The Emergency Power Packs come in two models: EP-LS1, EP-LS2, EP-LS3 and EP- HS1, EP-HS2, EP-HS3. These power packs are designed to provide emergency power to light fixtures in case of power outages. The power packs come with an automatic battery testing function that checks the battery life and indicates any faults through the LED indicator lights.

Technical Specifications

  • Models : EP-LS1, EP-LS2, EP-LS3 and EP-HS1, EP-HS2, EP-HS3
  • Power supply : AC 220-240V 50/60Hz
  • Charge power : 5W max.
  • Battery type : Ni-Cd or Ni-MH
  • Recharge time : 24 hours
  • Operating temperature : 0°C to 40°C
  • Dimensions : Model EP-HS1, EP-LS1: (L) 300 x (W) 52 x (H) 37 mm

Product Usage Instructions Emergency Power Packs

  1. The power pack should be installed indoors away from direct sunlight and moisture.
  2. Before use, always turn on the power pack by pressing the ON switch.
  3. To turn off the power pack, press the OFF switch.
  4. The power pack should be stored in temperatures under 25°C and should be charged every three months to maintain its operational life.
  5. Before operating the power pack, read the manual carefully for the safest and most effective use of the product.
  6. In case of any initial troubleshooting, refer to the troubleshooting section in the manual or contact customer service.
  7. To check the battery life, the power pack comes with an automatic battery testing function that checks the battery life and indicates any faults through the LED indicator lights.
  8. For best operation, do not connect the power pack to a 230V bulb using a ballast resistor.

Indicator Lights

  • On: A continuous green light indicates that the unit is turned on and operational. The green light turns off when the unit is not turned on.
  • AC: A continuous orange light indicates that the unit is receiving a normal AC power supply. The orange light turns off when the unit is receiving an AC power supply of less than 150VAC. A blinking orange light indicates that the automatic battery testing function is activated.
  • Charge: A continuous red light indicates that the battery is charging. A continuous green light indicates that the battery is fully charged. A red light blinks once every 2 seconds when the Low Voltage Indicator is warning that the battery’s charge is about to fall below the Voltage Cut-Off point. A red light blinks three times every 2 seconds when the Battery Testing Fault is indicating that the battery can only hold less than 30 minutes of charge. A red light blinks four times every 2 seconds when the Battery Charging Fault is indicating that the battery is still not fully charged even after 10-15 hours of charging.

MODELS

Model: EP-LS1, EP-LS2, EP-LS3

Model: EP-HS1, EP-HS2, EP-HS3

Installation and Operation

Connect the unit’s INPUT electrical cable to the mains power supply of the building. Press the ON switch on the unit. The green LED should blink once to indicate that the unit is operational. Securely install the unit to prevent any accidents that could result in injury or damage. The unit will start operating the first time it receives a 230VAC/50 power supply (AC Start). The orange AC LED should turn on to indicate that the unit is receiving an AC power supply. The green ON LED will be on to indicate that the unit is operational. When there is a power outage the unit should start operating automatically. Once power has returned, the unit will continue to provide power from its battery for another 3-5 seconds before turning off. The EP-HS1, EP-HS2, EP-HS3 model also comes with a built-in Transfer Relay that can be connected to a 230VAC control switch at a desired location.

Wiring Diagram for EP-HS1, EP-HS2, EP-HS3

SUNNY-EP-LS1-Emergency-Power-Packs-fig-3 Wiring Diagram for EP-LS1, EP-LS2, EP-LS3

SUNNY-EP-LS1-Emergency-Power-Packs-fig-8

Indicators

SUNNY-EP-LS1-Emergency-Power-Packs-fig-4

Automatic Battery Test

The battery test is performed to help extend the operational lifetime of the battery, it will also test that the unit is in good condition and ready for operation. If the test finds that the battery can supply the unit with power for less than a designated amount of time, the red Charge LED will blinks red 3 times every 2 seconds to indicate a Battery Testing Fault.

SUNNY-EP-LS1-Emergency-Power-Packs-fig-5

Important Note on Using the Unit

  1. The unit should be installed indoors away from direct sunlight and rain or moisture.
  2. Always press the “ON” switch every time after installation to turn on the unit.
  3. When the unit is not in use always turn it off by pressing the “OFF” switch.
  4. The unit should be stored in temperatures under 25 Degree Celsius and the battery should be charged every 3 months to maintain its operational life.
  5. Please always read the manual carefully prior to operating the unit for the saftest and most effective use of the product.

Initial Trouble Shooting

Problem| Cause|
---|---|---
– Power not getting to the unit after plugging in. The LED AC light does not turn on.| – The power socket might not have any power.

– The plug or socket is loose.

– The AC.230V fuse is blown.

| – Check the 230VAC power supply.

– Check the plug and socket.

– Contact customer service.

– Emergency light does not turn on after the power went out.| – The ON switch was not pressed

– The lamp is faulty

– The circuit’s wiring is loose.

– The DC fuse is blown

| – Press the ON switch

– Contact customer service.

– Check the unit’s circuit connections

– Contact customer service.

– Emergency light only turns on for a short time after the power went out.| – The battery is not fully charged.

– The battery is past its operational lifetime or has deteriorated

| – Plug the unit in to charge the battery for about 10 – 15 hours.

– Contact customer service to replace the battery

Dimension (mm)

Model: EP-HS1, EP-LS1

SUNNY-EP-LS1-Emergency-Power-Packs-fig-6

Model: EP-LS2, EP-LS3, EP-HS2, EP-HS3

SUNNY-EP-LS1-Emergency-Power-Packs-fig-7

Terms for Warranty and Service

  1. The product will only be under warranty if the customer ils in the ‘warranty card and return the “return part” to the company within 7 days of purchasing the product. If this is not done within the specified time then the warranty will be considered void.
  2. The warranty only covers the unit’s internal parts for the duration specihed by the company counting from the date of purchase.
  3. Please show the warranty card every time when contacting our service department or the dealer you purchased the unit from.
  4. The warranty will be considered void in the following cases.
    • The unit has been used outside of its intended use specified in the manual.
    • The unit has been used with equipment that does not meet the specifications specified within the manual.
    • The unit has been damaged from impact, for example parts are dented, scratched missing or distorted.
    • The unit has been modified or repaired by people not officially certihed by our company.
    • The Sticker Warranty Void has been removed or torn.
    • The unit is damaged from negligence or incompetent use, for example, the battery is SWollen, the batter has been overcharged, the battery has been damaged from quick charging, the battery has been short-circuited, the battery’s charged has been completely drained.
    • The unit has been stored improperly, for example, it was exposed to moisture causing rust and damage to the internal circuitry
    • Damaged was caused by a malfunction in the AC power supply
    • Damage from natural disaster such as hre, moisture, submersion in liquids, chemical damage or from unavoidable circumstances.
    • Damage from animals or insects.

Note : Please read the manual carefully before installation and operation to understand how to properly operate the unit

For any further questions about your product please feel free to contact SUNNY’s customer service department.

IsOn Import-Export Co., Ltd. 2915-2917 Ladprao Road, Klongjan, Bangkapi, Bangkok 10240

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Sunny User Manuals

Related Manuals