VEICHI VC-4AD Analog Input Module User Manual

June 9, 2024
VEICHI

VEICHI-logo

VEICHI VC-4AD Analog Input Module

VEICHI-VC-4AD-Analog-Input-Module-product

Thank you for purchasing the VC-4AD analog input module developed and manufactured by Suzhou VEICHI Electric Technology Co. Before using our VC series PLC products, please read this manual carefully, so that you can grasp the characteristics of the product more clearly and install and use it correctly. You can make full use of the rich functions of this product for safer application.

Tip:
Before starting to use, please read the operation instructions, precautions carefully to reduce the occurrence of accidents. Personnel responsible for the installation and operation of the product must be strictly trained to comply with the safety codes of the relevant industry, strictly observe the relevant equipment precautions and special safety instructions provided in this manual, and perform all operations of the equipment in accordance with the correct operating methods

Interface Description

Interface Description
The VC-4AD has a cover for both the expansion interface and the user terminal, and the appearance is shown in Figure 1-1.VEICHI-VC-4AD-Analog-Input-Module-
fig 1

Figure 1-1 Appearance of the module interface

Model descriptionVEICHI-VC-4AD-Analog-Input-Module-fig
2

Figure 1-2 Illustrative diagram of the product model

Definition of terminals

No| Marking| Instructions| No| Marking| Instructions
---|---|---|---|---|---
01| 24V| Analogue power supply 24V positive| 02| COM| Analogue power supply 24V negative
03| V1+| Voltage signal input for channel 1| 04| PG| Grounded terminal
05| I1+| Channel 1 current signal input| 06| VI1–| Channel 1 common ground end
07| V2+| Channel 2 voltage signal input| 08| l| Reserved
09| I2+| 2nd channel current signal input| 10| VI2-| Channel 2 common ground end
11| V3+| Voltage signal input for channel 3| 12| l| Reserved
13| I3+| Channel 3 current signal input| 14| VI3–| Channel 3 common ground end
15| V4+| Channel 4 voltage signal input| 16| l| Reserved
17| I4+| Channel 4 current signal input| 18| VI4–| Channel 4 common ground end

1-3 Terminal definition table

Note: For each channel, voltage and current signals cannot be input at the same time. When measuring current signals, please short the channel voltage signal input to the current signal input.

Access systems
The expansion interface allows the VC-4AD to be connected to a main module of the VC series PLC or to other expansion modules. The expansion interface can also be used to connect other expansion modules of the same or different models of the VC series. This is shown in Figure 1-4.VEICHI-VC-4AD-Analog-
Input-Module-fig 3

Figure 1-4 Schematic diagram of the connection to the main module and other expansion modules

Wiring instructions
User terminal wiring requirements, as shown in Figure 1-5.

Figure 1 5 Diagram of user terminal wiring

The diagrams ① to ⑦ indicate the seven aspects that must be taken into account when wiring.

  1. It is recommended that the analogue input is connected via a twisted shielded cable. The cable should be routed away from power cables or other wires that may cause electrical interference.
  2. If there are fluctuations in the input signal, or if there is electrical interference in the external wiring, it is recommended to connect a smoothing capacitor (0.1μF to 0.47μF/25V).
  3. If the current channel uses the current input, short the voltage input and the current input for that channel.
  4. If there is excessive electrical interference, connect the shielding ground FG to the module earth terminal PG.
  5. Ground the module’s earth terminal PG well.
  6. The analogue power supply can use the 24 Vdc power supply from the main module output, or any other power supply that meets the requirements.
  7. Do not use the empty pins on the user terminals.

Instructions for use

Power indicators

Table 2 1 Power supply indicators

Projects Description
Analog circuits 24Vdc (-10% to +10%), maximum allowable ripple voltage 2%,

50mA (from mains module or external power supply)
Digital Circuits| 5Vdc, 70mA (from the main module)

Performance indicators

Table 2-2 Performance indicators

Projects Indicators
Conversion speed 2ms/channel

Analogue input range

|

Voltage input

| -10Vdc to +10Vdc, input impedance

1MΩ

|

4 channels can be used simultaneously.

Current input| -20mA to +20mA, input impedance 250Ω

Digital output

| Current setting range: -2000 to +2000

Voltage setting range: -10000 to +10000

Ultimate voltage| ±12V
Ultimate current| ±24mA

Resolution

| Voltage input| 1mV
Current input| 10μA
Precision| ±0.5% of full scale

Isolation

| The analogue circuitry is isolated from the digital circuitry by an opto- coupler. The analogue circuitry is internally isolated from the module input 24Vdc supply. No isolation between

analogue channels

Indicator light description

Projects Description
Signal indicator RUN status indicator, blinking when normal

ERR error status indicator, illuminated on failure

Expansion module rear stage interface| Connection of rear modules, hot- swappable not supported
Expansion module front interface| Connection of front-end modules, hot- swappable not supported

Characteristic settings

The input channel characteristics of the VC-4AD are the linear relationship between the channel analogue input quantity A and the channel digital output quantity D, which can be set by the user. Each channel can be understood as the model shown in Figure 3-1, and since it is a linear characteristic, the characteristics of the channel can be determined by determining two points P0 (A0, D0) and P1 (A1, D1), where D0 indicates that when the analogue input is A0 D0 indicates the channel output digital quantity when the analogue input is A0 and D1 indicates the channel output digital quantity when the analogue input is A1.VEICHI-VC-4AD-Analog-Input-Module-fig 5

Figure 3-1 Schematic diagram of the channel characteristics of the VC-4AD
In consideration of the user’s ease of use and without affecting the realization of the function, in the current mode, A0 and A1 correspond to [Actual Value 1] and [Actual Value 2] respectively, and D0 and D1 correspond to [Standard Value 1] and [Standard Value 2] respectively, as shown in Figure 3-1, the user can change the channel characteristics by adjusting (A0,D0) and (A1,D1), the factory default (A0,D0) is the external The factory default (A0,D0) is the 0 value of the external analogue input, (A1,D1) is the maximum value of the external analogue input. This is shown in Figure 3-2.

Figure 3-2 Channel characteristic change for VC-4AD
If you change the value of D0 and D1 of the channel, you can change the channel characteristics, D0 and D1 can be set anywhere between -10000 and +10000, if the set value is out of this range, VC-4AD will not receive and keep the original valid setting, Figure 3-3 shows the example of characteristics change, please refer to it.

Programming examples

Programming example for VC series + VC-4AD module
Example: VC-4AD module address is 1, use its 1st channel input voltage signal (-10V to +10V), 2nd channel input current signal (-20mA to +20mA), close the 3rd channel, set the average number of points to 8, and use data registers D0 and D2 to receive the average conversion result.

  1. Create a new project and configure the hardware for the project, as shown belowVEICHI-VC-4AD-Analog-Input-Module-fig 8
    Figure 4-1 Hardware configuration

  2. Double click on the “VC-4AD” module on the rail to enter the 4AD configuration parametersVEICHI-VC-4AD-Analog-Input-Module-fig 9
    4.2 Basic application channel one setup.

  3. Click on “▼” to configure the second channel modeVEICHI-VC-4AD-Analog-Input-Module-fig 10
    4.3 Basic Application Channel 2 Setup

  4. Click on “▼” to configure the third channel mode and click on “Confirm” when finished.VEICHI-VC-4AD-Analog-Input-Module-fig 11
    4.4 Basic application channel three setup

Installation

Size specificationVEICHI-VC-4AD-Analog-Input-Module-fig
12

Figure 5-1 External dimensions and mounting hole dimensions (unit: mm)

Installation method
The installation method is the same as that for the main module, please refer to the VC Series Programmable Controllers User Manual for details. An illustration of the installation is shown in Figure 5-2VEICHI-VC-4AD-Analog-
Input-Module-fig 13

Figure 5-2 Fixing with DIN slot

Operational checks

Routine checks

  1. Check that the analogue input wiring meets the requirements (see 1.5 Wiring instructions).
  2. Check that the VC-4AD expansion connector is reliably plugged into the expansion connector.
  3. Check that the 5V and 24V power supplies are not overloaded. Note: The power supply for the digital part of the VC-4AD comes from the main module and is supplied via the expansion interface.
  4. Check the application to ensure that the correct operating method and parameter range has been selected for the application.
  5. Set the VC main module to RUN.

Fault checking
If the VC-4AD is not running properly, check the following items.

  • Checking the status of the main module “ERR” indicator.
    blinking: check whether the expansion module is connected and whether the configuration model of the special module is the same as the actual connected module model.
    extinguished: the extension interface is correctly connected.

  • Check the analogue wiring.
    Confirm that the wiring is accurate and can be wired as shown in Figure 1-5.

  • Check the status of the module’s “ERR” indicator
    Lit: 24Vdc power supply may be faulty; if 24Vdc power supply is normal, the VC-4AD is faulty.
    Off: 24Vdc power supply is normal.

  • Check the status of the “RUN” indicator
    blinking: the VC-4AD is operating normally.

Information for users

  1. The scope of the warranty refers to the programmable controller body.

  2. The warranty period is eighteen months. If the product fails or is damaged during the warranty period under normal use, we will repair it free of charge.

  3. The start of the warranty period is the date of manufacture of the product, the machine code is the only basis for determining the warranty period, equipment without the machine code is treated as out of warranty.

  4. Even within the warranty period, a repair fee will be charged for the following cases.
    failure of the machine due to non-operation in accordance with the user manual.
    Damage to the machine caused by fire, flooding, abnormal voltage, etc..
    Damage is caused when using the programmable controller for a function other than its normal function.

  5. The service charge will be calculated on the basis of the actual cost, and if there is another contract, the contract will take precedence.

  6. Please make sure that you keep this card and present it to the service unit at the time of warranty.

  7. If you have questions, you can contact the agent or contact us directly.

Suzhou VEICHI Electric Technology Co.ltd
China Customer Service Centre
Address: No.1000 Song Jia Road, Wuzhong Economic & Technological Development Zone
Tel: 0512-66171988
Fax: 0512-6617-3610
Service Hotline: 400-600-0303
Website: www.veichi.com
Data Version V1.0 Archived 2021-07-30
All rights reserved. Contents are subject to change without prior notice.

Warranty





Customer Information

| Unit address.
---|---
Name of unit.| Contact person.
Contact number.




Product information

| Product type.
Fuselage barcode.
Name of agent.


Fault information

| Repair time and content:. Maintenance people


Mailing Address

| Suzhou VEICHI Electric Technology Co.

Address: No. 1000, Songjia Road, Wuzhong Economic and Technological Development Zone

Documents / Resources

| VEICHI VC-4AD Analog Input Module [pdf] User Manual
VC-4AD Analog Input Module, VC-4AD, Analog Input Module, Input Module, Module
---|---
| VEICHI VC-4AD Analog Input Module [pdf] User Manual
VC-4AD Analog Input Module, VC-4AD, Analog Input Module, Input Module

References

Read User Manual Online (PDF format)

Loading......