solinved 6.5KW Solar Inverter Charger User Manual

June 9, 2024
solinved

6.5KW Solar Inverter Charger

error
{
“error”: {
“message”: “You exceeded your current quota, please check your plan and billing details.”,
“type”: “insufficient_quota”,
“param”: null,
“code”: null
}
}

the following is the text from the user manual / instructions:
User Manual
6.5KW / 8KW SOLAR INVERTER / CHARGER
Version: 1.4
Table of Contents
ABOUT THIS MANUAL …………………………………………………………………………………………………………………….. 1 Purpose………………………………………………………………………………………………………………………………………… 1 Scope …………………………………………………………………………………………………………………………………………… 1
SAFETY INSTRUCTIONS………………………………………………………………………………………………………………….. 1 INTRODUCTION ………………………………………………………………………………………………………………………………. 2
ABOUT THIS MANUAL Purpose
This manual describes the assembly, installation, operation and troubleshooting of this unit. Please read this manual carefully before installations and operations. Keep this manual for future reference.
Scope
This manual provides safety and installation guidelines as well as information on tools and wiring.
SAFETY INSTRUCTIONS
WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.
1. Before using the unit, read all instructions and cautionary markings on the unit, the batteries and all appropriate sections of this manual.
3. Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
4. To reduce risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
size. It’s very important to correctly operate this inverter/charger. 8. Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop
a tool to spark or short circuit batteries or other electrical parts and could cause an explosion. 9. Please strictly follow installation procedure when you want to disconnect AC or DC terminals. Please
refer to INSTALLATION section of this manual for the details. 10. Fuses are provided as over-current protection for the battery supply. 11. GROUNDING INSTRUCTIONS -This inverter/charger should be connected to a permanent grounded
wiring system. Be sure to comply with local requirements and regulation to install this inverter. 12. NEVER cause AC output and DC input short circuited. Do NOT connect to the mains when DC input
short circuits. 13. Warning!! Only qualified service persons are able to service this device. If errors still persist after
following troubleshooting table, please send this inverter/charger back to local dealer or service center for maintenance.
14. WARNING: Because this inverter is non-isolated, only three types of PV modules are acceptable:
single crystalline, poly crystalline with class A-rated and CIGS modules. To avoid any malfunction, do not connect any PV modules with possible current leakage to the inverter. For example, grounded PV modules will cause current leakage to the inverter. When using CIGS modules, please be sure NO grounding. 15. CAUTION: It’s required to use PV junction box with surge protection. Otherwise, it will cause damage on inverter when lightning occurs on PV modules.

User Manual
6.5KW / 8KW SOLAR INVERTER / CHARGER
Version: 1.4

Table of Contents
ABOUT THIS MANUAL …………………………………………………………………………………………………………………….. 1 Purpose………………………………………………………………………………………………………………………………………… 1 Scope …………………………………………………………………………………………………………………………………………… 1
SAFETY INSTRUCTIONS………………………………………………………………………………………………………………….. 1 INTRODUCTION ………………………………………………………………………………………………………………………………. 2
Features ……………………………………………………………………………………………………………………………………….. 2 Basic System Architecture ………………………………………………………………………………………………………………. 2 Product Overview…………………………………………………………………………………………………………………………… 3 Unpacking and Inspection ………………………………………………………………………………………………………………. 4 Mounting the Unit …………………………………………………………………………………………………………………………… 4 Preparation …………………………………………………………………………………………………………………………………… 5 Battery Connection ………………………………………………………………………………………………………………………… 5 AC Input/Output Connection ……………………………………………………………………………………………………………. 6 PV Connection ………………………………………………………………………………………………………………………………. 8 Final Assembly…………………………………………………………………………………………………………………………….. 10 DC Output Connectors………………………………………………………………………………………………………………….. 10 Communication Connection…………………………………………………………………………………………………………… 11 Dry Contact Signal ……………………………………………………………………………………………………………………….. 12 OPERATION…………………………………………………………………………………………………………………………………… 13 Power ON/OFF ……………………………………………………………………………………………………………………………. 13 Operation and Display Panel …………………………………………………………………………………………………………. 13 LCD Display Icons ……………………………………………………………………………………………………………………….. 14 LCD Setting…………………………………………………………………………………………………………………………………. 16 LCD Display ………………………………………………………………………………………………………………………………… 32 Operating Mode Description ………………………………………………………………………………………………………….. 38 Faults Reference Code …………………………………………………………………………………………………………………. 42 Warning Indicator …………………………………………………………………………………………………………………………. 43 CLEARANCE AND MAINTENANCE FOR ANTI-DUST KIT…………………………………………………………………. 44 Overview …………………………………………………………………………………………………………………………………….. 44 Clearance and Maintenance ………………………………………………………………………………………………………….. 44 BATTERY EQUALIZATION ……………………………………………………………………………………………………………… 45 SPECIFICATIONS …………………………………………………………………………………………………………………………… 46 Table 1 Line Mode Specifications ……………………………………………………………………………………………………. 46 Table 2 Inverter Mode Specifications ………………………………………………………………………………………………. 47 Table 3 Charge Mode Specifications………………………………………………………………………………………………… 48 Table 4 General Specifications………………………………………………………………………………………………………… 49 TROUBLE SHOOTING ……………………………………………………………………………………………………………………. 50 Appendix I: Parallel function ………………………………………………………………………………………………………….. 51 Appendix II: BMS Communication Installation………………………………………………………………………………… 64 Appendix III: The Wi-Fi Operation Guide…………………………………………………………………………………………. 70

ABOUT THIS MANUAL Purpose
This manual describes the assembly, installation, operation and troubleshooting of this unit. Please read this manual carefully before installations and operations. Keep this manual for future reference.
Scope
This manual provides safety and installation guidelines as well as information on tools and wiring.
SAFETY INSTRUCTIONS
WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.
1. Before using the unit, read all instructions and cautionary markings on the unit, the batteries and all appropriate sections of this manual.
2. CAUTION ­ To reduce risk of injury, charge only deep-cycle lead acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
3. Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
4. To reduce risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
5. CAUTION ­ Only qualified personnel can install this device with battery. 6. NEVER charge a frozen battery. 7. For optimum operation of this inverter/charger, please follow required spec to select appropriate cable
size. It’s very important to correctly operate this inverter/charger. 8. Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop
a tool to spark or short circuit batteries or other electrical parts and could cause an explosion. 9. Please strictly follow installation procedure when you want to disconnect AC or DC terminals. Please
refer to INSTALLATION section of this manual for the details. 10. Fuses are provided as over-current protection for the battery supply. 11. GROUNDING INSTRUCTIONS -This inverter/charger should be connected to a permanent grounded
wiring system. Be sure to comply with local requirements and regulation to install this inverter. 12. NEVER cause AC output and DC input short circuited. Do NOT connect to the mains when DC input
short circuits. 13. Warning!! Only qualified service persons are able to service this device. If errors still persist after
following troubleshooting table, please send this inverter/charger back to local dealer or service center for maintenance.
14. WARNING: Because this inverter is non-isolated, only three types of PV modules are acceptable:
single crystalline, poly crystalline with class A-rated and CIGS modules. To avoid any malfunction, do not connect any PV modules with possible current leakage to the inverter. For example, grounded PV modules will cause current leakage to the inverter. When using CIGS modules, please be sure NO grounding. 15. CAUTION: It’s required to use PV junction box with surge protection. Otherwise, it will cause damage on inverter when lightning occurs on PV modules.
1

INTRODUCTION
This is a multi-function inverter, combining functions of inverter, solar charger and battery charger to offer uninterruptible power support in a single package. The comprehensive LCD display offers user-configurable and easy- accessible button operations such as battery charging current, AC or solar charging priority, and acceptable input voltage based on different applications.
Features
Pure sine wave inverter Customizable status LED ring with RGB lights Touchable button with 5″ colored LCD Built-in Wi-Fi for mobile monitoring (APP is required) Supports USB On-the-Go function Built-in anti-dusk kit Reserved communication ports for BMS (RS485, CAN-BUS, RS232) Configurable input voltage ranges for home appliances and personal computers via LCD control panel Configurable output usage timer and prioritization Configurable charger source priority via LCD control panel Configurable battery charging current based on applications via LCD control panel Compatible to utility mains or generator power
Basic System Architecture
The following illustration shows basic application for this unit. It also required the following devices to have a complete running system:
Generator or Utility mains. PV modules Consult with your system integrator for other possible system architectures depending on your requirements. This inverter can power various appliances in home or office environment, including motor-type appliances such as tube light, fan, refrigerator and air conditioners.
Figure 1 Basic hybrid PV System Overview
2

Product Overview
NOTE: For parallel installation and operation, please check Appendix I. 1. RGB LED ring (refer to LCD Setting section for the details) 2. LCD display 3. Touchable function keys 4. PV connectors 5. AC input connectors 6. AC output connectors (Load connection) 7. Battery connectors 8. Current sharing port 9. Parallel communication port 10. Power switch 11. Dry contact 12. USB port as USB communication port and USB function port 13. RS-232 communication port 14. BMS communication port: CAN, RS-485 or RS-232 15. DC output connectors 16. Power switch for DC output
3

INSTALLATION
Unpacking and Inspection
Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. You should have received the following items inside of package:

Inverter unit Manual software CD RS-232 cable Parallel communication cable

Current sharing cable

DC Fuse

Cable gland x 4 pcs PV connectors x 2 sets Mounting bracket Mounting ear x 2 M5 screw x 6 pcs

Mounting the Unit
Consider the following points before selecting where to install: Do not mount the inverter on flammable construction
materials. Mount on a solid surface Install this inverter at eye level in order to allow the LCD
display to be read at all times. The ambient temperature should be between 0°C and 55°C
to ensure optimal operation. The recommended installation position is to be adhered to
the wall vertically. Be sure to keep other objects and surfaces as shown in the
right diagram to guarantee sufficient heat dissipation and to
have enough space for removing wires.

SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.

Please follow below steps to install the inverter on the wall.

Step 1: Install the mounting Step 2: Install the mounting ears

bracket by fixing six pieces of M5 on the back of the unit with four

screws.

supplied M5 screws.

Step 3: Raise the inverter and place it over the mounting bracket.

4

Step 4: Removing bottom cover with six screws as shown below chart.

Step 5: Fix the inverter to mounting bracket by screwing two supplied M5 screws as shown below chart.

Step 6: Assemble the bottom cover back to original position.

Preparation
Before connecting all wirings, please take off wiring cover by removing six screws. When removing the bottom cover, be carefully to remove two cables as shown below.

Battery Connection

CAUTION: For safety operation and regulation compliance, it’s requested to install a separate DC over-current

protector or disconnect device between battery and inverter. It may not be requested to have a disconnect

device in some applications, however, it’s still requested to have over- current protection installed. Please refer

to typical amperage in below table as required fuse or breaker size.

Ring terminal:

WARNING! All wiring must be performed by a qualified personnel.
WARNING! It’s very important for system safety and efficient operation to use appropriate cable for battery connection. To reduce risk of injury, please use the proper recommended cable and terminal size as below.

Recommended battery cable and terminal size:

Model

Typical Amperage

Battery capacity

Wire Size

6.5KW

153A

250AH

1*2/0AWG

8KW

182.2A

250AH

1*2/0AWG

Cable mm2
67
67.4

Ring Terminal Dimensions
D (mm) L (mm)

8.4

51

8.4

51

Torque value
5 Nm 5 Nm

5

Please follow below steps to implement battery connection: 1. Assemble battery ring terminal based on recommended battery cable and terminal size. 2. Fix two cable glands into positive and negative terminals. 3. Insert the ring terminal of battery cable flatly into battery connector of inverter and make sure the nuts are
tightened with torque of 5 Nm. Make sure polarity at both the battery and the inverter/charge is correctly connected and ring terminals are tightly screwed to the battery terminals.

WARNING: Shock Hazard Installation must be performed with care due to high battery voltage in series.
CAUTION!! Do not place anything between the flat part of the inverter terminal and the ring terminal. Otherwise, overheating may occur. CAUTION!! Do not apply anti-oxidant substance on the terminals before terminals are connected tightly. CAUTION!! Before making the final DC connection or closing DC breaker/disconnector, be sure positive (+) must be connected to positive (+) and negative (-) must be connected to negative (-).

AC Input/Output Connection
CAUTION!! Before connecting to AC input power source, please install a separate AC breaker between inverter and AC input power source. This will ensure the inverter can be securely disconnected during maintenance and fully protected from over current of AC input. CAUTION!! There are two terminal blocks with “IN” and “OUT” markings. Please do NOT mis-connect input and output connectors.

WARNING! All wiring must be performed by a qualified personnel. WARNING! It’s very important for system safety and efficient operation to use appropriate cable for AC input connection. To reduce risk of injury, please use the proper recommended cable size as below. Suggested cable requirement for AC wires

Model

Gauge

Torque Value

6.5KW

4 AWG

1.4~ 1.6Nm

8KW

8 AWG

1.4~ 1.6Nm

Please follow below steps to implement AC input/output connection: 1. Before making AC input/output connection, be sure to open DC protector or disconnector first. 2. Remove insulation sleeve 10mm for six conductors. And shorten phase L and neutral conductor N 3 mm. 3. Fix two cable glands into input and output sides. 4. Insert AC input wires according to polarities indicated on terminal block and tighten the terminal screws.
Be sure to connect PE protective conductor ( ) first.
Ground (yellow-green) LLINE (brown or black) NNeutral (blue)

6

WARNING: Be sure that AC power source is disconnected before attempting to hardwire it to the unit. 5. Then, insert AC output wires according to polarities indicated on terminal block and tighten terminal screws. Be sure to connect PE protective conductor ( ) first. Ground (yellow-green) LLINE (brown or black) NNeutral (blue)
6. Make sure the wires are securely connected. CAUTION: Important Be sure to connect AC wires with correct polarity. If L and N wires are connected reversely, it may cause utility short-circuited when these inverters are worked in parallel operation. CAUTION: Appliances such as air conditioner requires at least 2~3 minutes to restart because it’s required to have enough time to balance refrigerant gas inside of circuits. If a power shortage occurs and recovers in a short time, it will cause damage to your connected appliances. To prevent this kind of damage, please check manufacturer of air conditioner if it’s equipped with time-delay function before installation. Otherwise, this inverter/charger will be trigger overload fault and cut off output to protect your appliance but sometimes it still causes internal damage to the air conditioner.
7

PV Connection
CAUTION: Before connecting to PV modules, please install separately DC circuit breakers between inverter and PV modules. NOTE1: Please use 600VDC/30A circuit breaker. NOTE2: The overvoltage category of the PV input is II. Please follow the steps below to implement PV module connection:
WARNING: Because this inverter is non-isolated, only three types of PV modules are acceptable: single crystalline and poly crystalline with class A-rated and CIGS modules. To avoid any malfunction, do not connect any PV modules with possible current leakage to the inverter. For example, grounded PV modules will cause current leakage to the inverter. When using CIGS modules, please be sure NO grounding. CAUTION: It’s required to use PV junction box with surge protection. Otherwise, it will cause damage on inverter when lightning occurs on PV modules. Step 1: Check the input voltage of PV array modules. This system is applied with two strings of PV array. Please make sure that the maximum current load of each PV input connector is 18A. CAUTION: Exceeding the maximum input voltage can destroy the unit!! Check the system before wire connection. Step 2: Disconnect the circuit breaker and switch off the DC switch. Step 3: Assemble provided PV connectors with PV modules by the following steps. Components for PV connectors and Tools: Female connector housing
Female terminal Male connector housing
Male terminal Crimping tool and spanner
Prepare the cable and follow the connector assembly process: Strip one cable 8 mm on both end sides and be careful NOT to nick conductors.
Insert striped cable into female terminal and crimp female terminal as shown below.
Insert assembled cable into female connector housing as shown below.
Insert striped cable into male terminal and crimp male terminal as shown below.
Insert assembled cable into male connector housing as shown below.
Then, use spanner to screw pressure dome tightly to female connector and male connector as shown below.
8

Step 4: Check correct polarity of connection cable from PV modules and PV input connectors. Then, connect positive pole (+) of connection cable to positive pole (+) of PV input connector. Connect negative pole (-) of connection cable to negative pole (-) of PV input connector.

WARNING! For safety and efficiency, it’s very important to use appropriate cables for PV module connection.

To reduce risk of injury, please use the proper cable size as recommended below.

Model

Wire Size

Cable mm2

8KW

10~12 AWG

4~6

CAUTION: Never directly touch the terminals of inverter. It might cause lethal electric shock.

Recommended Panel Configuration When selecting proper PV modules, please be sure to consider the following parameters: 1. Open circuit Voltage (Voc) of PV modules not to exceed maximum PV array open circuit voltage of the
inverter. 2. Open circuit Voltage (Voc) of PV modules should be higher than the start-up voltage.

INVERTER MODEL

6.5KW

8KW

Max. PV Array Power

8000W

Max. PV Array Open Circuit Voltage

250Vdc

500Vdc

PV Array MPPT Voltage Range

90Vdc~230Vdc

90Vdc~450Vdc

Start-up Voltage (Voc)

80Vdc

Recommended solar panel configuration for 6.5KW model:

Solar Panel Spec. (reference) – 330Wp – Vmp: 33.7Vdc – Imp: 9.79A – Voc: 39.61Vdc – Isc: 10.4A – Cells: 60

SOLAR INPUT 1

SOLAR INPUT 2

Min in series: 3pcs, per input Max. in series:6pcs, per input

3pcs in series

x

x

3pcs in series

6pcs in series

x

x

6pcs in series

6pcs in series

6pcs in series

6pcs in series, 2 strings

x

Q’ty of panels
3pcs 3pcs 6pcs 6pcs 12pcs 12pcs

x

6pcs in series, 2 strings

12pcs

6pcs in series, 2 strings 6pcs in series, 2 strings

24pcs

Total Input Power
990W 990W 1980W 1980W 3960W 3960W 3960W 7920W

9

Recommended solar panel configuration for 8KW model:

Solar Panel Spec.

SOLAR INPUT 1

SOLAR INPUT 2

(reference)

Min in series: 4pcs, per input

Q’ty of panels

– 250Wp

Max. in series: 12pcs, per input

– Vmp: 30.7Vdc

4pcs in series

x

4pcs

– Imp: 8.3A – Voc: 37.7Vdc – Isc: 8.4A – Cells: 60

x 12pcs in series
x 6pcs in series

4pcs in series x
12pcs in series 6pcs in series

4pcs 12pcs 12pcs 12pcs

6pcs in series, 2 strings

x

12pcs

x

6pcs in series, 2 strings

12pcs

8pcs in series, 2 strings

x

16pcs

x

8pcs in series, 2 strings

16pcs

9pcs in series, 1 string 9pcs in series, 1 string

18pcs

10pcs in series, 1 string 10pcs in series, 1 string

20pcs

12pcs in series, 1 string 12pcs in series, 1 string

24pcs

6pcs in series, 2 strings 6pcs in series, 2 strings

24pcs

7pcs in series, 2 strings 7pcs in series, 2 strings

28pcs

8pcs in series, 2 strings 8pcs in series, 2 strings

32pcs

Total Input Power
1000W 1000W 3000W 3000W 3000W 3000W 3000W 4000W 4000W 4500W 5000W 6000W 6000W 7000W 8000W

Final Assembly
After connecting all wirings, re-connect two cables and then put bottom cover back by fixing six screws as shown below.

DC Output Connectors
These DC output connectors are used to provide emergency power backup to all kinds of DC-powered equipment such as routers, modems, set-top box, VOIP phone systems, surveillance system, alarm system, access control system and many critical telecom equipment. There are 3 channels (current limit at 3A for each channel), which could be activated/disabled manually either through LCD operation or power switch beside the DC jacks. Supplied dimension of DC jack (male) is OD 5.5mm, ID 2.5mm.
10

Communication Connection
Follow below chart to connect all communication wiring.

RS-232 communication to PC
USB communication to PC

BMS communication

Serial Connection Please use the supplied serial cable to connect between the inverter and your PC. Install the monitoring software from the bundled CD and follow the on-screen instructions to complete your installation. For detailed software operation, refer to the software user manual on the bundled CD.
Wi-Fi Connection This unit is equipped with a Wi-Fi transmitter. Wi-Fi transmitter can enable wireless communication between off-grid inverters and monitoring platform. Users can access and control the monitored inverter with downloaded APP. You may find “WatchPower” app from the Apple® Store or “WatchPower Wi-Fi” in Google® Play Store. All data loggers and parameters are saved in iCloud. For quick installation and operation, please refer to Appendix III – The Wi-Fi Operation Guide for details.

BMS Communication Connection It is recommended to purchase a special communication cable if you are connecting to Lithium-Ion battery banks. Please refer to Appendix II – BMS Communication Installation for details.
11

Dry Contact Signal
There is one dry contact (3A/250VAC) available on the rear panel. It could be used to deliver signal to external device when battery voltage reaches warning level.

Unit Status

Condition

Power Off Power On

Unit is off and no output is powered.

Output is

Program 01 Battery voltage < Low DC

powered

set as USB warning voltage

from Battery (utility first) Battery voltage > Setting

power or

or SUB (solar value in Program 13 or

Solar energy. first)

battery charging reaches

floating stage

Program 01 Battery voltage < Setting

is set as SBU value in Program 12

(SBU priority) Battery voltage > Setting

value in Program 13 or

battery charging reaches

floating stage

Dry contact port:

NC & C Close

NO & C Open

Open

Close

Close

Open

Open

Close

Close

Open

12

OPERATION
Power ON/OFF
Once the unit has been properly installed and the batteries are connected well, simply press power switch to turn on the unit.

Operation and Display Panel
The operation and the LCD module, shown in the chart below, includes one RGB LED ring, one power switch, four touchable function keys and a LCD display to indicate the operating status and input/output power information.
RGB LED ring
LCD display Touchable function keys
Power switch

Touchable Function Keys Function Key ESC Access USB setting mode Up Down Enter

Description To exit the setting To enter USB setting mode To last selection To next selection To confirm/enter the selection in setting mode
13

LCD Display Icons

Battery Information

Indicates battery level by 0-24%, 25-49%, 50-74% and 75-100% in battery

mode and charging status in line mode.

When battery is charging, it will present battery charging status.

Status
C.C. mode C.V. mode

Battery voltage <2V/cell 2 ~ 2.083V/cell
2.083 ~ 2.167V/cell

2.167 V/cell

LCD Display 4 bars will flash in turns. The right bar will be on and the other three bars will flash in turns. The right two bars will be on and the other two bars will flash in turns.
The right three bars will be on and the left bar will
flash.

Floating mode. Batteries are fully charged. 4 bars will be on.

In battery mode, it will present battery capacity.

Load Percentage Battery Voltage

LCD Display

< 1.85V/cell

Load >50%

1.85V/cell ~ 1.933V/cell 1.933V/cell ~ 2.017V/cell

2.017V/cell

< 1.892V/cell

Load < 50%

1.892V/cell ~ 1.975V/cell 1.975V/cell ~ 2.058V/cell

2.058V/cell Load Information
Indicates overload.

Indicates the load level by 0-24%, 25-49%, 50-74% and 75-100%.

14

Charger Source Priority Setting Display
Indicates setting program 16 “Charger source priority” is selected as “Solar first”.
Indicates setting program 16 “Charger source priority” is selected as “Solar and Utility”.
Indicates setting program 16 “Charger source priority” is selected as “Solar only”. Output source priority setting display
Indicates setting program 01 “Output source priority” is selected as “Utility first”.

Indicates setting program 01 “Output source priority” is selected as “Solar first”.

Indicates setting program 01 “Output source priority” is selected as “SBU”.

AC Input Voltage Range Setting Display

Indicates setting program 03 is selected as ”

“. The acceptable

AC input voltage range will be within 170-280VAC for 8KW and 90-

140VAC for 6.5KW.

Indicates setting program 03 is selected as ”

“. The acceptable

AC input voltage range will be within 90-280VAC for 8KW and 80-

140VAC for 6.5KW.

Operation Status Information

Indicates unit connects to the mains.

Indicates unit connects to the PV panel.
Indicates battery type. Indicates parallel operation is working. Indicates unit alarm is disabled. Indicates Wi-Fi transmission is working. Indicates USB disk is connected.

15

LCD Setting
General Setting
After pressing and holding ” ” button for 3 seconds, the unit will enter the Setup Mode. Press ” ” or ” ” button to select setting programs. Press ” ” button to confirm you selection or ” ” button to exit.

Setting Programs:

Program

Description

Selectable option Escape

00

Exit setting mode

Utility first (default)

Solar first

Output source priority:

01

To configure load power

source priority

SBU priority

Maximum charging current: 60A (default)

To configure total charging

current for solar and utility

02

chargers.

(Max. charging current =

utility charging current +

solar charging current)

16

Utility will provide power to the loads as first priority. Solar and battery energy will provide power to the loads only when utility power is not available.
Solar energy provides power to the loads as first priority. If solar energy is not sufficient to power all connected loads, Utility energy will supply power to the loads at the same time.
Solar energy provides power to the loads as first priority. If solar energy is not sufficient to power all connected loads, battery energy will supply power to the loads at the same time. Utility provides power to the loads only when battery voltage drops to either lowlevel warning voltage or the setting point in program 12.
Setting range is from 10A to 120A for 6.5KW model and from 10A to 150A for 8KW model. Increment of each click is 10A.

Appliances (default)

03

AC input voltage range

UPS

AGM (default)

If selected, acceptable AC input voltage range will be within 90-280VAC for 8KW and 80-140VAC for 6.5KW..
If selected, acceptable AC input voltage range will be within 170-280VAC for 8KW and 90-140VAC for 6.5KW.
Flooded

05

Battery type

User-Defined PylonTech battery WECO battery Soltaro battery
17

If “User-Defined” is selected, battery charge voltage and low DC cut-off voltage can be set up in program 26, 27 and 29.
If selected, programs of 02, 26, 27 and 29 will be automatically set up. No need for further setting.
If selected, programs of 02, 12, 26, 27 and 29 will be auto-configured per battery supplier recommended. No need for further adjustment.
If selected, programs of 02, 26, 27 and 29 will be automatically set up. No need for further setting.

05

Battery type

LIb-protocol compatible battery 3rd party Lithium battery

Select “LIb” if using Lithium battery compatible to Lib protocol. If selected, programs of 02, 26, 27 and 29 will be automatically set up. No need for further setting. If selected, programs of 02, 26, 27 and 29 will be automatically set up. No need for further setting. Please contact the battery supplier for installation procedure.

Restart disable (default)

Restart enable

06

Auto restart when overload occurs

Restart disable (default)

07

Auto restart when over temperature occurs

Restart enable

09

Output frequency

50Hz (default for 8KW model)

60Hz (default for 6.5KW model)

Available options for 6.5KW model

110V

120V (default)

10

Output voltage

127V

18

Available options for 8KW model

220V

230V (default)

10

Output voltage

240V

Maximum utility charging current

30A (default)

Note: If setting value in

11

program 02 is smaller than

that in program in 11, the

inverter will apply charging

current from program 02

for utility charger.

46V (default)

Setting voltage point back

12

to utility source when selecting “SBU” (SBU

priority) in program 01.

Setting range is from 2A, then 10A to 120A. Increment of each click is 10A.
Setting range is from 44V to 51V. Increment of each click is 1V.

Setting range is FUL and from 48V to 62V. Increment of each

click is 1V.

Battery fully charged Setting voltage point back

54V (default)

to battery mode when 13
selecting “SBU” (SBU

priority) in program 01.

If this inverter/charger is working in Line, Standby or Fault

mode, charger source can be programmed as below:

Solar first

Solar energy will charge

Charger source priority:

battery as first priority.

16

To configure charger

Utility will charge battery only

source priority

when solar energy is not

available.

19

Solar and Utility (default)

Solar energy and utility will charge battery at the same time.

Charger source priority:

16

To configure charger

source priority

Only Solar

Solar energy will be the only charger source no matter utility is available or not.

18

Alarm control

Alarm on (default)

Alarm off

19

Auto return to default display screen

Return to default display screen (default)

If selected, no matter how users switch display screen, it will automatically return to default display screen after no button is pressed for 1 minute.

Stay at latest screen

If selected, the display screen will stay at latest screen user finally switches.

20

Backlight control

Backlight on (default)

Backlight off

20

Alarm on (default)

22

Beeps while primary source is interrupted

Alarm off

Bypass disable (default)

Overload bypass:

When enabled, the unit will

23

transfer to line mode if

overload occurs in battery

mode.

Record enable (default)

25

Record Fault code

Bypass enable Record disable

26

Bulk charging voltage (C.V voltage)

56.4V (default)

If user-defined is selected in program 5, this program can be set up. Setting range is from 48.0V to 62.0V. Increment of each click is 0.1V.

54V (default)

27

Floating charging voltage

If user-defined is selected in program 5, this program can be set up. Setting range is from 48.0V to 62.0V. Increment of each click is 0.1V.

Single: This inverter is used in Parallel: This inverter is

single phase application.

operated in parallel system.

AC output mode

*This setting is only

28

available when the inverter

is in standby mode (Switch

off).

21

When the inverter is operated in 3-phase application, set up

inverter to be operated in specific phase.

L1 phase:

L2 phase:

L3 phase:

AC output mode *This setting is only

When the inverter is operation in split phase application, set up

28

available when the inverter inverter to be operated in specific phase. These options are only

is in standby mode (Switch available for 6.5KW model. off).
L1 for split phase:

L2 for split phase:

(120° phase difference)

L2 for split phase: (180° phase difference)

Low DC cut-off voltage:

42.0V (default)

If battery power is only

power source available,

inverter will shut down.

If PV energy and

battery power are

29

available, inverter will

charge battery without

AC output.

If PV energy, battery power

and utility are all available,

inverter will transfer to line

mode

22

If user-defined is selected in program 5, this program can be set up. Setting range is from 42.0V to 48.0V. Increment of each click is 0.1V. Low DC cutoff voltage will be fixed to setting value no matter what percentage of load is connected.

Battery equalization

Battery equalization disable (default)

30

Battery equalization

If “Flooded” or “User-Defined” is selected in program 05, this

program can be set up.

58.4V (default)

Setting range is from 48.0V to

62.0V. Increment of each click is

0.1V.

31

Battery equalization voltage

60min (default)

33

Battery equalized time

Setting range is from 5 min to 900 min. Increment of each click is 5 min.

120min (default)

34

Battery equalized timeout

Setting range is from 5 min to 900 min. Increment of each click is 5 min.

35

Equalization interval

30days (default)

Setting range is from 0 to 90 days. Increment of each click is 1 day

36

Equalization activated immediately

Enable

Disable (default)

23

If equalization function is enabled in program 30, this program
can be set up. If “Enable” is selected in this program, it’s to activate battery equalization immediately and LCD main page will

show ” “. If “Disable” is selected, it will cancel equalization function until next activated equalization time arrives based on

program 35 setting. At this time, ” ” will not be shown in LCD

main page.

Not reset(Default)

Reset

Reset all stored data for PV

37

generated power and

output load energy

Disable (Default)

If selected, battery discharge protection is disabled.

41

Maximum battery discharging current

30A 150A

The setting range is from 30 A to 150 A. Increment of each click is 10A. If discharging current is higher than setting value, battery will stop discharging. At this time, if the utility is available, the inverter will operate in bypass mode. If no utility is available, the inverter will shut down output after 5-minute operation in battery mode.

Enable (default) On/Off control for 12V DC 82 output

83

Erase all data log

Not reset (Default)

Disable Reset

24

3 minutes

5 minutes

10 minutes (default)

Data log recorded interval

*The maximum data log

84

number is 1440. If it’s over

1440, it will re-write the

first log.

30 minutes

20 minutes 60 minutes

85

Time setting ­ Minute

86

Time setting ­ Hour

87

Time setting­ Day

88

Time setting­ Month

For minute setting, the range is from 0 to 59.
For hour setting, the range is from 0 to 23.
For day setting, the range is from 1 to 31.
For month setting, the range is from 1 to 12.

25

89

Time setting ­ Year

Enabled (default)

On/Off control for RGB LED

91

*It’s required to enable this

setting to activate RGB LED

lighting function.

Low

For year setting, the range is from 17 to 99. Disable
Normal (default)

92

Brightness of RGB LED

High

Low

93

Lighting speed of RGB LED

High

Normal (default)

94

RGB LED effects

Power cycling

26

Power wheel

94 RGB LED effects

Power chasing

Solid on (Default)

LED lighting portion will be changed

by the percentage of solar input

Solar input power in watt

power and nominal PV power.

If “Solid on” is selected in #94, LED

ring will light up with background

color setting in #96.

If “Power wheel” is selected in #94,

LED ring will light up in 4 levels.

If “cycling” or “chasing” is selected in

94, LED ring will light up in 12

levels.

Battery capacity percentage (Default)

LED lighting portion will be changed by battery capacity percentage. If “Solid on” is selected in #94, LED

ring will light up with background

Data Presentation of data

color setting in #96.

color

If “Power wheel” is selected in #94,

*Energy source (Grid-PV-

LED ring will light up in 4 levels.

Battery) and battery 95
charge/discharge status

If “cycling” or “chasing” is selected in #94, LED ring will light up in 12 levels.

only available when RGB

LED lighting portion will be changed by

LED effects is set to Solid on.

Load percentage.

load percentage. If “Solid on” is selected in #94, LED

ring will light up with background

color setting in #96.

If “Power wheel” is selected in #94,

LED ring will light up in 4 levels.

If “cycling” or “chasing” is selected in

94, LED ring will light up in 12

levels.

Energy source(Grid-PV-

Battery)

If selected, the LED color will be

background color setting in #96 in AC

mode. If PV power is active, the LED

color will be data color setting in #97.

If the remaining status occur, the LED

color will be set in #98.

27

Data Presentation of data Battery charge/discharge

color

status

*Energy source (Grid-PV-

Battery) and battery 95
charge/discharge status

only available when RGB

LED effects is set to Solid

on.

Pink

If selected, the LED color will be background color setting in #96 in battery charging status. The LED color will be data color setting in #97 in battery discharging status.
Orange

Yellow

Background color of RGB

96

Blue

LED

Purple

Green
Sky blue (Default)
Other: If selected, the background color is set by RGB via software.

Pink 97 Data Color for RGB LED

Orange

28

Yellow

Green

Blue 97 Data Color for RGB LED
Purple (Default)

Sky blue
Other: If selected, the data color is set by RGB via software.

Pink

Orange

Yellow

Background color of RGB

LED

*Only available when data

98

Blue

Presentation of data color

is set to Energy source

(Grid-PV-Battery).

Purple

Green
Sky blue (Default)
Other: If selected, the background color is set by RGB via software.

29

Timer Setting for Output Source Priority

Once access this program, it will show “OPP” in LCD. Press ” ” button

to select timer setting for output source priority. There are three timers

to set up. Press ” ” or ” ” button to select specific timer option.

Then, press ” ” to confirm timer option. Press ” ” or ” ” button

to adjust starting time first and the setting range is from 00 to 23.

Increment of each click is one hour. Press ” ” to confirm starting time setting.Next, the cursor will jump to right column to set up end

time. Once end time is set completely, press ” ” to confirmall setting.

Utility first timer

Solar first timer

99

SBU priority timer

Timer Setting for Charger Source Priority

Once access this program, it will show “CGP” in LCD. Press ” ” button to select timer setting for charger source priority. There are three

timers to set up. Press ” ” or ” ” button to select specific timer

option. Then, press ” ” to confirm timer option. Press ” ” or ” ” button to adjust starting time first and the setting range is from 00 to

23. Increment of each click is one hour. Press ” ” to confirm starting

time setting.Next, the cursor will jump to right column to set up end

time. Once end time is set completely, press ” ” to confirmall setting.

Solar first

Sloar and utility

100

Only solar

30

USB Function Setting

There are three USB function setting such as firmware upgrade, data log export and internal parameter re-

write from the USB disk. Please follow below procedure to execute selected USB function setting.

Procedure Step 1: Insert an OTG USB disk into the USB port (L).

LCD Screen

Step 2: Press ” ” button to enter USB function setting.

Step 3: Please select setting program by following the procedure.

Program#

Operation Procedure

After entering USB function setting, press ” ” button to enter

Upgrade

“upgrade firmware” function. This function is to upgrade inverter

firmware

firmware. If firmware upgrade is needed, please check with your

dealer or installer for detail instructions.

After entering USB function setting, press ” ” button to switch

Re-write

to “Re-write internal parameters” function. This function is to over-

internal

write all parameter settings (TEXT file) with settings in the USB

parameters disk from a previous setup or to duplicate inverter settings.

Please check with your dealer or installer for detail instructions.

After entering USB function setting, press ” ” button twice to

switch to “export data log” function and it will show “LOG” in the

LCD. Press ” ” button to confirm the selection for export data

log.

LCD Screen

Export data log

If the selected function is ready, LCD will display ” ” ” button to confirm the selection again.

“. Press

Press ” ” button to select “Yes” to export data log. “YES” will disappear after this action is complete. Then, press ” ” button to return to main screen.
Or press ” ” button to select “No” to return to main screen.
If no button is pressed for 1 minute, it will automatically return to main screen.

Error message: Error Code Messages
No USB disk is detected.

USB disk is protected from copy.

Document inside the USB disk with wrong format.

If any error occurs, error code will only show 3 seconds. After 3 seconds, it will automatically return to display screen.

31

LCD Display

The LCD display information will be switched in turn by pressing the ” ” or ” ” button. The selectable information is switched as the following table in order.

Selectable information

LCD display

Input Voltage=230V, Input frequency=50Hz

Utility voltage/ Utility frequency

PV1 voltage=300V, PV1 current=2.0A, PV1 power=600W

Default Display Screen

PV voltage/ PV current/ PV power (PV1 and PV2 switch every 5 seconds)

PV2 voltage=300V, PV2 current=2.0A, PV2 power=600W

Battery voltage=50.4V, Bulk charging voltage=56.4V, Charging current=20A Battery voltage, charging stage/ Configured battery parameters/ Charging or discharging current
32

Battery voltage=53.9V, Floating charging voltage=54.0V, Charging current=1A

Battery voltage, charging stage/ Configured battery parameters/ Charging or discharging current

Battery voltage=50.4V, Low DC cut-off voltage=44.0V, Discharging current=48A

Default Display Screen

Output voltage=230V, Output frequency=50Hz

Output voltage, load in VA, load in Watt switch every 5 second/ Output frequency

Load in VA=2.4kVA, Output frequency=50Hz

33

Load in Watt=2.4kW, Output frequency=50Hz

Output voltage, load in VA, load in Watt switch every 5 second/ Output frequency

Default Display Screen

Real date Dec 14, 2020.

Real date.

Real time.

Real time 11:38.

PV energy generation today

PV energy generation today =888Wh.

34

PV energy generation this month =8.88kWh. PV energy generation this month

PV energy generation this year

PV energy generation this year =88.8kWh.

Total PV energy generation

Total PV energy generation =888kWh.

Load output energy today

Load output energy today =888Wh.

35

Load output energy this month

Load output energy this month =8.88kWh.

Load output energy this year

Load output energy this year =88.8kWh.

Total load output energy Main CPU version checking.

Total load output energy =888kWh. Main CPU version 00050.72.

36

Secondary CPU version 00022.01. Secondary CPU version checking.

Wi-Fi version checking

Wi-Fi version 00088.88.

37

Operating Mode Description

Operation mode

Description

LCD display Charging by utility and PV energy.

Charging by utility.

Standby mode Note: *Standby mode: The inverter is not turned on yet but at this time, the inverter can charge battery without AC output.

No output is supplied by the unit but it still can charge batteries.

Charging by PV energy.

No charging.

Fault mode Note: *Fault mode: Errors are caused by inside circuit error or external reasons such as over temperature, output short circuited and so on.

No charging at all no matter if grid or PV power is available.

Grid and PV power are available.

38

Operation mode

Description

LCD display Grid is available.

Fault mode Note: *Fault mode: Errors are caused by inside circuit error or external reasons such as over temperature, output short circuited and so on.

No charging at all no matter if grid or PV power is available.

PV power is available.

No charging.

Charging by utility and PV energy.

Line Mode

The unit will provide output power from the mains. It will also charge the battery at line mode.

Charging by utility.

39

Operation mode

Description

LCD display
If “SUB” (solar first) is selected as output source priority and solar energy is not sufficient to provide the load, solar energy and the utility will provide the loads and charge the battery at the same time.

Line Mode

The unit will provide output power from the mains. It will also charge the battery at line mode.

If either “SUB” (solar first) or “SBU” is selected as output source priority and battery is not connected,
solar energy and the utility will provide the loads.

Power from utility

Battery Mode

Power from battery and PV energy.
The unit will provide output power from battery and/or PV power.

40

Operation mode

Description

LCD display PV energy will supply power to the loads and charge battery at the same time. No utility is available.

Battery Mode

Power from battery only.
The unit will provide output power from battery and/or PV power.

Power from PV energy only.

41

Faults Reference Code

Fault Code

Fault Event

01

Fan is locked when inverter is off.

02

Over temperature

03

Battery voltage is too high

04

Battery voltage is too low

05

Output short circuited.

06

Output voltage is too high.

07

Overload time out

08

Bus voltage is too high

09

Bus soft start failed

10

PV over current

11

PV over voltage

12

DCDC over current

13

Battery discharge over current

51

Over current

52

Bus voltage is too low

53

Inverter soft start failed

55

Over DC voltage in AC output

57

Current sensor failed

58

Output voltage is too low

Icon on

42

Warning Indicator

Warning Code

Warning Event

01

Fan is locked when inverter is on.

02

Over temperature

Audible Alarm Beep three times every second
None

03

Battery is over-charged

Beep once every second

04

Low battery

Beep once every second

Icon flashing

07

Overload

Beep once every 0.5 second

10

Output power derating

Beep twice every 3 seconds

15

PV energy is low.

Beep twice every 3 seconds

16

High AC input (>280VAC) during BUS soft start

None

32

Communication failure between inverter and display panel

None

Battery equalization

None

43

CLEARANCE AND MAINTENANCE FOR ANTI-DUST KIT Overview
Every inverter is already installed with anti-dusk kit from factory. This kit keeps dusk from your inverter and increases product reliability in harsh environment.
Clearance and Maintenance
Step 1: Please remove the screws on the sides of the inverter.
Step 2: Then, dustproof case can be removed and take out air filter foam as shown in below chart.
Step 3: Clean air filter foam and dustproof case. After clearance, re-assemble the dust-kit back to the inverter. NOTICE: The anti-dust kit should be cleaned from dust every one month.
44

BATTERY EQUALIZATION
Equalization function is added into charge controller. It reverses the buildup of negative chemical effects like stratification, a condition where acid concentration is greater at the bottom of the battery than at the top. Equalization also helps to remove sulfate crystals that might have built up on the plates. If left unchecked, this condition, called sulfation, will reduce the overall capacity of the battery. Therefore, it’s recommended to equalize battery periodically. How to Apply Equalization Function You must enable battery equalization function in monitoring LCD setting program 33 first. Then, you may apply this function in device by either one of following methods: 1. Setting equalization interval in program 37. 2. Active equalization immediately in program 39. When to Equalize In float stage, when the setting equalization interval (battery equalization cycle) is arrived, or equalization is active immediately, the controller will start to enter Equalize stage.
Equalize charging time and timeout In Equalize stage, the controller will supply power to charge battery as much as possible until battery voltage raises to battery equalization voltage. Then, constant-voltage regulation is applied to maintain battery voltage at the battery equalization voltage. The battery will remain in the Equalize stage until setting battery equalized time is arrived.
However, in Equalize stage, when battery equalized time is expired and battery voltage doesn’t rise to battery equalization voltage point, the charge controller will extend the battery equalized time until battery voltage achieves battery equalization voltage. If battery voltage is still lower than battery equalization voltage when battery equalized timeout setting is over, the charge controller will stop equalization and return to float stage.
45

SPECIFICATIONS
Table 1 Line Mode Specifications
MODEL Input Voltage Waveform Nominal Input Voltage
Low Loss Voltage
Low Loss Return Voltage
High Loss Voltage High Loss Return Voltage Max AC Input Voltage Max AC Input Current Nominal Input Frequency Low Loss Frequency Low Loss Return Frequency High Loss Frequency High Loss Return Frequency
Output Short Circuit Protection
Efficiency (Line Mode)
Transfer Time
Output power de-rating: For 8KW model, when AC input voltage under 170V the output power will be derated. For 6.5KW model, when AC input voltage under 105V the output power will be derated.

6.5KW

8KW

Sinusoidal (utility or generator)

120Vac 90Vac±7V (UPS) 80Vac±7V (Appliances) 100Vac±7V (UPS); 90Vac±7V (Appliances)
140Vac±7V

230Vac 170Vac±7V (UPS) 90Vac±7V (Appliances) 180Vac±7V (UPS); 100Vac±7V (Appliances)
280Vac±7V

135Vac±7V

270Vac±7V

150Vac

300Vac

60A

50Hz / 60Hz (Auto detection)

40±1Hz

42±1Hz

65±1Hz

63±1Hz Line mode: Circuit Breaker (70A) Battery mode: Electronic Circuits >95% ( Rated R load, battery full charged )

10ms typical (UPS); 20ms typical (Appliances)

Output Power

Rated Power
50% Power

90V 170V 80V 105V

Input Voltage
280V 8K model 140V 6.5K model

46

Table 2 Inverter Mode Specifications

MODEL

6.5KW

8KW

Rated Output Power

6500W

8000W

Output Voltage Waveform

Pure Sine Wave

Output Voltage Regulation

120Vac±5%

230Vac±5%

Output Frequency

60Hz or 50Hz

Peak Efficiency

91%

93%

Overload Protection
Surge Capacity Low DC Warning Voltage @ load < 20%
@ 20% load < 50% @ load < 50% @ load 50%

100ms@205% load;5s@150% load; 10s@110%~150% load 2* rated power for 5 seconds
46.0Vdc 42.8Vdc
40.4Vdc

Low DC Warning Return Voltage @ load < 20%
@ 20% load < 50% @ load < 50% @ load 50% Low DC Cut-off Voltage @ load < 20%
@ 20% load < 50% @ load < 50% @ load 50%

48.0Vdc 44.8Vdc 42.4Vdc
44.0Vdc 40.8Vdc 38.4Vdc

High DC Recovery Voltage

64Vdc

High DC Cut-off Voltage

66Vdc

DC Voltage Accuracy

+/-0.3V@ no load

THDV DC Offset

<5% for linear load,<10% for non-linear load @ nominal voltage 100mV

No Load Power Consumption

<75W

47

Table 3 Charge Mode Specifications

Utility Charging Mode

MODEL

Charging Current (UPS) @ Nominal Input Voltage

Flooded

Bulk Charging Battery

Voltage

AGM / Gel

Battery

Floating Charging Voltage

Overcharge Protection

6.5KW 120A(@VI/P=120Vac)

Charging Algorithm

Battery Voltage, per cell

8KW 120A (@VI/P=230Vac)

58.4Vdc

56.4Vdc
54Vdc 66Vdc 3-Step

Charging Current, %

2.43Vdc (2.35Vdc) 2.25Vdc

Voltage

100%

Charging Curve
Solar Input MODEL Rated Power Max. PV Array Open Circuit Voltage PV Array MPPT Voltage Range Max. Input Current Start-up Voltage
Power Limitation

50%

minimum 10mins, maximum 8hrs

Bulk (Constant Current)

Absorption (Constant Voltage)

Current
Maintenance (Floating)

Time

6.5KW 250Vdc 90Vdc~230Vdc
PV Current

8000W
18A x 2 80V +/- 5Vdc

8KW
500Vdc 90Vdc~450Vdc

18A

9A

75°

85°

MPPT temperature

48

Table 4 General Specifications
MODEL Safety Compliance Operating Temperature Range Storage temperature Humidity Dimension (DWH), mm Net Weight, kg

6.5KW

8KW

UL

CE

-10°C to 40°C

-10°C to 50°C

-15°C~ 60°C

5% to 95% Relative Humidity (Non-condensing)

158.4x 503.6 x 530.8

20

Table 5 Parallel Specifications

Max parallel numbers

6

Circulation Current under No Load Condition

Max 2A

Power Unbalance Ratio

<5% @ 100% Load

Parallel communication

CAN

Transfer time in parallel mode

Max 50ms

Parallel Kit

YES

Note: Parallel feature will be disabled when only PV power is available.

49

TROUBLE SHOOTING

Problem Unit shuts down automatically during startup process.
No response after power on.
Mains exist but the unit works in battery mode.

LCD/LED/Buzzer LCD/LEDs and buzzer will be active for 3 seconds and then complete off.
No indication.
Input voltage is displayed as 0 on the LCD and green LED is flashing.

Explanation / Possible cause
The battery voltage is too low (<1.91V/Cell)
1. The battery voltage is far too low. (<1.4V/Cell) 2. Battery polarity is connected reversed.
Input protector is tripped

Green LED is flashing.

Insufficient quality of AC power. (Shore or Generator)

When the unit is turned on, internal relay is switched on and off repeatedly.

Green LED is flashing.
LCD display and LEDs are flashing

Fault code 07

Fault code 05

Set “Solar First” as the priority of output source.
Battery is disconnected.
Overload error. The inverter is overload 110% and time is up.
Output short circuited.

Fault code 02

Buzzer beeps continuously and red LED is on.

Fault code 03
Fault code 01
Fault code 06/58 Fault code 08/09/53/57 Fault code 51 Fault code 52 Fault code 55
Fault code 56

Internal temperature of inverter component is over 100°C.
Battery is over-charged.
The battery voltage is too high.
Fan fault Output abnormal (Inverter voltage below than 190Vac or is higher than 260Vac) Internal components failed.
Over current or surge. Bus voltage is too low. Output voltage is unbalanced.
Battery is not connected well or fuse is burnt.

What to do
1. Re-charge battery. 2. Replace battery.
1. Check if batteries and the wiring are connected well. 2. Re-charge battery. 3. Replace battery.
Check if AC breaker is tripped and AC wiring is connected well.
1. Check if AC wires are too thin and/or too long. 2. Check if generator (if applied) is working well or if input voltage range setting is correct. (UPSAppliance) Change output source priority to Utility first.
Check if battery wires are connected well.
Reduce the connected load by switching off some equipment. Check if wiring is connected well and remove abnormal load. Check whether the air flow of the unit is blocked or whether the ambient temperature is too high. Return to repair center. Check if spec and quantity of batteries are meet requirements. Replace the fan. 1. Reduce the connected load. 2. Return to repair center
Return to repair center.
Restart the unit, if the error happens again, please return to repair center.
If the battery is connected well, please return to repair center.

50

Appendix I: Parallel function
1. Introduction This inverter can be used in parallel with two different operation modes. 1. Parallel operation in single phase is with up to 6 units. The supported maximum output power for 8KW
model is 48KW/48KVA. The supported maximum output power for 6.5KW model is 39KW/39KVA. 2. Maximum six units work together to support three-phase equipment. Maximum four units support one
phase. 3. Maximum six units work together to support split-phase equipment only available for 6.5KW model.
Maximum 5 units support one phase application. The supported maximum output power is 39KW/39KVA and one phase can be up to 32.5KW/32.5KVA.
2. Mounting the Unit When installing multiple units, please follow below chart.

NOTE: For proper air circulation to dissipate heat, allow a clearance of approx. 20 cm to the side and approx. 50 cm above and below the unit. Be sure to install each unit in the same level.

3. Wiring Connection

WARNING: It’s REQUIRED to connect battery for parallel operation. The cable size of each inverter is shown as below:

Recommended battery cable and terminal size for each inverter:

Wire Size

Cable mm2

Ring Terminal Dimensions
D (mm) L (mm)

Torque value

1*2/0AWG

67.4

8.4

47

5 Nm

Ring terminal:

WARNING: Be sure the length of all battery cables is the same. Otherwise, there

will be voltage difference between inverter and battery to cause parallel inverters

not working.

Recommended AC input and output cable size for each inverter:

Model

AWG no.

Torque

6.5KW

4 AWG

1.4~ 1.6 Nm

8KW

8 AWG

1.4~ 1.6 Nm

You need to connect the cables of each inverter together. Take the battery cables for example: You need to

use a connector or bus-bar as a joint to connect the battery cables together, and then connect to the battery

terminal. The cable size used from joint to battery should be X times cable size in the tables above. “X” indicates the number of inverters connected in parallel.

Regarding AC input and output, please also follow the same principle.

CAUTION!! Please install the breaker at the battery and AC input side. This will ensure the inverter can be

51

securely disconnected during maintenance and fully protected from over current of battery or AC input. Recommended breaker specification of battery for each inverter:

Model

1 unit*

6.5KW/8KW

250A/70VDC

*If you want to use only one breaker at the battery side for the whole system, the rating of the breaker

should be X times current of 1 unit. “X” indicates the number of inverters connected in parallel.

Recommended breaker specification of AC input with single phase:

Model

2 units

3 units

4 units

5 units

6 units

6.5KW/8KW 120A/230VAC 180A/230VAC 240A/230VAC 300A/230VAC 360A/230VAC

Note 1: Also, you can use 60A breaker with only 1 unit and install one breaker at its AC input in each inverter. Note 2: Regarding three-phase system, you can use 4-pole breaker directly and the rating of the breaker should be compatible with the phase current limitation from the phase with maximum units Recommended battery capacity

Inverter parallel numbers 2

3

4

5

6

Battery Capacity

200AH 400AH 400AH 600AH 600AH

WARNING! Be sure that all inverters will share the same battery bank. Otherwise, the inverters will transfer to fault mode.

4-1. Parallel Operation in Single phase Two inverters in parallel: Power Connection

Communication Connection

1

2

52

Three inverters in parallel: Power Connection

Communication Connection

1

2

3

Four inverters in parallel: Power Connection

Communication Connection

1

2

3

4

53

Five inverters in parallel: Power Connection

Communication Connection

1

2

3

4

5

Six inverters in parallel: Power Connection

Communication Connection

1

2

3

4

5

6

54

4-2. Support 3-phase equipment
Two inverters in each phase: Power Connection

Communication Connection
P1

1

2

P2

3

4

Four inverters in one phase and one inverter for the other two phases: Power Connection

P3

5

6

Communication Connection
P1

1

2

3

P2

P3

4

5

6

55

Three inverters in one phase, two inverters in second phase and one inverter for the third phase: Power Connection

Communication Connection

P1

P2

P3

1

2

3

4

5

6

Three inverters in one phase and only one inverter for the remaining two phases: Power Connection

Communication Connection
P1

1

2

P2

P3

3

4

5

56

Two inverters in two phases and only one inverter for the remaining phase: Power Connection

Communication Connection
P1

1

2

P2
3

P3

4

5

Two inverters in one phase and only one inverter for the remaining phases: Power Connection

Communication Connection
P1

1

2

P2
3

P3
4

57

One inverter in each phase: Power Connection

Communication Connection

P1

P2

1

2

P3
3

WARNING: Do not connect the current sharing cable between the inverters which are in different phases. Otherwise, it may damage the inverters.
4-3. Support split-phase equipment (only for 6.5KW model) Three inverters in each phase:

Communication Connection

P1

P2

1

2

3

4

5

6

58

Two inverters in each phase: Power Connection

Communication Connection
P1

1

2

One inverter in each phase: Power Connection

P2

3

4

Communication Connection

P1

P2

1

2

5. PV Connection Please refer to user manual of single unit for PV Connection. CAUTION: Each inverter should connect to PV modules separately.
59

6. LCD Setting and Display
Setting Program: Program Description Selectable option Single

When the unit is operated alone, please select “SIG” in program 28.

Parallel

When the units are used in parallel for single phase application, please select “PAL” in program 28. Please refer to 5-1 for detailed information.

L1 phase:

L2 phase:

AC output mode

*This setting is

able to set up

only when the L3 phase:

28

inverter is in

standby mode.

Be sure that

on/off switch is

in “OFF” status.

When the units are operated in 3-phase application, please choose “3PX” to define each inverter. It is required to have at least 3 inverters or maximum 6 inverters to support threephase equipment. It’s required to have at least one inverter in each phase or it’s up to four inverters in one phase. Please refers to 4-2 for detailed information. Please select “3P1” in program 28 for the inverters connected to L1 phase, “3P2” in program 28 for the inverters connected to L2 phase and “3P3” in program 28 for the inverters connected to L3 phase.
Be sure to connect share current cable to units which are on the same phase. Do NOT connect share current cable between units on different phases.

L1 for split phase:
L2 for split phase: (120° phase difference)
L2 for split phase: (180° phase difference)

When the units are operated in split phase application, please choose “2PX” to define each inverter. These options are only available for 6.5KW model. It is required to have at least 2 inverters or maximum 6 inverters to support splitphase equipment. It’s required to have at least one inverter in each phase or it’s up to three inverters in one phase. Please refers to 4-3 for detailed information. Please select “2P1” in program 28 for the inverters connected to L1 phase, “2P2” in program 28 for the inverters connected to L2 phase. And it can choose 120°or 180° phase difference for “2P2”.
Be sure to connect share current cable to units which are on the same phase.
Do NOT connect share current cable
between units on different phases.

60

Fault code display: Fault Code

Fault Event

60

Power feedback protection

71

Firmware version inconsistent

72

Current sharing fault

80

CAN fault

81

Host loss

82

Synchronization loss

83

Battery voltage detected different

84

AC input voltage and frequency detected different

85

AC output current unbalance

86

AC output mode setting is different

Icon on

Code Reference: Code

Description

NE

Unidentified unit master or slave

HS

Master unit

SL

Slave unit

Icon on

7. Commissioning

Parallel in single phase
Step 1: Check the following requirements before commissioning: Correct wire connection Ensure all breakers in Line wires of load side are open and each Neutral wires of each unit are
connected together.

Step 2: Turn on each unit and set “PAL” in LCD setting program 28 of each unit. And then shut down all units.
NOET: It’s necessary to turn off switch when setting LCD program. Otherwise, the setting cannot be programmed.

Step 3: Turn on each unit. LCD display in Master unit

LCD display in Slave unit

61

NOTE: Master and slave units are randomly defined.

Step 4: Switch on all AC breakers of Line wires in AC input. It’s better to have all inverters connect to utility at

the same time. If not, it will display fault 82 in following-order inverters. However, these inverters will

automatically restart. If detecting AC connection, they will work normally.

LCD display in Master unit

LCD display in Slave unit

Step 5: If there is no more fault alarm, the parallel system is completely installed.

Step 6: Please switch on all breakers of Line wires in load side. This system will start to provide power to the load.

Support three-phase equipment

Step 1: Check the following requirements before commissioning:

Correct wire connection Ensure all breakers in Line wires of load side are open and each Neutral wires of each unit are

connected together.

Step 2: Turn on all units and configure LCD program 28 as P1, P2 and P3 sequentially. And then shut down

all units.

NOET: It’s necessary to turn off switch when setting LCD program. Otherwise, the setting cannot be programmed.

Step 3: Turn on all units sequentially.

LCD display in L1-phase unit

LCD display in L2-phase unit

LCD display in L3-phase unit

Step 4: Switch on all AC breakers of Line wires in AC input. If AC connection is detected and three phases are

matched with unit setting, they will work normally. Otherwise, the AC icon will flash and they will not

work in line mode.

LCD display in L1-phase unit

LCD display in L2-phase unit

LCD display in L3-phase unit

Step 5: If there is no more fault alarm, the system to support 3-phase equipment is completely installed.
Step 6: Please switch on all breakers of Line wires in load side. This system will start to provide power to the load.
Note 1: To avoid overload occurring, before turning on breakers in load side, it’s better to have whole system in operation first. Note 2: Transfer time for this operation exists. Power interruption may happen to critical devices, which cannot bear transfer time.
62

8. Trouble shooting

Situation

Fault Fault

Event

Solution

Code Description

1. Restart the inverter.

2. Check if L/N cables are not connected reversely in all inverters.

60

Current feedback into the inverter is detected.

3. For parallel system in single phase, make sure the sharing are connected in all inverters. For supporting three-phase system, make sure the sharing cables are connected in the inverters in the same phase, and disconnected in

the inverters in different phases.

4. If the problem remains, please contact your installer.

1. Update all inverter firmware to the same version.

71

The firmware version of each inverter is not the same.

2. 3.

Check the version of each inverter via LCD setting and make sure the CPU versions are same. If not, please contact your instraller to provide the firmware to update. After updating, if the problem still remains, please contact your

installer.

72

The output current of each inverter is different.

1. Check if sharing cables are connected well and restart the inverter. 2. If the problem remains, please contact your installer.

80 81
82

CAN data loss Host data loss Synchronization data loss

1. Check if communication cables are connected well and restart the inverter.
2. If the problem remains, please contact your installer.

1. Make sure all inverters share same groups of batteries together.

2. Remove all loads and disconnect AC input and PV input. Then, check

The battery voltage of

battery voltage of all inverters. If the values from all inverters are

83

each inverter is not

close, please check if all battery cables are the same length and

the same.

same material type. Otherwise, please contact your installer to

provide SOP to calibrate battery voltage of each inverter.

3. If the problem still remains, please contact your installer.

1. Check the utility wiring conncetion and restart the inverter.

AC input voltage and 2. Make sure utility starts up at same time. If there are breakers

84

frequency are

installed between utility and inverters, please be sure all breakers

detected different.

can be turned on AC input at same time.

3. If the problem remains, please contact your installer.

1. Restart the inverter.

85

AC output current unbalance

2. Remove some excessive loads and re-check load information from LCD of inverters. If the values are different, please check if AC input and output cables are in the same length and material type.

3. If the problem remains, please contact your installer.

1. Switch off the inverter and check LCD setting #28.

2. For parallel system in single phase, make sure no 3P1, 3P2 or 3P3 is

86

AC output mode setting is different.

set on #28.
For upporting three-phase system, make sure no “PAL” is set on #28.

3. If the problem remains, please contact your installer.

63

Appendix II: BMS Communication Installation
1. Introduction If connecting to lithium battery, it is recommended to purchase a custom-made RJ45 communication cable. Please check with your dealer or integrator for details.

This custom-made RJ45 communication cable delivers information and signal between lithium battery and the inverter. These information are listed below: Re-configure charging voltage, charging current and battery discharge cut-off voltage according to the
lithium battery parameters. Have the inverter start or stop charging according to the status of lithium battery.

2. Pin Assignment for BMS Communication Port

Definition

PIN 1

RS232TX

PIN 2

RS232RX

PIN 3

RS485B

PIN 4

NC

PIN 5

RS485A

PIN 6

CANH

PIN 7

CANL

PIN 8

GND

3. Lithium Battery Communication Configuration LIO-4810-150A

ESS LIO-I 4810 ID switch

ID switch

ID Switch indicates the unique ID code for each battery module. It’s required to assign a unique ID to each battery module for normal operation. We can set up the ID code for each battery module by rotating the PIN number on the ID switch. From number 0 to 9, the number can be random; no particular order. Maximum 10 battery modules can be operated in parallel.
64

PYLONTECH

Dip Switch: There are 4 Dip Switches that sets different baud rate and battery group address. If switch
position is turned to the “OFF” position, it means “0”. If switch position is turned to the “ON” position, it means “1”.
Dip 1 is “ON” to represent the baud rate 9600. Dip 2, 3 and 4 are reserved for battery group address. Dip switch 2, 3 and 4 on master battery (first battery) are to set up or change the group address.

NOTE: “1” is upper position and “0” is bottom position.

Dip 1

Dip 2 Dip 3 Dip 4 Group address

0

0

0

Single group only. It’s required to set up master battery with this

setting and slave batteries are unrestricted.

1

0

0

Multiple group condition. It’s required to set up master battery on the

1: RS485

first group with this setting and slave batteries are unrestricted.

baud

0

1

0

Multiple group condition. It’s required to set up master battery on the

rate=9600

second group with this setting and slave batteries are unrestricted.

Restart to 1

1

0

Multiple group condition. It’s required to set up master battery on the third group with this setting and slave batteries are unrestricted.

take effect 0

0

1

Multiple group condition. It’s required to set up master battery on the

fourth group with this setting and slave batteries are unrestricted.

1

0

1

Multiple group condition. It’s required to set up master battery on the

fifth group with this setting and slave batteries are unrestricted.

NOTE: The maximum groups of lithium battery is 5 and for maximum number for each group, please check with battery manufacturer.

65

4. Installation and Operation LIO-4810-150A/ESS LIO-I 4810 After ID no. is assigned for each battery module, please set up LCD panel in inverter and install the wiring connection as following steps. Step 1: Use supplied RJ11 signal cable to connect into the extension port ( P1 or P2 ).
Step 2: Use supplied RJ45 cable (from battery module package) to connect inverter and Lithium battery.

  • For multiple battery connection, please check battery manual for the details. Note for parallel system: 1. Only support common battery installation. 2. Use custom-made RJ45 cable to connect any inverter (no need to connect to a specific inverter) and
    Lithium battery. Simply set this inverter battery type to “LIB” in LCD program
  1. Others should be “USE”. Step 3: Turn the breaker switch “ON”. Now, the battery module is ready for DC output.
    Step 4: Press Power on/off button on battery module for 5 secs, the battery module will start up. *If the manual button cannot be approached, just simply turn on the inverter module. The battery module will be automatically turned on.
    66

Step 5: Turn on the inverter.

Step 6. Be sure to select battery type as “LIB” in LCD program 5.

If communication between the inverter and battery is successful, the battery icon flash. Generally speaking, it will take longer than 1 minute to establish communication.

on LCD display will

PYLONTECH After configuration, please install LCD panel with inverter and Lithium battery with the following steps. Step 1. Use custom-made RJ45 cable to connect inverter and Lithium battery.

Note for parallel system: 3. Only support common battery installation. 4. Use custom-made RJ45 cable to connect any inverter (no need to connect to a specific inverter) and
Lithium battery. Simply set this inverter battery type to “PYL” in LCD program 5. Others should be “USE”.

67

Step 2. Switch on Lithium battery. Step 3. Press more than three seconds to start Lithium battery, power output ready. Step 4. Turn on the inverter.

Step 5. Be sure to select battery type as “PYL” in LCD program 5.

If communication between the inverter and battery is successful, the battery icon flash. Generally speaking, it will take longer than 1 minute to establish communication.

on LCD display will

Active Function This function is to activate lithium battery automatically while commissioning. After battery wiring and commissioning is successfully, if battery is not detected, the inverter will automatically activate battery if the inverter is powered on.

68

4. LCD Display Information

Press ” ” or ” ” button to switch LCD display information. It will show battery pack and battery group

number before “Main CPU version checking” as shown below.

Selectable information

LCD display

Battery pack numbers & Battery Battery pack numbers = 3, battery group numbers = 1

group numbers

5. Code Reference

Related information code will be displayed on LCD screen. Please check inverter LCD screen for the operation.

Code

Description

If battery status is not allowed to charge and discharge after the communication

between the inverter and battery is successful, it will show code 60 to stop charging

and discharging battery.

Communication lost (only available when the battery type is not setting as “AGM”,

“Flooded” or “User-Defined”.) After battery is connected, communication signal is not detected for 3

minutes, buzzer will beep. After 10 minutes, inverter will stop charging and

discharging to lithium battery.

Communication lost occurs after the inverter and battery is connected

successfully, buzzer beeps immediately.

If battery status is not allowed to charge after the communication between the

inverter and battery is successful, it will show code 69 to stop charging battery.

If battery status must to be charged after the communication between the inverter and battery is successful, it will show code 70 to charge battery.

If battery status is not allowed to discharge after the communication between the inverter and battery is successful, it will show code 71 to stop discharging battery.

69

Appendix III: The Wi-Fi Operation Guide
1. Introduction Wi-Fi module can enable wireless communication between off- grid inverters and monitoring platform. Users have complete and remote monitoring and controlling experience for inverters when combining Wi-Fi module with WatchPower APP, available for both iOS and Android based device. All data loggers and parameters are saved in iCloud. The major functions of this APP: Delivers device status during normal operation. Allows to configure device setting after installation. Notifies users when a warning or alarm occurs. Allows users to query inverter history data.

2. WatchPower App 2-1. Download and install APP
Operating system requirement for your smart phone: iOS system supports iOS 9.0 and above Android system supports Android 5.0 and above
Please scan the following QR code with your smart phone and download WatchPower App.

Android

iOS system

system

Or you may find “WatchPower” app from the Apple® Store or “WatchPower Wi-Fi” in Google® Play Store.

2-2. Initial Setup Step 1: Registration at first time

After the installation, please tap the shortcut icon

to access this APP on your mobile screen. In the

screen, tap “Register” to access “User Registration” page. Fill in all required information and scan the Wi-Fi

module PN by tapping

icon. Or you can simply enter PN directly. Then, tap “Register” button.

70

Then, a “Registration success” window will pop up. Tap “Go now” to continue setting local Wi-Fi network connection.
Step 2: Local Wi-Fi Module Configuration Now, you are in “Wi-Fi Config” page. There are detailed setup procedure listed in “How to connect?” section and you may follow it to connect Wi-Fi.

Enter the “SettingsWi-Fi” and select connected Wi-Fi name. The connected Wi-Fi name is the same to your Wi-Fi PN number and enter default password “12345678”.

Then, return to WatchPower APP and tap ” connected successfully.
Step 3: Wi-Fi Network settings

” button when Wi-Fi module is

Tap

icon to select your local Wi-Fi router name (to access the internet) and enter password.

Step 4: Tap “Confirm” to complete the Wi-Fi configuration between the Wi-Fi module and the Internet. 71

If the connection fails, please repeat Step 2 and 3.

Diagnose Function

If the module is not monitoring properly, please tap ”

” on the top right corner of the screen for further

details. It will show repair suggestion. Please follow it to fix the problem. Then, repeat the steps in the chapter

4.2 to re-set network setting. After all setting, tap “Rediagnosis” to re- connect again.

72

2-3. Login and APP Main Function After finishing the registration and local Wi-Fi configuration, enter registered name and password to login. Note: Tick “Remember Me” for your login convenience afterwards.
Overview After login is successfully, you can access “Overview” page to have overview of your monitoring devices, including overall operation situation and Energy information for Current power and Today power as below diagram.

Devices

Tap the icon (located on the bottom) to enter Device List page. You can review all devices here by adding

or deleting Wi-Fi Module in this page.

Add device

Delete device

73

Tap icon on the top right corner and manually enter part number to add device. This part number label is pasted on the bottom of inverter. After entering part number, tap “Confirm” to add this device in the Device list.
Part number label is pasted on the bottom of inverter.
For more information about Device List, please refer to the section 2.4. ME In ME page, users can modify “My information”, includingUser’s Photo,Account security, Modify password,Clear cache,andLog-out, shown as below diagrams.
2-4. Device List In Device List page, you can pull down to refresh the device information and then tap any device you want to check up for its real-time status and related information as well as to change parameter settings. Please refer to the parameter setting list.
74

Device Mode On the top of screen, there is a dynamic power flow chart to show live operation. It contains five icons to present PV power, inverter, load, utility and battery. Based on your inverter model status, there will beStandby Mode,Line Mode,Battery Mode. Standby ModeInverter will not power the load until “ON” switch is pressed. Qualified utility or PV source can charge battery in standby mode.
Line ModeInverter will power the load from the utility with or without PV charging. Qualified utility or PV source can charge battery.
Battery ModeInverter will power the load from the batter with or without PV charging. Only PV source can charge battery.

Device Alarm and Name Modification

In this page, tap the

icon on the top right corner to enter the device alarm page. Then, you can review

alarm history and detailed information. Tap the icon on the top right corner, a blank input box will pop out. Then, you can edit the name for your device and tap “Confirm” to complete name modification.

75

Device Information Data Users can check up Basic Information,Product Information,Rated information,History, andWiFi Module Informationby swiping left.
Swipe left
Basic Informationdisplays basic information of the inverter, including AC voltage, AC frequency, PV input voltage, Battery voltage, Battery capacity, Charging current, Output voltage, Output frequency, Output apparent power, Output active power and Load percent. Please slide up to see more basic information. Production Informationdisplays Model type (Inverter type), Main CPU version, Bluetooth CPU version and secondary CPU version. Rated Informationdisplays information of Nominal AC voltage, Nominal AC current, Rated battery voltage, Nominal output voltage, Nominal output frequency, Nominal output current, Nominal output apparent power and Nominal output active power. Please slide up to see more rated information. Historydisplays the record of unit information and setting timely. Wi-Fi Module Informationdisplays of Wi-Fi Module PN, status and firmware version. Parameter Setting This page is to activate some features and set up parameters for inverters. Please be noted that the listing in “Parameter Setting” page in below diagram may differ from the models of monitored inverter. Here will briefly highlight some of it,Output Setting,Battery Parameter Setting,Enable/ Disable items, Restore to the defaultsto illustrate.
There are three ways to modify setting and they vary according to each parameter. a) Listing options to change values by tapping one of it. b) Activate/Shut down functions by clicking “Enable” or “Disable” button. c) Changing values by clicking arrows or entering the numbers directly in the column.
Each function setting is saved by clicking “Set” button. 76

Please refer to below parameter setting list for an overall description and be noted that the available parameters may vary depending on different models. Please always see the original product manual for detailed setting instructions. Parameter setting list:

Item

Description

Output setting Output source To configure load power source priority.

priority

AC input range When selecting “UPS”, it’s allowed to connect personal computer.

Please check product manual for details.

Output voltage

When selecting “Appliance”, it’s allowed to connect home appliances. To set output voltage.

Output

To set output frequency.

frequency

Battery

Battery type:

To set connected battery type.

parameter

Battery cut-off To set the battery stop discharging voltage.

setting

voltage

Please see product manual for the recommended voltage range

based on connected battery type.

Back to grid voltage

When “SBU” or “SOL” is set as output source priority and battery voltage is lower than this setting voltage, unit will transfer to line mode

and the grid will provide power to load.

Back to discharge

When “SBU” or “SOL” is set as output source priority and battery voltage is higher than this setting voltage, battery will be allowed to

voltage

discharge.

Charger source To configure charger source priority.

priority:

Max. charging

current Max. AC charging current: Float charging

It’s to set up battery charging parameters. The selectable values in different inverter model may vary.
Please see product manual for the details.

voltage Bulk charging voltage
Battery

It’s to set up battery charging parameters. The selectable values in different inverter model may vary. Please see product manual for the details.
Enable or disable battery equalization function.

equalization

Real-time Activate Battery

It’s real-time action to activate battery equalization.

Equalization

Equalized Time To set up the duration time for battery equalization.

Out

Equalized Time To set up the extended time to continue battery equalization.

Equalization

To set up the frequency for battery equalization.

Period

Equalization

To set up the battery equalization voltage.

Voltage

77

Enable/Disable Functions
RGB LED Setting Restore to the default

LCD Auto-return If enable, LCD screen will return to its main screen after one minute

to Main screen automatically.

Fault Code

If enabled, fault code will be recorded in the inverter when any fault

Record

happens.

Backlight

If disabled, LCD backlight will be off when panel button is not

operated for 1 minute.

Bypass Function If enabled, unit will transfer to line mode when overload happened in

battery mode.

Beeps while

If enabled, buzzer will alarm when primary source is abnormal.

primary source

interrupt

Over

If disabled, the unit won’t be restarted after over-temperature fault is

Temperature

solved.

Auto Restart

Overload Auto Restart

If disabled, the unit won’t be restarted after overload occurs.

Buzzer

If disabled, buzzer won’t be on when alarm/fault occurred.

Enable/disable Turn on or off RGB LEDs

Brightness

Adjust the lighting brightness

Speed

Adjust the lighting speed

Effects

Change the light effects

Color Selection Adjust color by setting RGB value

This function is to restore all settings back to default settings.

78

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals