NOTIFIER 5600 Series Mechanical Heat Detector Owner’s Manual

June 9, 2024
NOTIFIER

DN-6931:A1 · I-304
5600 Series
Mechanical Heat Detectors

Conventional Initiating Devices

GENERAL

System Sensor’s 5600 Series mechanical heat detectors offer property protection against fire and for non-life-safety installations, where smoke detectors are inappropriate.

Multiple configurations. The 5600 Series offers a full line of configurations to accommodate a broad range of applications. Both single- and dual-circuit models are offered, each available for low- and high-temperature ratings with either fixedtemperature or combination fixed-temperature/rate-of- rise (ROR) activation. The ROR element of the fixed/ROR models is restorable, to accommodate field-testing the unit.

Installation flexibility. To satisfy a variety of installations, the 5600 Series easily mounts to single-gang and octagonal backboxes. These models also accommodate 4″ (101.6 mm) square backboxes when used with a plaster ring. The mounting bracket is reversible to allow for flush- and surface-mount backbox installations.

Visual identification. The 5600 Series provides clear markings on the exterior of the unit to ensure that the proper detector is being used. Alphanumeric characters identify the activation method, as well as the temperature rating, in degrees Fahrenheit and Celsius. Fixed temperature models are identified “FX”, while combination fixed/rate-of-rise units are marked “FX/ROR”. The 5600 Series also provides a collector as a post- activation indicator. Once the detector has been activated, the collector drops from the unit to allow easy identification of the specific unit in alarm.

FEATURES

  • Multiple configurations available:
    • Fixed-temperature (non-resettable) or combination fixed (non-resettable)/rate-of-rise (self-restoring).
    • Low-temperature and high-temperature ratings.
    • Single-circuit and dual-circuit.
  • Easy-to-read alphanumeric identification of detector type and temperature rating.
  • External collector provides visual indication of activation.
  • Reversible mounting bracket for flush- and surface-mount installations.
  • Flexible mounting capabilities: single-gang, 3.5″ or 4″ octagonal, 4″ (101.6 mm) square with plaster ring.
  • Easy-to-use terminal screws provide a more positive wiring connection.
  • Low-profile design to coordinate with room aesthetics.

AGENCY LISTINGS AND APPROVALS

These listings and approvals apply to the modules specified in this document. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status.

  • UL Listed: S2101
  • ULC Listed: S2101 (all with “A” suffix)
  • MEA: 199-03-E
  • CSFM: 7270-1209:227, 7270-1653:167
  • FM Approved

SPECIFICATIONS

PHYSICAL SPECIFICATIONS

Maximum installation temperature:| For models 5601P, 5603, 5621, 5623: 100°F (38°C).
For models 5602, 5604, 5622, 5624: 150°F (65.6°C).
---|---
Alarm temperature:| For models 5601P, 5603, 5621, 5623: 135°F (57°C).
For models 5602, 5604, 5622, 5624: 194°F (90°C).
Rate-of-Rise Threshold:| 15°F (8.3°C) per minute (models 5601, 5602, 5621, 5622 only).
Operating Humidity Range:| 5% to 95% RH noncondensing.
Input Terminals:| non-polarized, accept 14 to 22 AWG (2.0 to 0.33 mm²).
Dimensions:| diameter with mounting bracket: 4.57″ (116 mm); height with mounting bracket: 1.69″ (43 mm).
Weight:|  6 oz. (170 grams).
Mounting Options:| 3.5″ (88.9 mm) octagonal backbox; 4″ (101.6 mm) octagonal backbox; single-gang backbox; 4″ (101.6 mm) square backbox with a square-to- round plaster ring.

ELECTRICAL SPECIFICATIONS

Operating Voltage Contact Ratings (resistive)
6 – 125 VAC 3.0 A
6 – 28 VDC 1.0 A
125 VDC 0.3 A
250 VDC 0.1 A

Mechanical heat detector shall be a System Sensor 5600 Series model number __, Listed to Underwriters Laboratories UL 521 for Heat Detectors for Fire Protective Signaling Systems. The detector shall be either a single-circuit or a dualcircuit type, normally open. The detector shall be rated for activation at either 135°F (57°C) or 194°F (90°C), and shall activate by means of a fixed-temperature thermal sensor, or a combination fixed-temperature/rate-of- rise thermal sensor. The rate-of-rise element shall be activated by a rapid rise in temperature, approximately 15°F (8.3°C) per minute. The detector shall include a reversible mounting bracket for mounting to 3.5-inch (88.9 mm) octagonal, 4-inch (101.6 mm) octagonal, single gang, and 4-inch (101.6 mm) square backboxes with a square-to-round plaster ring. Wiring connections shall be made by means of SEMS screws that shall accommodate 14 ­ 22 AWG wire. The detector shall contain alphanumeric markings on the exterior of the housing to identify its temperature rating and activation method. The rate-of-rise element of combination fixed-temperature/rate-of-rise models shall be restorable, to allow for field-testing. The detectors shall include an external collector that shall drop upon activation to identify the unit in alarm.

ORDERING INFORMATION

Model| Identification
Method on
Exterior| Circuit| Temperature
Rating| Activation| UL Protected Spacing,
10′ (3.048 m) Ceiling

---|---|---|---|---|---
5601 P| None| Single| 135°F (57°C)| Fixed-Temperature/Rate-of-Rise| 50 ft. x 50 ft. (15.24 m x 15.24 m)
5602| Lettering| Single| 194°F (90°C)| Fixed-Temperature/Rate-of-Rise| 50 ft. x 50 ft. (15.24 m x 15.24 m)
5603| Lettering| Single| 135°F (57°C)| Fixed-Temperature| 25 ft. x 25 ft. (7.62 m x 7.62 m)
5604| Lettering| Single| 194°F (90°C)| Fixed-Temperature| 25 ft. x 25 ft. (7.62 m x 7.62 m)
5621| Lettering| Dual| 135°F (57°C)| Fixed-Temperature/Rate-of-Rise| 50 ft. x 50 ft. (15.24 m x 15.24 m)
5622| Lettering| Dual| 194°F (90°C)| Fixed-Temperature/Rate-of-Rise| 50 ft. x 50 ft. (15.24 m x 15.24 m)
5623| Lettering| Dual| 135°F (57°C)| Fixed-Temperature| 25 ft. x 25 ft. (7.62 m x 7.62 m)
5624| Lettering| Dual| 194°F (90°C)| Fixed-Temperature| 25 ft. x 25 ft. (7.62 m x 7.62 m)

NOTE: Refer to NFPA 72 guidelines for spacing reductions when ceiling heights exceed 10 feet (3.048 m).

  • Add an “A” to part number for ULC model.

WIRING DIAGRAMS

©2010 by Honeywell International Inc. All rights reserved.
Unauthorized use of this document is strictly prohibited.

| This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice.
For more information, contact Notifier.
Phone: 203-484-7161, FAX: 203-484-7118. www.notifier.com|
---|---|---