TECNOWARE ATS Automatic Transfer Switch 16A Single Phase User Manual
- June 9, 2024
- TECNOWARE
Table of Contents
TECNOWARE ATS Automatic Transfer Switch 16A Single Phase
Introduction
This ATS product is designed with two independent power inlets to supply power
to the load from a primary power source. Should primarily power source fail,
the secondary will automatically back up the connected equipment without any
interruption. The transfer time from one line to another is seamless to the
connected equipment. After switching to a secondary power source, the ATS can
also switch power back to the primary input when power to the primary input is
restored.
Package contents:
- ATS module
- User manual
- mounting brackets
Product Overview
Front View:
- Power switch for input source A
- Power switch for input source B
- Circuit breaker for output 1
- Circuit breaker for output 2
- USB communication port
- RS-232 communication port
- Communication slot
- Operation indicators (please refer to section 4 for the details
Back View:
- Contact port (please refer to section 7 for the details)
- Output receptacles “Output 1” (IEC 10A)
- Output receptacles “Output 2” (IEC 10A)
- Output receptacle “Output 3” (IEC 16A)
- Input source A connector
- Input source B connector
Important Safety Warnings
-
Before using the unit, please read all instructions and cautionary markings on the unit, this manual and the batteries.
-
WARNING!! The ATS must be connected to earth when in use. In line with current regulations, only use the cables that have been supplied with the machine. The power supply socket must be easily accessible to the operator.
-
WARNING!! The ATS has been designed exclusively to operate indoors. It is advisable to install it in areas where no inflammable liquids or gases, or other harmful or noxious substances, have been stored.
-
ATTENTION!! A soft damp cloth may be used to clean the outside of the machine (always with the system disconnected from the mains power supply and users).
Do not use any type of solvent as this may damage the external finishing of the machine. -
ATTENTION!! The ATS has been designed exclusively for professional use.
-
NOTE: These instructions may be modified by the wiring regulations in force in the country where the ATS is purchased.
Operation Indicators & Status
- Source preference selector
- Priority setting LEDs
- Power source status LEDs
- Output source LEDs
- Fault indicator
- Alarm mute button
Indication type| LED description| LED status| Condition|
Alarm
---|---|---|---|---
Priority setting LEDs| Source A (v)| ON| Source A is priority| OFF
Source B (v)| OFF
Source A (v)| OFF| Source B is priority| OFF
Source B (v)| ON
Power source status| Status of source A (w)| OFF| Inlet A has no power input|
OFF
ON| Inlet A has power input, and power is OK| OFF
Flashing| Inlet A has power input, but power is out of SPEC| OFF
Status of source B (w)| OFF| Inlet B has no power input| OFF
ON| Inlet B has power, and power is OK| OFF
Flashing| Inlet B has power input, but power is out of SPEC| OFF
Output status| Output from source A (x)| ON| Power A is output| OFF
Output from source B (x)| OFF
Output from source A (x)| OFF| Power B is output| OFF
Output from source B (x)| ON
Output from source A (x)| OFF| NO OUTPUT| OFF
Output from source B (x)| OFF
Alarm| Fault (y)| OFF| Alarm not present| OFF
ON| Alarm present| Continuously
Installation
NOTE: Before installation, please inspect the unit. Be sure that nothing inside the package is damaged.
Mounting the Unit
The unit can be mounted in a standard 19″ rack. Fasten the mounting brackets
to the unit using the screws provided. With brackets attached securely, users
can mount the unit in a standard 19″ rack as shown below.
NOTE: If the temperature around the unit will rise above 40 °C, ventilation is required
Connecting the Unit
For connecting the ATS, plug “input source A connector” and “input source B
connector” to the two independent power sources or UPSs depending using the
SCHUCKO IEC or IEC IEC 16A cables supplied. Plug the user load to the output
10A (“Output 1 and 2”) or 16A (“Output 3”) sockets depending on user’s
requirements.
Operation
Power On/Off
Put the input power switch in “ON” position. The output will then be supplied
by the source set as selected.
Setting priority of power source
It is possible to set the power source preference to supply the output by
pushing the button of “source preference selector”. The default power source
is “Source A”.
Function | Description | Default | Possible configuration |
---|---|---|---|
Source perference selector | Selection of input that normally supplies the | ||
load | Source A | ·Source A |
·Source B
Communication Port
The ATS is supplied with the following communication ports:
-
Serial port is available with RS232 com. port and USB com. port on the front panel.
NOTE: the use of one port automatically excludes the other. -
Contacts port on the rear panel.
Serial Ports: RS-232 & USB connectors
PIN # | NAME | TYPE | SIGNAL |
---|---|---|---|
1 | |||
2 | TX | OUT | Serial line TX |
3 | RX | IN | Serial line RX |
4 | |||
5 | GND | POWER | |
6 | +12V | POWER | |
PIN # | SIGNAL | ||
--- | --- | ||
1 | VBUS | ||
2 | D- | ||
3 | D+ | ||
4 | GND |
NOTE: The utilization of the communication port is optional and it is
not necessary for the correct functioning of the ATS.
Contact Ports
The contacts port is formed using six (6) pins numbered from left to right
(see fig. 1), which can be connected to an external monitoring system (such as
a BMS) in order to monitor the operational status of the ATS. The external
equipment must respect the voltage and current characteristics of the contacts
port.
The contacts port provides the following pins:
- Pin 1: common contact.
- Pin 2: “Source B” active contact (if the contact between “pin 1” and “pin 2” is closed, output is supplied by “Source B”).
- Pin 3: “Source A” active contact (if the contact between “pin 3” and “pin 1” is closed, output is supplied by “Source A”).
- Pin 4: “Source A” status OK contact (if the contact between “pin 4” and “pin 1” is closed, “Source A” is present and regular).
- Pin 5: “Source B” status OK contact (if the contact between “pin 5” and “pin 1” is closed, “Source B” is present and regular).
- Pin 6: Status OK contact (if the contact between “pin 6” and “pin 1” is closed, ATS functioning status is regular).
The following diagram shows the functioning of the contacts port.
ATTENTION: The pins of the contact port are able to carry maximum current of 8A and maximum voltage of 250Vac.
TECNOWARE s.r.l.
www.tecnoware.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>