COOPER Notification XB11 Strobe 29 Candela Hazardous Location Owner’s Manual

June 9, 2024
COOPER Notification

COOPER Notification logo XB11 Strobe 29 Candela Hazardous Location
Owner’s ManualCOOPER Notification XB11 Strobe 29 Candela Hazardous
Location

Description:

These certified strobes have been designed for use in potentially explosive gas and dust atmospheres and harsh environmental conditions.
The glass reinforced polyester enclosures are suitable for use offshore or onshore, where light weight combined with corrosion resistance is required.
The strobe housing is manufactured completely from a U.V. stable, glass reinforced polyester. Stainless steel screws and mounting bracket are incorporated ensuring a totally corrosion free product.
Units can be painted to customer specification and supplied with identification labels.

Features*:

  • UL Listed for USA and Canada
    – Hazardous locations: Class I, Div 2, Groups C & D
    Class I, Zones 1 & 2, AExd IIB T5
    – Ordinary locations: Visual-Signal Device

  • California State Fire Marshal (CSFM) Listed

  • ATEX approved

  • NEMA 4x & 6, IP66 and IP67

  • Certified temperature –67°F to +158°F (–55°C to +70°C)

  • Corrosion resistant GRP

  • Optional stainless steel backstrap

  • Various lens colors

  • Optional lens guard

  • 29 candela

  • 4 wire monitored connection

  • Available as a status light

  • Xenon

  • 24 VDC, 110 and 240 VAC

Architects and Engineers Specifications

Strobes for hazardous locations and harsh environments shall be UL and cUL listed for Class I, Division 2, Groups C&D, and Class I, Zones 1&2, AExd IIB T5 applications and shall be listed under UL Standard 1638 for Indoor/Outdoor use. The strobe appliances shall be constructed of lightweight, UV stable glass reinforced polyester, shall be corrosion resistant, and shall meet NEMA 4x, NEMA 6, IP 66 & IP 67 environmental requirements over a temperature range of -67°F to 158°F (-55°C to 70°C).
The strobe shall be rated to flash at 1 Hz with 29 candela per flash. Rated current draw shall not exceed 320 mA at 24 vdc. The strobe shall be capable of direct surface mounting in any direction.
Note: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Cooper Wheelock standard terms and conditions.

COOPER Notification XB11 Strobe 29 Candela Hazardous Location - ALL
DIMENSIONS IN MIL

Specification

Certification:| UL Listed for USA and Canada to:
– Hazardous locations:  Class I, Div 2 Groups C & D.
Class I, Zones 1 & 2 AExd IIB T5.
UL Listing No: E187894.
– Ordinary locations: Visual-Signal Device.
California State Fire Marshal (CSFM) Listed UL listing No. S8128.
ATEX approved:  EExd IIB T5/T6
Cert. No. 99 ATEX 2195X
CENELEC EN50014 and EN50018
---|---
Material:| Body: – Glass reinforced polyester (GRP).
Lens: – Glass.
Cover Screws + Backstrap: – Stainless steel 316.
Finish:| Natural black or painted to customer specification.
Weight:| 5.5 lb./2.5Kg.
Certified Temperature:|  –67°F to +158°F (–55°C to +70°C) hazardous locations
–67°F to +131°F (–55°C to +55°C) ordinary locations
Ingress Protection:| NEMA 4x & 6, IP66 & IP67.
Terminals:| 6 x 14AWG
Labels:| Duty/Tag Label optional.
Entries:| 2 x 1/2″ NPT
Strobe/Sounder Unit:| The strobe may be combined with a sounder to create a visual/audible alarm.
| DC| AC50/60 Hz
---|---|---
Voltage| 24| 110| 240
XB11 Tube Energy (Joules)| 5| 5| 5
Peak Current Consumption (mA)| 320| 100| 60
Effective Intensity (Cd)| 29| 29| 29
NOTE: The Cd figures are for a clear lens @ 1 Hz flash rate.

FOR COLORED LENSES

Color Red Blue Amber Green Yellow
 Multiplying  Factor 0.15 0.12 0.51 0.49 0.86

The photometric data has been verified by BSI.
A report is available if required.
Configuration Options:
The following code is designed to help in the selection of the correct unit. Build up the reference number by inserting the code for each component into the appropriate box.

COOPER Notification XB11 Strobe 29 Candela Hazardous Location -
Configuration Options

Standard Models

Series Model Number Order Code Description
XB11 XB11UL02406RNBNNNR 109201-001 Strobe, Red lens, 29 candela, 24 VDC,

Red Finish
XB11| XB11UL02406CNBNNNR| 109201-002| Strobe, Clear lens, 29 candela, 24 VDC, Red Finish
XB11| XB11UL02406RNBNNNN| 109201-003| Strobe, Red lens, 29 candela, 24 VDC, Black Finish
XB11| XB11UL11006ANBNNNR| 109201-007| Strobe, Amber lens, 20 candela, 110VAC, Red Finish
XB11| XB11UL11006RNBNNNR| 109201-008| Strobe, Red lens, 29 candela, 110VAC, Red Finish

WE ENCOURAGE AND SUPPORT NICET CERTIFICATION
3 YEAR WARRANTY
XB11 02/08

NJ Location
273 Branchport Ave.
Long Branch, NJ 07740
P: 800-631-2148
F: 732-222-8707
www.coopernotification.com| FL Location
7565 Commerce Ct.
Sarasota, FL 34243
P: 941-487-2300
F: 941-487-2389| VA Location
P: 877-459-7726
F: 703-294-6560
---|---|---

Cooper Notification is Wheelock®
COOPER Notification XB11 Strobe 29 Candela Hazardous Location - icon
2firealarmresources.comCOOPER
Notification logo

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals