HUAWEI SUN2000-12KTL-M5 Series Solar Inverter User Guide

June 9, 2024
Huawei

HUAWEI logo SUN2000-12KTL-M5 Series Solar Inverter
User Guide SUN2000-(12KTL-25KTL)-M5 Series
Quick Guide
Issue: 03
Part Number: 31500HLD
Date: 2023-02-15
Huawei Digital Power Technologies Co., Ltd.

SUN2000-12KTL-M5 Series Solar Inverter

NOTICE

  • The information in this document is subject to change due to version upgrade or other reasons. Every effort has been made in the preparation of this document to ensure accuracy of the contents, but all statements, information, and recommendations in this document do not constitute a warranty of any kind, express or implied.
  • Only qualified and trained electrical technicians are allowed to operate the device. Operation personnel should understand the system composition and working principles, as well as the local regulations.
  • Before installing the device, read the user manual carefully to get familiar with product information and safety precautions. Device damage caused by failure to abide by the storage, transportation, installation, and operation guidelines specified in this document and the user manual is not covered by the product warranty.
  • Before installing the device, check that the package contents are intact and complete against the packing list. If any damage is found or any component is missing, contact your dealer.
  • Use insulated tools and wear proper personal protective equipment (PPE) when installing the device.

Clearance Requirements

If the installation clearance does not meet the requirements, the inverter power may be derated.   HUAWEI SUN2000-12KTL-M5 Series Solar Inverter -
Clearance

Device Installation

HUAWEI SUN2000-12KTL-M5 Series Solar Inverter - Device
Installation

NOTICE
If cables are not connected immediately after the device is installed, you need to install a junction box. Otherwise, the airtightness and waterproof performance of the device may be affected.

Electrical Connections

3.1 Preparations
DANGER

  • Do not connect the neutral wire to the enclosure as a ground cable. Otherwise, electric shocks may occur.
  • Before connecting cables, ensure that the DC SWITCH on the inverter and all the switches connected to the inverter are set to OFF. Otherwise, the high voltage of the inverter may result in electric shocks.

WARNING

  • Do not connect loads between the inverter and the AC switch that directly connects to the inverter. Otherwise, the switch may trip by mistake.
  • If an AC switch is used with specifications beyond local standards, regulations, or Huawei’s recommendations, the switch may fail to turn off in a timely manner in case of exceptions, causing serious faults.

CAUTION
Each inverter must be equipped with an AC output switch. Multiple inverters cannot connect to the same AC output switch.
NOTICE

  • To ensure that the inverter can be safely disconnected from the power grid when an exception occurs, connect an AC switch to the AC side of the inverter. Select an appropriate AC switch in accordance with local industry standards and regulations.
  • Connect cables in accordance with local installation laws and regulations.
  • The cable colors are for reference only. Select appropriate cables according to the local standards.
  • When routing signal cables, separate them from power cables and keep them away from strong interference sources to prevent communication from being affected.
No Component Description Source
1 AC switch Recommended: three-phase
AC circuit breaker Rated voltage ≥ 415 V AC

Rated current:
• 12KTL–20KTL: 40 A
• 25KTL: 50 A or 63 A

3.2 Cable Connections

HUAWEI SUN2000-12KTL-M5 Series Solar Inverter - Cable
Connections

3.3 Installing AC Output Power Cables and Signal Cables
1. Route the cables through the junction box and prepare cable terminals.HUAWEI SUN2000-12KTL-M5 Series Solar Inverter - Power
Cables

Inner Diameter Rubber Plug
15 mm
22 mm
26 mm
6 mm

8.6 mm
11 mm

NOTICE

  • If the cable stripping length does not meet the requirements, the airtightness and waterproof performance of the device may be affected.
  • The OT terminal size must match the cross-sectional area of the AC output power cable and M5 screw specifications.

2. Install AC output power cables and signal cables. (The following uses the RS485 signal cables as an example. For details about other signal cables, see the signal definitions of communications ports.)HUAWEI SUN2000-12KTL-M5
Series Solar Inverter - Power Cables 1

Pin

| Definition| Function|

Description

---|---|---|---
1| GND| Ripple control| GND port for the DIN1 to DIN5 signals
2| DIN1| Dry contact for grid scheduling
3| DIN2
4| DIN3
5| DIN4
6| DIN5|  Rapid shutdown signal+| For the rapid shutdown DI signal or connecting to the signal cable of an NS protective device
7| GND| GND| –
8| –| –| –
9| 485A1| RS485A1 differential signal+| For inverter cascading or connecting to the

RS485 signal port of a SmartLogger

10| 485B1| RS485B1 differential signal–
11| 485A2| RS485A2 differential signal+| Connecting to the RS485 signal port of a powermeter
12| 485B2| RS485B2 differential signal–

3. Align the pin holes at both ends of the junction box with the positioning pins on the inverter enclosure to ensure that the screw holes on the junction box are aligned.HUAWEI SUN2000-12KTL-M5 Series Solar Inverter - Power Cables
24. Install the junction box, seal the unused cable holes in the rubber plugs with waterproof plugs, and tighten the locking caps.
HUAWEI SUN2000-12KTL-M5 Series Solar Inverter - junction
box 3.4 Connecting DC Input Power Cables
NOTICE

  • Ensure that the PV module output is well insulated to ground.
  • Use the delivered Staubli MC4 metal terminals and DC connectors. Device damage caused by using other types of metal terminals and DC connectors is not covered by the product warranty.
  • If the open-end wrench slips, the locking nut is tightened.
  • If PV strings are configured with optimizers, check the cable polarity by referring to the Smart PV Optimizer Quick Guide.
  • If the DC input power cables are reversely connected, do not perform operations immediately. Wait until the night when solar irradiance declines and the PV string current drops to below 0.5 A. Then set the DC switch to OFF, remove the positive and negative connectors, and rectify the cable connection. Device damage caused by improper  operations is not covered by the product warranty.

HUAWEI SUN2000-12KTL-M5 Series Solar Inverter - Power Cables
4 3.5 (Optional) Installing the Smart Dongle and Anti-theft Components

  1. Install the Smart Dongle. For details, see the Smart Dongle Quick Guide.
  2. Install the anti-theft components.

HUAWEI SUN2000-12KTL-M5 Series Solar Inverter -
Components

Verifying the Installation

No.

|

Expected Result

---|---
1| The inverter is installed correctly and securely.
2| Cables are routed properly as required by the customer.
3| The Smart Dongle is installed correctly and securely.
4| Cable ties are evenly distributed and no burr exists.
5| Ground cables are connected correctly and securely.
6| The DC SWITCH and all switches connected to the inverter are set to OFF.
7| The AC output power cable, DC input power cables, and signal cables are connected correctly and securely.
8| Unused terminals and ports are sealed by watertight caps.
9| The installation space is proper, and the installation environment is clean and tidy.

Powering On the System

  1. At the AC switch between the inverter and the power grid, use a multimeter to measure the grid voltage and ensure that the voltage is within the operating voltage range of the inverter. If the voltage is not in the allowed range, check the circuits.
  2. Turn on the AC switch.
  3. Turn on the DC switch (if any) between the PV strings and the inverter.
  4. (Optional) Remove the locking screw next to the DC SWITCH on the inverter.
  5. Set the DC SWITCH to ON.
  6. Observe the LED indicators to check the status of the inverter.
  7. (Optional) Observe the Smart Dongle LED indicator to check the status of the Smart Dongle.

System Commissioning

6.1 Creating a Plant
For details about how to create a plant, see the app quick guide. Scan the QR codes below to download the app and quick guide.

|
---|---
https://intl.fusionsolar.huawei.com/pvmswebsite/nologin/
assets/build/index.html#/jumppage
| https://info.support.huawei.com/dpdoc/fs_qg_c/en

6.2 Resetting Password

  1. Check that the AC and DC sides of the inverter are both powered on, and indicators and are steady green or blinking slowly for more than 3 minutes.

  2. Turn off the AC switch, set the DC SWITCH of the inverter to OFF, and wait until all indicators on the inverter panel turn off.

  3. Complete the following operations within 4 minutes:
    a. Turn on the AC switch and wait for about 90s or until the inverter indicator blinks.
    b. Turn off the AC switch and wait about 30s or until all LED indicators on the inverter panel turn off.
    c. Turn on the AC switch and wait for about 30s or until all LED indicators on the inverter panel blink and then turn off after about 30s.

  4. Wait until the three green LEDs on the inverter panel blink fast and then the three red LEDs blink fast, which indicates that the password is restored.

  5. Reset the password within 10 minutes. (If no operation is performed within 10 minutes, all parameters of the inverter remain unchanged.)
    a. Wait until the indicator blinks.
    b. Connect to the app using the initial WLAN hotspot name (SSID) and initial password (PSW), which can be obtained from the label on the side of the inverter.
    c. On the login page, set a new password and log in to the app.

  6. Set router and management system parameters to implement remote management.

NOTICE
You are advised to reset the password in the morning or at night when the solar irradiance is low.

Customer Service Contact Information

Customer Service Contact Information


Region| Country| Email|

Tel

Europe| France| eu_inverter_support@huawei.com| 0080033888888
Germany
Spain
Italy
United Kingdom
Netherlands
Other countries| For details, visit solar.huawei.com.
Asia Pacific| Australia| eu_inverter_support@huawei.com| 1800046639
Turkey| eu_inverter_support@huawei.com| –
Malaysia| apsupport@huawei.com| 0080021686868/1800220036
Thailand| (+66) 26542662 (local call charge)
1800290055 (free in Thailand)
China| solarservice@huawei.com| 400-822-9999
Other countries| apsupport@huawei.com| 0060-3-21686868
Japan| Japan| Japan_ESC@ms.huawei.com| 0120258367
India| India| indiaenterprise_TAC@huawei.com| 1800 103 8009
South  Korea| South Korea| Japan_ESC@ms.huawei.com| –
NorthAmerica| United States| eu_inverter_support@huawei.com| 1-877-948-2934
Canada| eu_inverter_support@huawei.com| 1-855-482-9343

Latin America

| Mexico|

la_inverter_support@huawei.com

| 018007703456/0052-442-4288288
Argentina| 0-8009993456
Brazil| 0-8005953456
Chile| 800201866 (only for fixed lines)
Other countries| 0052-442-4288288
Middle East and Africa| Egypt| eu_inverter_support@huawei.com| 08002229000/0020235353900
UAE| 08002229000
South Africa| 0800222900
Saudi Arabia| 8001161177
Pakistan| 0092512800019
Morocco| 0800009900
Other countries| 0020235353900

Huawei Digital Power Technologies Co., Ltd.
Huawei Digital Power Antuoshan Headquarters
Futian, Shenzhen 518043
People’s Republic of China
solar.huawei.com

References