TRANE A4AH6E31A1B30B 2.5 Ton Convertible Air Handler User Manual
- June 4, 2024
- Trane
Table of Contents
TRANE A4AH6E31A1B30B 2.5 Ton Convertible Air Handler
Outline Drawing
NOTE
- THIS UNIT IS APPROVED FOR INSTALLATION CLEARANCES TO COMBUSTIBLE MATERIAL AS STATED ON THE UNIT RATING NAMEPLATE
- ALL DIMENSIONS ARE REFERENCE DIMENSIONS.
PRODUCT DIMENSIONS
Air Handler Model| A| B| C| D| E| F| H| Flow Control| Gas Line Braze
A4AH6E31A1B| 46.77| 18.50| 16.50| 16.75| 4.68| 7.33| 20.09| TXV| 3/4
All dimensions are in inches
Product Specifications
MODEL | A4AH6E31A1B30B |
---|---|
RATED VOLTS/PH/HZ | 208-230/1/60 |
RATINGS (a) | See O.D. Specifications |
INDOOR COIL — Type | Plate Fin |
Rows — F.P.I. | 4 – 14 |
Face Area (sq. ft.) | 3.44 |
Tube Size (in.) | 3/8 |
Refrigerant Control | TXV |
Drain Conn. Size (in.)(b) | 3/4 NPT |
DUCT CONNECTIONS | See Outline Drawing |
INDOOR FAN — Type | Centrifugal |
Diameter-Width (In.) | 11 X 8 |
No. Used | 1 |
Drive – No. Speeds | Direct – 5 |
CFM vs. in. w.g. | See Fan Performance Table |
No. Motors — H.P. | 1 – 1/3 |
Motor Speed R.P.M. | 1050 |
Volts/Ph/Hz | 208-230/1/60 |
F.L. Amps | 2.8 |
FILTER | |
Filter Furnished? (c) | No |
REFRIGERANT | R-410A |
Ref. Line Connections | Brazed |
Coupling or Conn. Size — in. Gas | 3/4 |
Coupling or Conn. Size — in. Liq. | **** |
3/8
---|---
DIMENSIONS| H x W x D
Crated (In.)| 48-1/4 x 22-1/2 x 25-1/2
Uncrated| 46-3/4 x 18-1/2 x 21-1/8
WEIGHT|
Shipping (Lbs.) / Net (Lbs.)| 145/138
- These Air Handlers are A.H.R.I certified with various Split System Air Conditioners and Heat Pumps (AHRI STANDARD 210/240). Refer to the Split System Outdoor Unit Product Data Guides for performance data.
- 3/4” Male Plastic Pipe (Ref: ASTM 1785–76)
- Remote filter required.
Minimum Airflow CFM
A4AH6E31A1B30B
Heater| Minimum Heat Speed Tap
| With Heat Pump| Without Heat Pump
BAYHTR1504BRK, BAYHTR1504LUG, BAYHTR1505BRK, BAYHTR1505LUG| ****
Low
| ****
Low
BAYHTR1508BRK, BAYHTR1508LUG, BAYHTR1510BRK, BAYHTR1510LUG| ****
Med-High
| ****
Med-Low
BAYHTR1517BRK, BAYHTR3517LUG, BAYHTR3510LUG| ****
High
| ****
Med
Heater Pressure Drop Table
Airflow CFM
| Number of Racks| | Heater Racks
---|---|---|---
1| 2| 3| 4| Heater Model| No. of Racks
Air Pressure Drop — Inches W.G.| BAYHTR1504| 1
1800| 0.02| 0.04| 0.06| 0.14| BAYHTR1505| 1
1700| 0.02| 0.04| 0.06| 0.14| BAYHTR1508| 2
1600| 0.02| 0.04| 0.06| 0.13| BAYHTR1510| 2
1500| 0.02| 0.04| 0.06| 0.12| BAYHTR1517| 3
1400| 0.02| 0.04| 0.06| 0.12| BAYHTR3510| 3
1300| 0.02| 0.04| 0.05| 0.11| BAYHTR3517| 3
1200| 0.01| 0.04| 0.05| 0.10| BAYHTR3515| 3
1100| 0.01| 0.03| 0.05| 0.09| BAYHTR1523| 4
1000| 0.01| 0.03| 0.04| 0.09| BAYHTR1525| 4
900| 0.01| 0.03| 0.04| 0.08| |
800| 0.01| 0.03| | | |
700| 0.01| 0.02| | | |
600| 0.01| 0.02| | | |
Performance and Electrical Data
- See Product Data or Air Handler nameplate for approved combinations of Air Handlers and Heaters.
- Heater model numbers may have additional suffix digits.
Air Flow Performance
A4AH6E31A1B30B
EXTERNAL STATIC
(in w.g)
| AIRFLOW
Speed Taps — 208 – 230 VOLTS
| High| Med-High| Med †| Med-Low| Low
0.1| 1072| 985| 901| 820| 661
0.2| 1028| 940| 863| 774| 605
0.3| 983| 893| 820| 722| 540
0.4| 938| 845| 772| 666| 465
0.5| 891| 795| 719| 605| 381
0.6| 844| 744| 661| 539| 288
0.7| 796| 691| 598| 468|
Notes:
- Values are with wet coil, no filter, and no heaters
- FM Correction for dry coil = Add 3%
- † = Factory Setting
- In downflow applications, airflow must not exceed 1200 cm due to condensate blowoff.
- Low = Tap 1, Med-Low = Tap 2, Med = Tap 3, Med-High= Tap 4, High = Tap 5
Electrical Data
A4AH6E31A1B30B
Heater Model No.
| ****
No. of Circuits/ Phases
| 240 Volt| 208 Volt
Capacity| Heater Amps per Circuit| Minimum Circuit Ampacity| Maximum Overload
Protection| Capacity| Heater Amps per Circuit| Minimum Circuit Ampacity|
Maximum Overload Protection
kW| BTUH| kW| BTUH
No Heater| | | | 4.1 | 8| 15| | | 4.1 | 8| 15
BAYHTR1504BRK BAYHTR1504LUG| 1/1| 3.8| 13100| 16.0| 28| 30| 2.9| 9800| 13.8|
25| 25
BAYHTR1505BRK BAYHTR1505LUG| 1/1| 4.8| 16400| 20.0| 33| 35| 3.6| 12300| 17.3|
29| 30
BAYHTR1508BRK BAYHTR1508LUG| 1/1| 7.7| 26200| 32.0| 48| 50| 5.8| 19700| 27.7|
42| 45
BAYHTR1510BRK BAYHTR1510LUG| 1/1| 9.6| 32800| 40.0| 58| 60| 7.2| 24600| 34.6|
51| 60
BAYHTR1517BRK-
Circuit 1 (a)
| ****
2/1
| 9.6| 32800| 40.0| 58| 60| 7.2| 24600| 34.6| 51| 60
BAYHTR1517BRK-
Circuit 2
| 4.8| 16400| 20.0| 25| 25| 3.6| 12300| 17.3| 22| 25
BAYHTR3510LUG| 1/3| 9.6| 32800| 23.1| 36| 40| 7.2| 24600| 20.0| 32| 35
BAYHTR3517LUG| 1/3| 14.4| 49100| 34.6| 50| 50| 10.8| 36900| 30.0| 44| 45
BAYHTR1517BRK
with single circuit power source kit BAYSPEKT201A
| ****
1/1
| ****
14.4
| ****
49200
| ****
60.0
| ****
83
| ****
90
| ****
10.8
| ****
36900
| ****
51.9
| ****
73
| ****
80
-
= Motor Amps
- MCA and MOP for circuit 1 contain the motor amps.
Features and Benefits
- Galvanized metal cabinet with captured foil face insulation
- 2% or less air leakage
- R-4.2 Insulating Value
- Multi-Position UP/Down Flow, Horizontal Left /Right
- ALL Aluminum Coil
- Electric Heaters with polarized plug connections (sold as accessories)
- R-410A Thermal Expansion Valve
- ECM Motor (3.5 – 5 Ton Models )
- Low Voltage Pigtail Connections
- Draw Through Design
- Horizontal Drain pan
- Single Color
- Fused 24V Power
- 5-year warranty
- Optional extended warranty available
Important: Condensate management kit is required for all 5-ton air handler models installed in downflow applications.
About Trane and American Standard Heating and Air Conditioning Trane and American Standard create comfortable, energy efficient indoor environments for residential applications. For more information, please visit www.trane.com or www.americanstandardair.com.
The manufacturer has a policy of continuous data improvement and it reserves the right to change design and specifications without notice. We are committed to using environmentally conscious print practices.
A4AH6E31A1B-SUB-1B-EN 09 Mar 2022 Supersedes A4AH6E31A1B-SUB-1A-EN (December 2020)