NOTIFIER NCM-W Network Communications Module Installation Guide

June 9, 2024
NOTIFIER

12 Clintonville Road
Northford, CT 06472-1653 USA
www.notifier.com
NCM Installation Document
Network Communications Module NCM-W, NCM-F

Product Overview

The Network Communications Module (NCM) provides a means for connecting specific Notifier fire alarm control products to NOTI•FIRE•NET™. There are two types of NCMs available: NCM-W for connecting nodes with twisted-pair wire, and NCM-F for connecting nodes with fiber-optic cable.
1.1 The Network Communications Module for Wire (NCM-W)NOTIFIER NCM-W
Network Communications Module - Network Communications

  • Supports twisted-pair wire medium.
  • NFPA Style 4 (Class B) operation or NFPA Style 7 (Class A) operation.
  • Two programmable data thresholds.
  • Transformer coupling provides electrical isolation between nodes.
  • Pluggable terminal wiring with strain relief.
  • Pluggable service connector (feeds signal directly through) in the event that power must be removed from a node.
  • 312.5 Kbaud transmission rate.
  • Data is regenerated at each node.
  • Two network ports to allow simultaneous connection to fire alarm control panel and to programming computer
  • Enables software and database upload/download over NOTI•FIRE•NET™.
  • Refer to the NOTI•FIRE•NET™ Manual (Network Version 4.0 and Higher) for wiring length and threshold information.

1.2 The Network Communications Module for Fiber (NCM-F)NOTIFIER NCM-W
Network Communications Module - Network Communications 1

  • Supports fiber-optic medium.
  • NFPA Style 4 (Class B) or Style 7 (Class A) operation.
  • Data is immune to all environmental noise.
  • Optical isolation prevents ground loops.
  • NOTI•FIRE•NET™ fiber optic medium.
  • Fiber type:
  • 62.5/125 micrometers (multimode, 8 dB limit)
  • 50/125 micrometers (multimode, 4.2 dB limit)
  • Wavelength (1): 820 nanometers. (Use standard 850 nm fiber.)
  • Connectors: ST® Style (ST® is a registered trademark of AT &T ).
  • 312.5 Kbaud transmission rate.
  • Data is regenerated at each node.
  • Two network ports to allow simultaneous connection to fire alarm control panel and to programming computer.
  • Enables software and database upload/download over NOTI•FIRE•NET™.

Installing the NCM

2.1 Interconnecting the NCM-W
When wiring consecutive NCM-W boards, note that wiring may enter or exit at Port A or Port B as shown in Figure 4. NCM-W port-to-port wiring is not polarity sensitive. The use of Port A or Port B is arbitrary. An NCM-W may be connected to any of the following devices:

  • MIB-W
  • MIB-WF
  • NAM-232W
  • NCM-W (in another panel)
  • NCS-W network connection
  • RPT-W
  • RPT-WF

For information regarding these devices, refer to the documentation listed in Table 4 “Supplemental Documentation”. NOTIFIER NCM-W Network Communications
Module - Network Communications 2Note: Wiring from the NCM-W that is installed outside the building:

  • Cannot exceed 1000m (3280 ft.).
  • Must be in conduit and is to be buried in a trench separate from any power lines.
  • Cannot cross any power lines.

Figure 3 The NCM-W

TB100-1 CH-A (+) Channel-A Driver/Receiver
TB100-2 CH-A (-) Channel-A Driver/Receiver
TB100-3 CH-B (+) Channel-B Driver/Receiver
TB100-4 CH-B (-) Channel-B Driver/Receiver
TB100-5 Earth Ground

Table 1 NOTI•FIRE•NET™ Connections: NCM-W
Switch Functions:
Ground Fault Detection and Line Termination
The NCM-W provides two sets of switches to simplify network setup; in Figure 4 all are in the “off” position.

  • Enable ground fault detection by setting switches “on”: SW103 for Channel A, and SW101 for Channel B.
  • Activate on-board end-of-line resistors by setting switches “on”: SW100 for Channel A; SW102 for Channel B.

Note: Correct configuration depends on your network design; refer to the NOTI•FIRE•NET™ Manual (Network Version 4.0 and Higher).
2.2 Interconnecting the NCM-F
When connecting consecutive nodes/repeaters, note that fiber cable must exit one board on transmit (TX) and enter the next node/repeater on receive (RX). Also, note that the fiber-optic pair (RX, TX) from port A of one Node/Repeater may be connected to either Port A or Port B of another node/repeater (refer to Figure 5). An NCM-F may be connected to any of the following devices:

  • MIB-F
  • MIB-WF
  • NAM-232F
  • Another NCM-F
  • Network connection for NCS-F
  • RPT-F
  • RPT-WF

For information regarding these devices, refer to the NAM-232 and Repeater manuals listed in Table 4 “Supplemental Documentation”.
Note: See the NOTI•FIRE•NET™ Manual (Network Version 4.0 and Higher) for maximum fiberoptic cable attenuation.NOTIFIER NCM-W Network Communications
Module - Network Communications 4

J200 CH A Transmit
J201 CH A Receive
J202 CH B Transmit
J203 CH B Receive

Table 2 NOTI•FIRE•NET™ Connections: NCM-F
2.3 Mixing Wire & Fiber on One Network
In some networks, it may be necessary to mix twisted-pair wire and fiber-optic cable. There are two solutions for this situation.

  1. In any network, an RPT-WF may be used as an interface between wire and fiber.
  2. In a network that uses an AFP1010 or AM2020, a MIB-WF may also be used as the interface between wire and fiber.

See 1.2 “The Network Communications Module for Fiber (NCM-F)” for requirements and restrictions on the use of fiber optic cable. See the NOTI•FIRE•NET™ Manual (Network Version 4.0 and Higher) for a discussion of all compatible configurations.

Diagnostic Indicators

The NCM has LEDs that serve as diagnostic indicators to help in troubleshooting and system connection. Refer to Table 3 for a list of diagnostic indicators and their descriptions. Refer to Figure 6 for location of the diagnostic indicators.NOTIFIER NCM-W Network Communications Module -
Network Communications 5

LED Indicator LED Color LED Description
A HI (NCM-W only) Green Illuminates to indicate the NCM-W Port A is set for

high threshold.
B HI (NCM-W only)| Green| Illuminates to indicate the NCM-W Port B is set for high threshold.
RCD A| Green| Illuminates when the NCM is receiving data from NOTI•FIRE•NET™ on Port A.
RCD B| Green| Illuminates when the NCM is receiving data from NOTI•FIRE•NET™ on Port B.
STATA| Yellow| Illuminates when the NCM has not received valid data from NOTI•FIRE•NET™ on Port A for at least 16 seconds.
STATB| Yellow| Illuminates when the NCM has not received valid data from NOTI•FIRE•NET™ on Port B for at least 16 seconds.
RECON| Yellow| Illuminates when a reconfiguration on NOTI•FIRE•NET™ is in progress.
PULSE1| Green| Illuminates when the NCM is transmitting data to NOTI•FIRE•NET™.
RESET| Yellow| Illuminates when the microcontroller fails.
POWER| Green| Illuminates when +5 VDC is available

Table 3 Diagnostic Indicator Functions and Colors

Door-Mounting

Both NCM-W and NCM-F can be installed in any panel circuit module position; see your control panel installation manual. Additionally, the NCM-W can be door-mounted on the ADP-4B Dress Panel on a single-space blank plate (BMP-1) for mounting in a CAB-4 Series cabinet.
Note: The module cannot be mounted in the ADP-4B Dress Panel when a front slot of the CHS-4 or CHS-4N is occupied, or when either of the two front right positions of the CHS-M2 is occupied. Always be certain there is enough clearance to close the cabinet door when this installation is used.NOTIFIER
NCM-W Network Communications Module - Network Communications
6

Supplemental Documentation

The table below provides a list of document sources (manuals) containing additional information regarding the NCM and products that it can connect to. The NOTIFIER document (DOC-NOT) chart provides the current document revision.

F or information on… Refer to… Part No.
Networking NOTI•FIRE•NET™ Manual (for Network Version 4.0 and Higher) Onyx

NCS Network Control Station  (for Network Version 4.0 and Higher) NCS Network Control Station (for Network Version 4.0)
NFS-640 Installation
Operations
Programming
NCA Network Control Annunciator Media Interface Board (MIB) Manual NAM-232 Network Adaptor Module
RPT – W/WF/F Repeaters for NOTI•FIRE•NET™| 51584
51658
51585
51332
51333
51334
51482
50255
50038
50256
Off-line Programming Utility| VeriFire™ Tools CD on-line help file| VeriFire- TCD
Compatible Devices| Device Compatibility Document| 15378
Cabinets & Chassis| CAB-3/CAB-4 Series Installation Document BMP-1 Product Installation Document Also see your panel’s Installation Manual| 15330
51119

Table 4 Supplemental Documentation
Note: For module mounting instructions, refer to the documentation for your control panel

NCM Installation PN 51533:A1 03/27/03
www.PDF-Zoo.com
firealarmresources.com

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

NOTIFIER User Manuals

Related Manuals