MT-DP96FHMF meter with high ability and precision. It’s can measures important electrical parameter as V, A, F, PF, P, Q, S, KWh, KVARh, KWh (-), KVARh(-), Total Harmonic Distortion (THD), Harmonic Distrortion from 2nd to 31st order, multi rate function…/
With integration RS-485 communication port, complete with each kinds intelligent distribute system and power energy manage system, share abundance monitor data/
FUNCTION INTRODUCE
Measure function
Remark
Realtime measure
Three phase voltage (L-L, L-N)
Three phase current and neutral current
System Frequence
P, Q, S, PF (per phase & total
Electric energry
KWh import
KVARh import
KWh export, KVARh export
Multi rate function/
Da ti gia
8 period/ 8 khoang theyi gian 4 kind of multi rate/ 4 ti gia
Harmonics/ Song hai
THDU per phase/ T6ng hai ap tren tang pha
THDI per phase/ Tong hai dung ten t&ng pha
HDI per phase from 2″d to 318′ order/ Hai clang ter bac 2-31 tren trung pha
HDU per phase from 2nd to 318′ order/ Hai ap ter bac 2-31 hen ti:rng pha
Communication/ Truyen than Maximen Demand Ngo ra analog Digital input/ Ng6 vao
so Relay output
RS485 Port MODBUS-RTU
U,I,P,Q
Basic function
0-20mA/ 4-20mA/ 0-5V/ 0-10V
Dry contact type
AC250V 5A Remote
Expanded option
Display type
Measure function | Remark |
---|---|
**** Realtime measure | Three phase voltage (L-L, L-N) |
**** Basic function
Three phase current and neutral current
System Frequence
P, Q, S, PF (per phase & total
Electric energry| KWh import
KVARh import
KWh export, KVARh export
Multi rate function| 8 period
**** Harmonics| THDU per phase
THDI per phase
HDI per phase from 2nd to 31st order
HDU per phase from 2nd to 31st order
Communication| RS485 PortMODBUS-RTU
Maximen Demand| U,I,P,Q
Analog output| 0-20mA| **** Expanded option
Digital input| Dry contact type
Relay output| AC250V 5A Remote
**** Display type| Special display, LCDscreen
TECHNICAL PARAMETER
| Parameter
---|---
**** Signal Inpu| Connection system| 3P3W
**** Voltage| Measurementrange| 519V
Over load| Continous: 1.2 Vn; Instantaneous: 2Vn
Powerconsumption| < 1VA
Current| Measurementrange| 5A/ 1A
Over load| Continous: 1.2In; Instantaneous: 2In
Powerconsumption| < 1VA
Frequence| 45 – 65Hz
Auxiliary power suply| AC 85-265V DC100-300V
**** Communication| RS485 communication port, physical layer
isolation.According international standard MODBUS-RTU agreement. Communication
speed 1200-38400 (Default 9600)Test type N81, E81, 081 (Default N81)
Analog output| 0-20mA/ 4-20mA
Relay output| Programme remoteCapacity 5A at 250VAC
Digital input| Remote switch input signal, dry contact input. Programrelate
alarm output
**** Measure class| Current/ VoltageFrequency/ Tan so: +0.1HzActive power
Reactive powerEnergy
IP protection| IP53 for indoor type and PI65 for outdoor type
Evernionment| Working temperature -10+55°C Store temperatureRelative
Humidity
**** Safe| Isolation: Signal, auxiliary power suply, output terminalcrust
resistance >5MU and withstand voltage pulse>AC2KV
Parameters| MT-DP96FHMF| MT-DP96HMF| MT-DP96MF| MT-DP96MFA| MT-DP96V| MT-DP96A
---|---|---|---|---|---|---
Voltage| | | | | | x
Voltage| | | | | | x
Neutral voltage| | | | | | x
Line current| | | | | x|
Neutral current| | | | | x|
Average current| | | | | x| x
| | | | | x| x
Power factor| | | | | x| x
Averga power factor| | | | | x| x
Active Power| | | | | x| x
Total active power| | | | | x| x
Reactive power| | | | | x| x
Total reactive power| | | | | x| x
Apparent power (L1, L2, L3)| | | | | x| x
Total apparent power| | | | | x| x
Maximum voltage demand| | x| x| x| x| x
Maximum current demand| | x| x| x| x| x
Maximum power demand| | x| x| x| x| x
Maximum demand time| | x| x| x| x| x
Active import energy| | | | | x| x
Active export energy| | | | | x| x
Reactive import energy| | | | | x| x
Reactive export energy| | | | | x| x
Setting time (year, month,day, hour…)| | | | | x| x
Multi rate function| | | | | x| x
THD voltage (L1, L2, L3)/| | | x| x| x| x
THD current(L1, L2, L3)| | | x| x| x| x
Voltage harmonics (2nd to 31 torder)| | | x| x| x| x
Current harmonics (2nd to 31storder)| | | x| x| x| x
Communication MOBUS RS-485| | | | | x| x
---|---|---|---|---|---|---
Active pulse| | | | | x| x
Reactive pulse| | | | | x| x
Digital input| Option| Option| Option| Option| Option| Option
Relay output| Option| Option| Option| Option| Option| Option
Analog output| Option| Option| Option| Option| Option| Option
DIMENSION
Model| LxH (mm)| AxB (mm)| SxY (mm)| SxY (mm) IP65| N
(mm)| M(mm)
---|---|---|---|---|---|---
MT-DP96VMT-DP96A MT-DP96MFA MT-DP96MF MT-DP96HMFMT-DP96FHMF| **** 96×96|
**** 90.5×90.5| **** 91×91| **** 91.5×91.5| **** 94|
**** 88
MT-DP72VMT-DP72A MT-DP72MFA MT-DP72MF MT-DP72HMFMT-DP72FHMF| **** 72×72|
**** 65.6×65.6| **** 66×66| **** 67×67| **** 97| ****
91
MT-DP48VMT-DP48A MT-DP48MAF| 48×48| 44×44| 45×45| |
90| 84
MT-DP49VMT-DP49A MT-DP49MAF| 48×96| 43.2×90.2| 43.5×90.5| |
**** 95| 89
CONNECTION
Active Pulse | Reactive Pulse | RS485 | Aux. PowerSuply | ||
---|---|---|---|---|---|
Ep- | Ep+ | Ep- | Ep+ | B | |
48 | 47 | 50 | 49 | 59 | |
Relay Output | Digital input | Analog output | |||
--- | --- | --- | |||
DO1 | DO2 | DO3 | DO4 | COM | DI1 |
15 | 16 | 17 | 18 | 19 | 20 |