
Fault code 07
Fault code 05
Set “Solar First” as the priority of output source.
Battery is disconnected.
Overload error. The inverter is overload 110% and time is up.
Output short circuited.
Fault code 02
Buzzer beeps continuously and red LED is on.
Fault code 03
Fault code 01
Fault code 06/58 Fault code 08/09/53/57 Fault code 51 Fault code 52 Fault code
55
Fault code 56
Internal temperature of inverter component is over 100°C.
Battery is over-charged.
The battery voltage is too high.
Fan fault Output abnormal (Inverter voltage below than 190Vac or is higher
than 260Vac) Internal components failed.
Over current or surge. Bus voltage is too low. Output voltage is unbalanced.
Battery is not connected well or fuse is burnt.
What to do
1. Re-charge battery. 2. Replace battery.
1. Check if batteries and the wiring are connected well. 2. Re-charge
battery. 3. Replace battery.
Check if AC breaker is tripped and AC wiring is connected well.
1. Check if AC wires are too thin and/or too long. 2. Check if generator (if
applied) is working well or if input voltage range setting is correct.
(UPSAppliance) Change output source priority to Utility first.
Check if battery wires are connected well.
Reduce the connected load by switching off some equipment. Check if wiring is
connected well and remove abnormal load. Check whether the air flow of the
unit is blocked or whether the ambient temperature is too high. Return to
repair center. Check if spec and quantity of batteries are meet requirements.
Replace the fan. 1. Reduce the connected load. 2. Return to repair center
Return to repair center.
Restart the unit, if the error happens again, please return to repair center.
If the battery is connected well, please return to repair center.
50
Appendix I: Parallel function
1. Introduction This inverter can be used in parallel with two different
operation modes. 1. Parallel operation in single phase is with up to 6 units.
The supported maximum output power for 8KW
model is 48KW/48KVA. The supported maximum output power for 6.5KW model is
39KW/39KVA. 2. Maximum six units work together to support three-phase
equipment. Maximum four units support one
phase. 3. Maximum six units work together to support split-phase equipment
only available for 6.5KW model.
Maximum 5 units support one phase application. The supported maximum output
power is 39KW/39KVA and one phase can be up to 32.5KW/32.5KVA.
2. Mounting the Unit When installing multiple units, please follow below
chart.
NOTE: For proper air circulation to dissipate heat, allow a clearance of approx. 20 cm to the side and approx. 50 cm above and below the unit. Be sure to install each unit in the same level.
3. Wiring Connection
WARNING: It’s REQUIRED to connect battery for parallel operation. The cable size of each inverter is shown as below:
Recommended battery cable and terminal size for each inverter:
Wire Size
Cable mm2
Ring Terminal Dimensions
D (mm) L (mm)
Torque value
1*2/0AWG
67.4
8.4
47
5 Nm
Ring terminal:
WARNING: Be sure the length of all battery cables is the same. Otherwise, there
will be voltage difference between inverter and battery to cause parallel inverters
not working.
Recommended AC input and output cable size for each inverter:
Model
AWG no.
Torque
6.5KW
4 AWG
1.4~ 1.6 Nm
8KW
8 AWG
1.4~ 1.6 Nm
You need to connect the cables of each inverter together. Take the battery cables for example: You need to
use a connector or bus-bar as a joint to connect the battery cables together, and then connect to the battery
terminal. The cable size used from joint to battery should be X times cable size in the tables above. “X” indicates the number of inverters connected in parallel.
Regarding AC input and output, please also follow the same principle.
CAUTION!! Please install the breaker at the battery and AC input side. This will ensure the inverter can be
51
securely disconnected during maintenance and fully protected from over current of battery or AC input. Recommended breaker specification of battery for each inverter:
Model
1 unit*
6.5KW/8KW
250A/70VDC
*If you want to use only one breaker at the battery side for the whole system, the rating of the breaker
should be X times current of 1 unit. “X” indicates the number of inverters connected in parallel.
Recommended breaker specification of AC input with single phase:
Model
2 units
3 units
4 units
5 units
6 units
6.5KW/8KW 120A/230VAC 180A/230VAC 240A/230VAC 300A/230VAC 360A/230VAC
Note 1: Also, you can use 60A breaker with only 1 unit and install one breaker at its AC input in each inverter. Note 2: Regarding three-phase system, you can use 4-pole breaker directly and the rating of the breaker should be compatible with the phase current limitation from the phase with maximum units Recommended battery capacity
Inverter parallel numbers 2
3
4
5
6
Battery Capacity
200AH 400AH 400AH 600AH 600AH
WARNING! Be sure that all inverters will share the same battery bank. Otherwise, the inverters will transfer to fault mode.
4-1. Parallel Operation in Single phase Two inverters in parallel: Power Connection
Communication Connection
1
2
52
Three inverters in parallel: Power Connection
Communication Connection
1
2
3
Four inverters in parallel: Power Connection
Communication Connection
1
2
3
4
53
Five inverters in parallel: Power Connection
Communication Connection
1
2
3
4
5
Six inverters in parallel: Power Connection
Communication Connection
1
2
3
4
5
6
54
4-2. Support 3-phase equipment
Two inverters in each phase: Power Connection
Communication Connection
P1
1
2
P2
3
4
Four inverters in one phase and one inverter for the other two phases: Power Connection
P3
5
6
Communication Connection
P1
1
2
3
P2
P3
4
5
6
55
Three inverters in one phase, two inverters in second phase and one inverter for the third phase: Power Connection
Communication Connection
P1
P2
P3
1
2
3
4
5
6
Three inverters in one phase and only one inverter for the remaining two phases: Power Connection
Communication Connection
P1
1
2
P2
P3
3
4
5
56
Two inverters in two phases and only one inverter for the remaining phase: Power Connection
Communication Connection
P1
1
2
P2
3
P3
4
5
Two inverters in one phase and only one inverter for the remaining phases: Power Connection
Communication Connection
P1
1
2
P2
3
P3
4
57
One inverter in each phase: Power Connection
Communication Connection
P1
P2
1
2
P3
3
WARNING: Do not connect the current sharing cable between the inverters which
are in different phases. Otherwise, it may damage the inverters.
4-3. Support split-phase equipment (only for 6.5KW model) Three inverters in
each phase:
Communication Connection
P1
P2
1
2
3
4
5
6
58
Two inverters in each phase: Power Connection
Communication Connection
P1
1
2
One inverter in each phase: Power Connection
P2
3
4
Communication Connection
P1
P2
1
2
5. PV Connection Please refer to user manual of single unit for PV
Connection. CAUTION: Each inverter should connect to PV modules separately.
59
6. LCD Setting and Display
Setting Program: Program Description Selectable option Single
When the unit is operated alone, please select “SIG” in program 28.
Parallel
When the units are used in parallel for single phase application, please select “PAL” in program 28. Please refer to 5-1 for detailed information.
L1 phase:
L2 phase:
AC output mode
*This setting is
able to set up
only when the L3 phase:
28
inverter is in
standby mode.
Be sure that
on/off switch is
in “OFF” status.
When the units are operated in 3-phase application, please choose “3PX” to
define each inverter. It is required to have at least 3 inverters or maximum 6
inverters to support threephase equipment. It’s required to have at least one
inverter in each phase or it’s up to four inverters in one phase. Please
refers to 4-2 for detailed information. Please select “3P1” in program 28 for
the inverters connected to L1 phase, “3P2” in program 28 for the inverters
connected to L2 phase and “3P3” in program 28 for the inverters connected to
L3 phase.
Be sure to connect share current cable to units which are on the same phase.
Do NOT connect share current cable between units on different phases.
L1 for split phase:
L2 for split phase: (120° phase difference)
L2 for split phase: (180° phase difference)
When the units are operated in split phase application, please choose “2PX” to
define each inverter. These options are only available for 6.5KW model. It is
required to have at least 2 inverters or maximum 6 inverters to support
splitphase equipment. It’s required to have at least one inverter in each
phase or it’s up to three inverters in one phase. Please refers to 4-3 for
detailed information. Please select “2P1” in program 28 for the inverters
connected to L1 phase, “2P2” in program 28 for the inverters connected to L2
phase. And it can choose 120°or 180° phase difference for “2P2”.
Be sure to connect share current cable to units which are on the same phase.
Do NOT connect share current cable
between units on different phases.
60
Fault code display: Fault Code
Fault Event
60
Power feedback protection
71
Firmware version inconsistent
72
Current sharing fault
80
CAN fault
81
Host loss
82
Synchronization loss
83
Battery voltage detected different
84
AC input voltage and frequency detected different
85
AC output current unbalance
86
AC output mode setting is different
Icon on
Code Reference: Code
Description
NE
Unidentified unit master or slave
HS
Master unit
SL
Slave unit
Icon on
7. Commissioning
Parallel in single phase
Step 1: Check the following requirements before commissioning: Correct wire
connection Ensure all breakers in Line wires of load side are open and each
Neutral wires of each unit are
connected together.
Step 2: Turn on each unit and set “PAL” in LCD setting program 28 of each
unit. And then shut down all units.
NOET: It’s necessary to turn off switch when setting LCD program. Otherwise,
the setting cannot be programmed.
Step 3: Turn on each unit. LCD display in Master unit
LCD display in Slave unit
61
NOTE: Master and slave units are randomly defined.
Step 4: Switch on all AC breakers of Line wires in AC input. It’s better to have all inverters connect to utility at
the same time. If not, it will display fault 82 in following-order inverters. However, these inverters will
automatically restart. If detecting AC connection, they will work normally.
LCD display in Master unit
LCD display in Slave unit
Step 5: If there is no more fault alarm, the parallel system is completely installed.
Step 6: Please switch on all breakers of Line wires in load side. This system will start to provide power to the load.
Support three-phase equipment
Step 1: Check the following requirements before commissioning:
Correct wire connection Ensure all breakers in Line wires of load side are open and each Neutral wires of each unit are
connected together.
Step 2: Turn on all units and configure LCD program 28 as P1, P2 and P3 sequentially. And then shut down
all units.
NOET: It’s necessary to turn off switch when setting LCD program. Otherwise, the setting cannot be programmed.
Step 3: Turn on all units sequentially.
LCD display in L1-phase unit
LCD display in L2-phase unit
LCD display in L3-phase unit
Step 4: Switch on all AC breakers of Line wires in AC input. If AC connection is detected and three phases are
matched with unit setting, they will work normally. Otherwise, the AC icon will flash and they will not
work in line mode.
LCD display in L1-phase unit
LCD display in L2-phase unit
LCD display in L3-phase unit
Step 5: If there is no more fault alarm, the system to support 3-phase
equipment is completely installed.
Step 6: Please switch on all breakers of Line wires in load side. This system
will start to provide power to the load.
Note 1: To avoid overload occurring, before turning on breakers in load side,
it’s better to have whole system in operation first. Note 2: Transfer time for
this operation exists. Power interruption may happen to critical devices,
which cannot bear transfer time.
62
8. Trouble shooting
Situation
Fault Fault
Event
Solution
Code Description
1. Restart the inverter.
2. Check if L/N cables are not connected reversely in all inverters.
60
Current feedback into the inverter is detected.
3. For parallel system in single phase, make sure the sharing are connected in all inverters. For supporting three-phase system, make sure the sharing cables are connected in the inverters in the same phase, and disconnected in
the inverters in different phases.
4. If the problem remains, please contact your installer.
1. Update all inverter firmware to the same version.
71
The firmware version of each inverter is not the same.
2. 3.
Check the version of each inverter via LCD setting and make sure the CPU versions are same. If not, please contact your instraller to provide the firmware to update. After updating, if the problem still remains, please contact your
installer.
72
The output current of each inverter is different.
1. Check if sharing cables are connected well and restart the inverter. 2. If the problem remains, please contact your installer.
80 81
82
CAN data loss Host data loss Synchronization data loss
1. Check if communication cables are connected well and restart the inverter.
2. If the problem remains, please contact your installer.
1. Make sure all inverters share same groups of batteries together.
2. Remove all loads and disconnect AC input and PV input. Then, check
The battery voltage of
battery voltage of all inverters. If the values from all inverters are
83
each inverter is not
close, please check if all battery cables are the same length and
the same.
same material type. Otherwise, please contact your installer to
provide SOP to calibrate battery voltage of each inverter.
3. If the problem still remains, please contact your installer.
1. Check the utility wiring conncetion and restart the inverter.
AC input voltage and 2. Make sure utility starts up at same time. If there are breakers
84
frequency are
installed between utility and inverters, please be sure all breakers
detected different.
can be turned on AC input at same time.
3. If the problem remains, please contact your installer.
1. Restart the inverter.
85
AC output current unbalance
2. Remove some excessive loads and re-check load information from LCD of inverters. If the values are different, please check if AC input and output cables are in the same length and material type.
3. If the problem remains, please contact your installer.
1. Switch off the inverter and check LCD setting #28.
2. For parallel system in single phase, make sure no 3P1, 3P2 or 3P3 is
86
AC output mode setting is different.
set on #28.
For upporting three-phase system, make sure no “PAL” is set on #28.
3. If the problem remains, please contact your installer.
63
Appendix II: BMS Communication Installation
1. Introduction If connecting to lithium battery, it is recommended to
purchase a custom-made RJ45 communication cable. Please check with your dealer
or integrator for details.
This custom-made RJ45 communication cable delivers information and signal
between lithium battery and the inverter. These information are listed below:
Re-configure charging voltage, charging current and battery discharge cut-off
voltage according to the
lithium battery parameters. Have the inverter start or stop charging according
to the status of lithium battery.
2. Pin Assignment for BMS Communication Port
Definition
PIN 1
RS232TX
PIN 2
RS232RX
PIN 3
RS485B
PIN 4
NC
PIN 5
RS485A
PIN 6
CANH
PIN 7
CANL
PIN 8
GND
3. Lithium Battery Communication Configuration LIO-4810-150A
ESS LIO-I 4810 ID switch
ID switch
ID Switch indicates the unique ID code for each battery module. It’s required
to assign a unique ID to each battery module for normal operation. We can set
up the ID code for each battery module by rotating the PIN number on the ID
switch. From number 0 to 9, the number can be random; no particular order.
Maximum 10 battery modules can be operated in parallel.
64
PYLONTECH
Dip Switch: There are 4 Dip Switches that sets different baud rate and battery
group address. If switch
position is turned to the “OFF” position, it means “0”. If switch position is
turned to the “ON” position, it means “1”.
Dip 1 is “ON” to represent the baud rate 9600. Dip 2, 3 and 4 are reserved for
battery group address. Dip switch 2, 3 and 4 on master battery (first battery)
are to set up or change the group address.
NOTE: “1” is upper position and “0” is bottom position.
Dip 1
Dip 2 Dip 3 Dip 4 Group address
0
0
0
Single group only. It’s required to set up master battery with this
setting and slave batteries are unrestricted.
1
0
0
Multiple group condition. It’s required to set up master battery on the
1: RS485
first group with this setting and slave batteries are unrestricted.
baud
0
1
0
Multiple group condition. It’s required to set up master battery on the
rate=9600
second group with this setting and slave batteries are unrestricted.
Restart to 1
1
0
Multiple group condition. It’s required to set up master battery on the third group with this setting and slave batteries are unrestricted.
take effect 0
0
1
Multiple group condition. It’s required to set up master battery on the
fourth group with this setting and slave batteries are unrestricted.
1
0
1
Multiple group condition. It’s required to set up master battery on the
fifth group with this setting and slave batteries are unrestricted.
NOTE: The maximum groups of lithium battery is 5 and for maximum number for each group, please check with battery manufacturer.
65
4. Installation and Operation LIO-4810-150A/ESS LIO-I 4810 After ID no. is
assigned for each battery module, please set up LCD panel in inverter and
install the wiring connection as following steps. Step 1: Use supplied RJ11
signal cable to connect into the extension port ( P1 or P2 ).
Step 2: Use supplied RJ45 cable (from battery module package) to connect
inverter and Lithium battery.
- For multiple battery connection, please check battery manual for the details. Note for parallel system: 1. Only support common battery installation. 2. Use custom-made RJ45 cable to connect any inverter (no need to connect to a specific inverter) and
Lithium battery. Simply set this inverter battery type to “LIB” in LCD program
- Others should be “USE”. Step 3: Turn the breaker switch “ON”. Now, the
battery module is ready for DC output.
Step 4: Press Power on/off button on battery module for 5 secs, the battery module will start up. *If the manual button cannot be approached, just simply turn on the inverter module. The battery module will be automatically turned on.
66
Step 5: Turn on the inverter.
Step 6. Be sure to select battery type as “LIB” in LCD program 5.
If communication between the inverter and battery is successful, the battery icon flash. Generally speaking, it will take longer than 1 minute to establish communication.
on LCD display will
PYLONTECH After configuration, please install LCD panel with inverter and Lithium battery with the following steps. Step 1. Use custom-made RJ45 cable to connect inverter and Lithium battery.
Note for parallel system: 3. Only support common battery installation. 4. Use
custom-made RJ45 cable to connect any inverter (no need to connect to a
specific inverter) and
Lithium battery. Simply set this inverter battery type to “PYL” in LCD program
5. Others should be “USE”.
67
Step 2. Switch on Lithium battery. Step 3. Press more than three seconds to start Lithium battery, power output ready. Step 4. Turn on the inverter.
Step 5. Be sure to select battery type as “PYL” in LCD program 5.
If communication between the inverter and battery is successful, the battery icon flash. Generally speaking, it will take longer than 1 minute to establish communication.
on LCD display will
Active Function This function is to activate lithium battery automatically while commissioning. After battery wiring and commissioning is successfully, if battery is not detected, the inverter will automatically activate battery if the inverter is powered on.
68
4. LCD Display Information
Press ” ” or ” ” button to switch LCD display information. It will show battery pack and battery group
number before “Main CPU version checking” as shown below.
Selectable information
LCD display
Battery pack numbers & Battery Battery pack numbers = 3, battery group numbers = 1
group numbers
5. Code Reference
Related information code will be displayed on LCD screen. Please check inverter LCD screen for the operation.
Code
Description
If battery status is not allowed to charge and discharge after the communication
between the inverter and battery is successful, it will show code 60 to stop charging
and discharging battery.
Communication lost (only available when the battery type is not setting as “AGM”,
“Flooded” or “User-Defined”.) After battery is connected, communication signal is not detected for 3
minutes, buzzer will beep. After 10 minutes, inverter will stop charging and
discharging to lithium battery.
Communication lost occurs after the inverter and battery is connected
successfully, buzzer beeps immediately.
If battery status is not allowed to charge after the communication between the
inverter and battery is successful, it will show code 69 to stop charging battery.
If battery status must to be charged after the communication between the inverter and battery is successful, it will show code 70 to charge battery.
If battery status is not allowed to discharge after the communication between the inverter and battery is successful, it will show code 71 to stop discharging battery.
69
Appendix III: The Wi-Fi Operation Guide
1. Introduction Wi-Fi module can enable wireless communication between off-
grid inverters and monitoring platform. Users have complete and remote
monitoring and controlling experience for inverters when combining Wi-Fi
module with WatchPower APP, available for both iOS and Android based device.
All data loggers and parameters are saved in iCloud. The major functions of
this APP: Delivers device status during normal operation. Allows to configure
device setting after installation. Notifies users when a warning or alarm
occurs. Allows users to query inverter history data.
2. WatchPower App 2-1. Download and install APP
Operating system requirement for your smart phone: iOS system supports iOS 9.0
and above Android system supports Android 5.0 and above
Please scan the following QR code with your smart phone and download
WatchPower App.
Android
iOS system
system
Or you may find “WatchPower” app from the Apple® Store or “WatchPower Wi-Fi” in Google® Play Store.
2-2. Initial Setup Step 1: Registration at first time
After the installation, please tap the shortcut icon
to access this APP on your mobile screen. In the
screen, tap “Register” to access “User Registration” page. Fill in all required information and scan the Wi-Fi
module PN by tapping
icon. Or you can simply enter PN directly. Then, tap “Register” button.
70
Then, a “Registration success” window will pop up. Tap “Go now” to continue
setting local Wi-Fi network connection.
Step 2: Local Wi-Fi Module Configuration Now, you are in “Wi-Fi Config” page.
There are detailed setup procedure listed in “How to connect?” section and you
may follow it to connect Wi-Fi.
Enter the “SettingsWi-Fi” and select connected Wi-Fi name. The connected Wi-Fi name is the same to your Wi-Fi PN number and enter default password “12345678”.
Then, return to WatchPower APP and tap ” connected successfully.
Step 3: Wi-Fi Network settings
” button when Wi-Fi module is
Tap
icon to select your local Wi-Fi router name (to access the internet) and enter password.
Step 4: Tap “Confirm” to complete the Wi-Fi configuration between the Wi-Fi module and the Internet. 71
If the connection fails, please repeat Step 2 and 3.
Diagnose Function
If the module is not monitoring properly, please tap ”
” on the top right corner of the screen for further
details. It will show repair suggestion. Please follow it to fix the problem. Then, repeat the steps in the chapter
4.2 to re-set network setting. After all setting, tap “Rediagnosis” to re- connect again.
72
2-3. Login and APP Main Function After finishing the registration and local
Wi-Fi configuration, enter registered name and password to login. Note: Tick
“Remember Me” for your login convenience afterwards.
Overview After login is successfully, you can access “Overview” page to have
overview of your monitoring devices, including overall operation situation and
Energy information for Current power and Today power as below diagram.
Devices
Tap the icon (located on the bottom) to enter Device List page. You can review all devices here by adding
or deleting Wi-Fi Module in this page.
Add device
Delete device
73
Tap icon on the top right corner and manually enter part number to add device.
This part number label is pasted on the bottom of inverter. After entering
part number, tap “Confirm” to add this device in the Device list.
Part number label is pasted on the bottom of inverter.
For more information about Device List, please refer to the section 2.4. ME In
ME page, users can modify “My information”, includingUser’s Photo,Account
security, Modify password,Clear cache,andLog-out, shown as below diagrams.
2-4. Device List In Device List page, you can pull down to refresh the device
information and then tap any device you want to check up for its real-time
status and related information as well as to change parameter settings. Please
refer to the parameter setting list.
74
Device Mode On the top of screen, there is a dynamic power flow chart to show
live operation. It contains five icons to present PV power, inverter, load,
utility and battery. Based on your inverter model status, there will beStandby
Mode,Line Mode,Battery Mode. Standby ModeInverter will not power the load
until “ON” switch is pressed. Qualified utility or PV source can charge
battery in standby mode.
Line ModeInverter will power the load from the utility with or without PV
charging. Qualified utility or PV source can charge battery.
Battery ModeInverter will power the load from the batter with or without PV
charging. Only PV source can charge battery.
Device Alarm and Name Modification
In this page, tap the
icon on the top right corner to enter the device alarm page. Then, you can review
alarm history and detailed information. Tap the icon on the top right corner, a blank input box will pop out. Then, you can edit the name for your device and tap “Confirm” to complete name modification.
75
Device Information Data Users can check up Basic Information,Product
Information,Rated information,History, andWiFi Module Informationby swiping
left.
Swipe left
Basic Informationdisplays basic information of the inverter, including AC
voltage, AC frequency, PV input voltage, Battery voltage, Battery capacity,
Charging current, Output voltage, Output frequency, Output apparent power,
Output active power and Load percent. Please slide up to see more basic
information. Production Informationdisplays Model type (Inverter type), Main
CPU version, Bluetooth CPU version and secondary CPU version. Rated
Informationdisplays information of Nominal AC voltage, Nominal AC current,
Rated battery voltage, Nominal output voltage, Nominal output frequency,
Nominal output current, Nominal output apparent power and Nominal output
active power. Please slide up to see more rated information. Historydisplays
the record of unit information and setting timely. Wi-Fi Module
Informationdisplays of Wi-Fi Module PN, status and firmware version. Parameter
Setting This page is to activate some features and set up parameters for
inverters. Please be noted that the listing in “Parameter Setting” page in
below diagram may differ from the models of monitored inverter. Here will
briefly highlight some of it,Output Setting,Battery Parameter Setting,Enable/
Disable items, Restore to the defaultsto illustrate.
There are three ways to modify setting and they vary according to each
parameter. a) Listing options to change values by tapping one of it. b)
Activate/Shut down functions by clicking “Enable” or “Disable” button. c)
Changing values by clicking arrows or entering the numbers directly in the
column.
Each function setting is saved by clicking “Set” button. 76
Please refer to below parameter setting list for an overall description and be noted that the available parameters may vary depending on different models. Please always see the original product manual for detailed setting instructions. Parameter setting list:
Item
Description
Output setting Output source To configure load power source priority.
priority
AC input range When selecting “UPS”, it’s allowed to connect personal computer.
Please check product manual for details.
Output voltage
When selecting “Appliance”, it’s allowed to connect home appliances. To set output voltage.
Output
To set output frequency.
frequency
Battery
Battery type:
To set connected battery type.
parameter
Battery cut-off To set the battery stop discharging voltage.
setting
voltage
Please see product manual for the recommended voltage range
based on connected battery type.
Back to grid voltage
When “SBU” or “SOL” is set as output source priority and battery voltage is lower than this setting voltage, unit will transfer to line mode
and the grid will provide power to load.
Back to discharge
When “SBU” or “SOL” is set as output source priority and battery voltage is higher than this setting voltage, battery will be allowed to
voltage
discharge.
Charger source To configure charger source priority.
priority:
Max. charging
current Max. AC charging current: Float charging
It’s to set up battery charging parameters. The selectable values in different
inverter model may vary.
Please see product manual for the details.
voltage Bulk charging voltage
Battery
It’s to set up battery charging parameters. The selectable values in different
inverter model may vary. Please see product manual for the details.
Enable or disable battery equalization function.
equalization
Real-time Activate Battery
It’s real-time action to activate battery equalization.
Equalization
Equalized Time To set up the duration time for battery equalization.
Out
Equalized Time To set up the extended time to continue battery equalization.
Equalization
To set up the frequency for battery equalization.
Period
Equalization
To set up the battery equalization voltage.
Voltage
77
Enable/Disable Functions
RGB LED Setting Restore to the default
LCD Auto-return If enable, LCD screen will return to its main screen after one minute
to Main screen automatically.
Fault Code
If enabled, fault code will be recorded in the inverter when any fault
Record
happens.
Backlight
If disabled, LCD backlight will be off when panel button is not
operated for 1 minute.
Bypass Function If enabled, unit will transfer to line mode when overload happened in
battery mode.
Beeps while
If enabled, buzzer will alarm when primary source is abnormal.
primary source
interrupt
Over
If disabled, the unit won’t be restarted after over-temperature fault is
Temperature
solved.
Auto Restart
Overload Auto Restart
If disabled, the unit won’t be restarted after overload occurs.
Buzzer
If disabled, buzzer won’t be on when alarm/fault occurred.
Enable/disable Turn on or off RGB LEDs
Brightness
Adjust the lighting brightness
Speed
Adjust the lighting speed
Effects
Change the light effects
Color Selection Adjust color by setting RGB value
This function is to restore all settings back to default settings.
78
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>