Master MT-DP96MFA Digital Multifunction Meter User Manual
- June 9, 2024
- MASTER
Table of Contents
DIGITAL MULTIFUNCTION METER
User Manual
MT-DP96MFA
MT-DP96MFA Digital Multifunction Meter
Thanks for choosing our product – MT-DP96MFA, Please read this manual
carefully and pay attention to below caution matters.
CAUTION
This product should be installed and maintained by professional person
Before operating this product inside or outside, please cut off the input
signal and power supply;
Please make sure all parts of the product don’t have voltage by suitable
voltage detection device
The power supply should be within the rated range
The below situation will result in device damage and abnormal working
Auxilliary power source voltage over range
Distribute system frequence over range
Current, voltage input polarity incorrect
Disconnect the communication plug under charged situation
No according requirement to connect termial
Please don’t touch the terminals when the meter is in operation!
Function introduce
Measure function | Remark |
---|---|
Realtime measure | Three phase voltage (L-L, L-N) |
Three phase current and neutral current
System Frequence
P, Q, S, PF (per phase & total
Electric energry| KWh import
KVARh import
KWh export, KVARh export
Communication| RS485 Port MODBUS-RTU
Maximum Demand/| U,I,P,Q| Expanded option/
Analog output/| 0-20mA/ 4-20mA/ 0-5V/ 0-10V
Digital input/| Dry contact type/
Relay output/| AC250V 5A Remote/ Alarm
Display type/| LCD
Technical parameter
| Parameter
---|---
Signal Input/| Connection system| 3P3W/ 3P4W
Voltage| Measurement range| 450V L-L
Over load| Continous: 1.2 Vn; Instantaneous: 2Vn
Power consumption| < 1VA
Current| Measurement range| 5A/ 1A
Over load| Continous: 1.2In; Instantaneous: 2In
Power consumption| < 1VA
Frequence| 45 – 65Hz
Auxiliary power suply| AC85-265V DC100-300V
Communication
| RS485 communication port, physical layer isolation. According international
standard MODBUS-RTU agreement. Communication speed 1200-38400 (Default 9600)
Test type N81, E81, 081 (Default N81)
Analog output| 0-20mA/ 4-20mA/ 0-5V/ 0-10V
Relay output| Programme remote/ Alarm switching ouput
Capacity 5A at 250VAC/ 30VDC
Digital input| Remote switch input signal, dry contact input. Program relate
alarm output
Measure class| Current, Voltage: 0.5S Frequency: ±0.1Hz Active power: 0.5S
Reactive power: 2S
Active Energy: 0.5S; Reactive En.: 2S
IP protection| IP53 for indoor type and PI65 for outdoor type
Evernionment
| Working temperature: -10÷55°C Store temperature: -20÷75°C Relative
Humidity:<80%RH
Safe| Isolation: Signal, auxiliary power suply, output terminal crust
resistance
5MW and withstand voltage pulse
AC2KV
Installation and correction
LxH (mm)| AxB (mm)| SxY (mm)| SxY (mm) IP65| N
(mm)| M (mm)
---|---|---|---|---|---
96×96| 90.5×90.5| 91×91| 91.5×91.5| 94| 88
3P4W System: 3PT, Direct Volt input| 3P4W System: 3PT, 3VT
---|---
3P3W System: 2PT, Direct Volt input| 3P3W System: 2PT, 2VT
Active Pulse| Reactive Pulse| | RS485| | Aux. Power Suply
---|---|---|---|---|---
Ep-| Ep+| Ep-| Ep+| | B| A| | N(V-)| L(V+)
48| 47| 50| 49| | 59| 58| | 2| 1
Relay Output| Digital input| Analog output
---|---|---
DO1| DO2| DO3| DO4| COM| DI1| DI2| DI3| DI4| A0-| A01+| A02+| A03+| A04+
15| 16| 17| 18| 19| 20| 21| 22| 70| 71| 72| 73| 74| 30| 31| 32| 33| 34
Display & Buttons
a. Four lines digital display measure information: Three phase voltage, three
phase current, active power, reactive power, power factor,frequence, switch
input, output, other switch input, two way actice power, two way reactive
power, analog input, demand
b. K is light mean practice value is display value is 1.000 times. M is light
mean practice value is display value is 1.000.000 times
c. Measure item unit or charactierise: three phase voltage V, three phase
current A, active power W, reactive power VAR…
d. Buttons use in change or programme set:
is change page button or value increase or decrease button
is enter programme status
is select confirm button
If there is no relative symbol display or the set data not working, It means the product without the relative function
Board | Content | Explain |
---|
DISP=1
-Three phase voltage
-Forward active energy
Kwh| | Seperate display voltage Ua, Ub, Uc
(in the 3P4W)
In left fig. Ua=5774V Ub=5774V Uc=5774V
Forward active energy = 2908.05KWh
DISP=2
-Three phase voltage
-Reverse active energy
Kwh| | Seperate display voltage Uab, Ubc, Uca
(in the 3P4W)
In left fig.
Uab=10KV
Ubc=10KV
Uac 10KV
Reverse active energy =1000.02Kwh
DISP=3
-Three phase current
-Forward reactive energy Kvarh| | Seperate display current la, lb, lc (in the 3P4W)
In left fig.
la=5A
Ib=5A
Ic=5A
Reverse reactive energy = 50Kvarh
DISP=4
-Total active power
-Total reactive power
-Total apparent power| | Total active power = 86.6KW
Total reactive power = 0000Kvar
Total apparent power =86.6KVA
Reverse reactive energy =100.08Kvarh
---|---|---
DISP=5
– Active power phase A
-Reactive power phase A
-Apparent power phase A| | Active power of phase A = 28.87KW
Reactive power of phase A = 0000Kvar
Apparent power of phase A =28.87KVA
Forward active energy =2908.05KWh
DISP=6
– Active power phase B
-Reactive power phase B
-Apparent power phase B| | Active power of phase B = 28.87KW
Reactive power of phase B = 0000Kvar
Apparent power of phase B =28.87KVA
Reverse active energy =1000.02KWh
DISP=7
– Active power phase C
-Reactive power phase C
-Apparent power phase C| | Active power of phase C = 28.87KW
Reactive power of phase C = 0000Kvar
Apparent power of phaseCB =28.87KVA
Forward reactive energy =50.00KVARh
---|---|---
DISP=8
– Average current
-Zero sequence current| | Average current = 5A
Zero sequence current = 0.06A
Reverse reactive energy =50.00KVARh
DISP=9
– Three phase total power factor
-Frequence -Voltage unbalance| | Three phase total power factor =1.000
Frequence = 50Hz
Voltage unbalancedness = 9V
Forward active energy =2908.05KWh
DISP=10
Split phase power factor| | Power factor of phase A =0.999 (inductive load)
Power factor of phase B =0.999 (inductive load)
Power factor of phase C =0.999 (inductive load)
Reverse active energy =1000.02KWh
---|---|---
DISP=11
Residual current| | Residual current = 10.09mA
DISP=12
Digital input infomation from 1 to 12 way channel| | First line: 1-4 way
channel Second ine: 5-8 way channel Third line: 9-12 way channel
In left fig.: No.5 way, No.6 way, No.8 way chanel are ON, other way channel is
OFF
DISP=13
Digital output infomation from 1 to 4 way channel| | First line: 1-4 way
channel Second ine: 5-8 way channel Third line: 9-12 way channel
In left fig.: No.1 way, No.3 way, No.4 way chanel are ON, No.2 way chanel is
OFF
---|---|---
Programme operation
In programme status, digital interface adopt layers structure menu type, meter
supply three lines number display (se fig. 5)
No.1 line is first layer menu information;
No.2 line is second layer menu information;
No.3 line is third layer menu information;
Exp: The fig.5 shown: No.1 layer: INPT = Signal input; No.2 layer: CT =
current transformer; No.3 layer: current value is 5, It means ratio of CT is
25/5A.
The digital display interface menu has the following organizational structure,
the user can choose the appropriate setting parameters according tho the
actual situation.
No.1 Layer | No.2 Layer | No.3 Layer | Description |
---|
System
SET| Display
DISP| 0000-0017| 0000 mean automatic cycling display. Each board connect see
table 6
D I SL| 0001-0003
or
0000-0120| 0000-0120 is keeing time of LCD back light.
0000 means the backlight keeping ON
Data dear
CL r.E| 1111| 1111 means the data clear other value is invalid
Signal Input
I NPT| Wiring type Net| 0000
or other value| 0000 mean 3P4W system. Other value is mean 3P3W system
---|---|---|---
Voltage trans. ratio PT| 1 –9999| PT value= PT primary value/ secondary value
Current trans. rato PT| 1 –9999| CT value= CT primary value/ secondary value
Communication
Set CON i ( i is 1 —2)| Address SN| 1~247| Meter address range 1 to 247
---|---|---|---
Communication speed
BAUD| 0001~0004| 0001 is 1200; 0002 is 2400; 0003 is 4800; 0004 is 9600; 00005
is 9200; 00006 is 38400
Data format
DATA| 0001~0003| 0000 is E,8, 1; 0001 is 0,8,1; 00002 is N,8,1
Digital output
Set Do-i ( iis 1~4)| Choose alarm item or close
alarm| Set alarm item’s specitic threshold value| Choose alarm item, and set
relative threshold value (when alarm item is digital value, no need set
threshol value), once meet alarm condition, switch ouput working
---|---|---|---
Analog outputSet
AQ-i. (ib 1~4)| Choosen transmitter itemor cose analog output (refer to 8.2
analog output)| Set the full scale value of analog item| Choose transmitter
item’s and relative electrical parameter (0-20mA, 4-20mA, 4-12-20mA) For
example, set “AO-1″
TYPE”0135″ UAL”5000”, which means A phase current 0-5A corresponds to the
transmitter output signal of first loop 4-20mA
---|---|---|---
Note: The above menu is applied to the product with complete functions. If you
find there is no such menu in the product or the menu is not working, It means
the product not supporting the function.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>