PRODUCT

Description

The Cooper-Wheelock Series NS Horn Strobe Appliances will satisfy virtually all requirements for indoor, wall mount applications. The Series NH Horn and the horn portion of the Series NS include a select-able continuous horn tone or temporal pattern (Code 3) with selectable dBA settings of 90 or 95 dBA. Strobe options include 15/75cd or Coo-per-Wheelock’s patented Multi-Candela strobe with field selectable candela settings of 15/30/75/110cd. These versatile Horn Strobe Appliances may be synchronized when used in conjunction with the Wheelock SM or DSM Sync Modules or a Power Sup-ply with the Cooper- Wheelock patented Sync Protocol. Additionally, the audible may be silenced while maintaining strobe activation. All models of the Series NS and NH are designed for maximum performance, reliability and cost-effective-ness while meeting or exceeding the latest requirements of NFPA 72/ANSI 117.1/UFC and UL Standards 1971 and 464 as well as meeting ADA requirements concerning photosensitive epilepsy. NS Horn Strobe
NH Horn
Gamewell Cooper-Wheelock NS Series Horn Strobes and NH Series Horn
03 Multi-Candela Indicator (bottom of Strobe Lens)

General Notes

  • Strobes are designed to flash once per second minimum over their “Regulated Voltage Range”. Note that NFPA-72 specifies a flash rate of 1 to 2 flashes per second and ADA Guidelines specify a flash rate of 1 to 3 flashes per second.
  •  All candela ratings represent minimum effective Strobe intensity based on UL Standard 1971.
  •  Series NS Strobe products are listed under UL Standard 1971 for indoor use with a temperature range of 32°F to 120°F (0°C to 49°C) and maximum humidity of 93% (± 2%).
  •  Series NH horns are listed under UL Standard 464 for audible signal appli-ances (Indoor use only).
  •  “Regulated Voltage Range” is the newest terminology used by UL to identify the voltage range. Prior to this change UL used the terminology “Listed Voltage Range”.

Features

  •  Field Selectable Candela Settings 15/30/75/110cd (24 VDC Multi-Candela models) or 15/75cd in 12 or 24 VDC
  • Selectable Continuous Horn or Temporal (Code 3)
  • 2 Selectable dBA settings of 90 and 95 dBA in both tones
  • 12 and 24 VDC models with UL “Regulated Voltage” using filtered DC or unfiltered VRMS input voltage
  •  Patented Universal Mounting Plate
  •  Wall Mount
  •  ADA/NFPA/UFC/ANSI compliant
  • Complies with OSHA 29, Part 1910.165
  •  NH horn is selectable 12 or 24 VDC in 1 unit
  •  Synchronize with Wheelock SM or DSM Sync Module or a Power Supply with built-in sync protocol
  • Patent pending Universal Mounting Plate for single-gang, double-gang, 4” (10.16 cm) square, or 100 mm European backboxes, or Wheelock’s SHBB shallow surface backbox.
  •  Fast installation with IN/OUT screw terminals using #12 to #18 AWG wires

Listings
Listings and approvals below apply to the basic NS Series Strobes and NH Series Horns. In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status.

  • UL Listed: file E5946.
  • ULC Listed: files CS243 & CS356.
  • FM approved.
  • MEA approved: file 151-92-E.
  • CSFM approved: file 7125-0785:142

Engineer’s Specifications

The audible/visual notification appliances shall be Cooper-Wheelock Series NS Horn Strobe appliances and Series NH Horn appliances or approved equals. The Series NS appliances shall meet and be listed for UL Standard 1971(Emergency Devices for the Hearing-Impaired for Indoor Fire Protection Service). The Series NH Horn shall be UL Listed under Standard 464 (Fire Protective Signaling). The horn strobe shall be listed for indoor use and shall meet the requirements of FCC Part 15 Class B. All inputs shall be compatible with standard reverse polarity supervision of circuit wiring by the Fire Alarm Control Panel (FACP). The audible portion of the appliance shall have a minimum of two (2) field selectable settings for dBA levels (90 and 95 dBA) and shall have a choice of continuous or temporal (Code 3) audible outputs. The strobe portion of the appliance shall produce a flash rate of one (1) flash per second over the Regulated Voltage Range and shall incorporate a Xenon flashtube enclosed in a rugged Lexan lens. The Series NS shall be of low current design. Where wall mount, Multi-Candela appliances are specified, the strobe intensity shall have field selectable settings and shall be rated per UL Standard 1971 for 15/30/75/110 candela. The selector switch for selecting the candela setting shall be tamper resistant. The 15/75 candela strobe shall be specified when 15 candela UL Standard 1971 Listing with 75 candela on-axis is required (e.g. ADA compliance). When synchronization is required, the appliance shall be compatible with Cooper- Wheelock’s SM, DSM Sync Modules or a Power Supply with Cooper-Wheelock’s built-in Patented Sync Protocol. The strobes shall not drift out of synchronization at any time during operation. If the sync module or Power Supply fails to operate, (i.e., contacts remain closed), the strobes shall revert to a non-synchronized flash-rate. The appliance shall also be designed so that the audible signal may be silenced while maintaining strobe activation. The Series NS Horn Strobes and NH horn shall incorporate a Patented Universal Mounting Plate that shall allow mounting to a single-gang, double-gang, 4-inch square, 100mm European type backboxes, or the SHBB Surface Backbox. If required, an NATP (Notification Appliance Trim plate) shall be provided.
All notification appliances shall be backward compatible.

Wiring DiagramGamewell Cooper-Wheelock NS Series Horn Strobes and NH
Series Horn 04 NS AND NH APPLIANCES SYNCHRONIZED WITH SM MODULE SINGLE CLASS “B” NAC CIRCUIT WITH AUDIBLE SILENCE FEATURE
Gamewell Cooper-Wheelock NS Series Horn Strobes and NH Series Horn
05NS AND NH APPLIANCES SYNCHRONIZED WITH DSM MODULE DUAL CLASS “A” NAC CIRCUIT WITH NO AUDIBLE SILENCE FEATURE
Gamewell Cooper-Wheelock NS Series Horn Strobes and NH Series Horn
06 NOTE: NS/NH must be set on Code 3 horn to achieve synchronized temporal (Code 3) tone. Refer to instruction (P38983, P83600 respectively).
WARNING: CONTACT COOPER-WHEELOCK FOR THE CURRENT IN-STALLATION INSTRUCTIONS (P83983) SERIES NS-24MCW, (P84234) SERIES NS-12 AND 24 VDC SINGLE CANDELA MODELS, (P83600) SERIES NH AND “GENERAL INFORMATION” SHEET (P82380) ON THESE PROD-UCTS. THESE DOCUMENTS UNDERGO PERIODIC CHANGES. IT IS IMPOR-TANT THAT YOU HAVE CURRENT IN-FORMATION ON THESE PRODUCTS. THESE MATERIALS CONTAIN IMPOR-TANT INFORMATION THAT SHOULD BE READ PRIOR TO SPECIFYING OR IN-STALLING THESE PRODUCTS, IN-CLUDING:

  • TOTAL CURRENT REQUIRED BY ALL APPLIANCES CONNECTED TO SYSTEM SECONDARY POWER SOURCES.
  • FUSE RATINGS ON NOTIFICATION AP-PLIANCE CIRCUITS TO HANDLE PEAK CURRENTS FROM ALL APPLIANCES ON THOSE CIRCUITS.
  • COMPOSITE FLASH RATE FROM MUL-TIPLE STROBES WITHIN A PERSON’S FIELD OF VIEW.
  • ADDING, REPLACING OR CHANGING AP-PLIANCES OR CHANGING CANDELA SETTINGS WILL AFFECT CURRENT DRAW.
  •  RECALCULATE CURRENT DRAW TO IN-SURE THAT THE TOTAL AVERAGE CURRENT AND TOTAL PEAK REQUIRED BY ALL APPLIANCES DO NOT EXCEED THE RATED CAPACITY OF THE POWER SOURCES OR FUSES.
  •  THE VOLTAGE APPLIED TO THESE PRODUCTS MUST BE WITHIN THEIR “REGULATED VOLTAGE RANGE”.
  • INSTALLATION OF 110 CANDELA STROBE PRODUCTS IN SLEEPING AR-EAS.
  • INSTALLATION IN OFFICE AREAS AND OTHER SPECIFICATION AND INSTALLA-TION ISSUES.
  • THESE APPLIANCES ARE NOT DE-SIGNED TO BE USED ON CODED SYS-TEMS IN WHICH THE APPLIED VOLTAGE IS CYCLED ON AND OFF.
  • FAILURE TO COMPLY WITH THE INSTAL-LATION INSTRUCTIONS OR GENERAL INFORMATION SHEETS COULD RESULT IN IMPROPER INSTALLATION, APPLICA-TION, AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUA-TION, WHICH COULD RESULT IN PROP-ERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
  • CONDUCTOR SIZE (AWG), LENGTH AND AMPACITY SHOULD BE TAKEN INTO CONSIDERATION PRIOR TO DESIGN AND INSTALLATION OF THESE PROD-UCTS, PARTICULARLY IN RETROFIT IN-STALLATIONS.

Specification & Ordering Information

MODEL| STROBE CANDELA| NON- SYNC| SYNC W/SM, DSM| 24
VDC| 12
VDC| **2
WIRE| MOUNTING OPTIONS***| AGENCY APPROVALS
---|---|---|---|---|---|---|---|---
UL| MEA| CSFM| FM| BFP
NS-24MCW-FR| 15/30/75/110| X| X| X| –| X| B,D,E,F,G,H,J,N,O,R,X| X| X| X| X| X
NS-24MCW-FW| 15/30/75/110| X| X| X| –| X| B,D,E,F,G,H,J,N,O,R,X| X| X| X| X| X
NS-241575W-FR| 15 (75 on axis)| X| X| X| –| X| B,D,E,F,G,H,J,N,O,R,X| X| X| X| X| X
NS-121575W-FR| 15 (75 on axis)| X| X| –| X| X| B,D,E,F,G,H,J,N,O,R,X| X| X| X| X| X
**
NH-12/24-R| 12V
24V| X| X| X| X| X| B,D,E,F,G,H,J,N,O,R,X| X| X| X| X| ** X
Table 1: Ratings Per UL Standard 1971**

Model| Input Voltage VDC| Regulated Voltage Range VDC/FWR| Strobe Candela (CD)
NS-24MCW| 24| 16.0 – 33.0| 15/30/75/110
NS-241575W| 24| 16.0 – 33.0| 15 (75 on Axis)
NS-121575W| 12| 8.0 – 17.5| 15 (75 on Axi)
Table 2: *Average RMS Current Ratings

NS-24MCW with High (95 dBA) Setting
Voltage| 15cd| 30cd| 75cd| 110cd
16.0 VDC| .077| .113| .195| .268
24.0 VDC| .065| .087| .134| .174
33.0 VDC| .069| .082| .117| .134
NS-24MCW with Low (90 dBA) Setting
Voltage| 15cd| 30cd| 75cd| 110cd
16.0 VDC| .070| .106| .188| .261
24.0 VDC| .052| .072| .126| .158
33.0 VDC| .045| .060| .097| .114
Table *3: Average RMS Current Ratings**

NS-241575W
Voltage| High (95) dBA| Low (90) dBA
16.0 VDC| .120| .116
24.0 VDC| .094| .093
33.0 VDC| .102| .078
NS-121575W
Voltage| High (95) dBA| Low (90) dBA
8.0 VDC| .341| .324
12.0 VDC| .251| .265
17.5 VDC| .216| .188
*Table  4: Ave r age  M e an Current Ratings  NH Horn  24 Volt M ode ls**

Voltage| High (95) dBA| Low   (90) dBA
16.0 V DC| .019| .017
24.0 V DC| .028| .022
33.0 V DC| .039| .027

  • Average RMS Current is per UL average RMS method and Average Mean Current is per UL average mean method. NH models use average mean current. For rated In Rush and Peak current across the UL listed voltage range for both filtered DC and unfiltered VRMS (FWR), see installation instructions.

Refer to mounting options.

Table 5: dBA Ratings for Series NS/NH Horn

Description| Volume| Reverberant dBA @ 10 ft. per UL 464| Anechoic dBA @ 10 ft.
12 VDC| 24 VDC| 12 VDC| 24 VDC
Continous
Horn| High| 83| 87| 89| 95
Low| 76| 81| 84| 90
Code 3
Horn| High| 79| 82| 89| 95
Low| 72| 76| 84| 90
SYNC MODELS/POWER SUPPLY

M ODEL NUM BER

| INP UT
VOLTAGE (VDC)| AVERAGE MEAN
CURRENT @ 24 VDC| M OUNTING OP TIONS
SM-12/24-R| 24| .028| W
DSM-12/24-R| 24| .035| W

NOTES:
SM Sync Module is rated for 3.0 amperes @ 24 VDC;
DSM Sync Module is rated for 3.0 amperes per circuit. The maximum number of interconnected DSM Modules is twenty (20).
Specifications and wiring information are provided for information only and are believed to be accurate. Gamewell-FCI assumes no responsibility for their use. Data and design are subject to change without notice. Installation and wiring instructions shipped with the product shall always be used for actual installation. For more information, contact Gamewell-FCI.
Gamewell-FCI
12 Clintonville Road
Northford, CT 06472-1610
Phone: 203-484-7161
Fax: 203-484-7118
www.gamewell-fci.com