SIEMENS FH2016 EBA2001 Booster Amplifier Enclosure Installation Guide
- June 9, 2024
- SIEMENS
Table of Contents
SIEMENS FH2016 EBA2001 Booster Amplifier Enclosure Installation Guide
Legal notice
Technical specifications and availability subject to change without notice. ©
2014 Copyright by Siemens Industry, Inc.
Transmittal, reproduction, dissemination and/or editing of this document as well as utilization of its contents and communication thereof to others without express authorization are prohibited. Offenders will be held liable for payment of damages. All rights created by patent grant or registration of a utility model or design patent are reserved.
Issued by: Siemens Industry, Inc. Building Technologies Division 8 Fernwood
Road Florham Park, NJ 07932 Tel. +1
973-593-2600
www.sbt.siemens.com/FIS
Edition: 2014-10-02 Document ID: A6V10437426_en–_a
1 Enclosure (EBA2001) FH2016
1.1 Description
The enclosure (EBA2001) FH2016 is for installing components for the booster amplifier (100 W) EBA2001 and has the following features:
- l Pre-stamped openings for cable supplies
- EMC-protected area for installed components
- Closable door
- Four-point wall fastening
Information on EBA2004-A1
You will find more information on the booster amplifier mainboard (100 W)
EBA2004-A1 in document A6V10407858, e.g.
– Designation and order number
– Requirements for installation
– Complete installation instructions
1.2 Enclosure overviews (EBA2001)
Complete overview of the enclosure (EBA2001) FH2016
- Door with lock, open
- Ground cable for door/back box
- 2x cable channels, L=130 mm/5.12″
- Back box
- Ground cable for power supply (170W) FP2011
Dimension drawing for the back box with mounting positions
Dimensions and mounting positions
- A 4x threaded rods for the power supply (170W) FP2011
- B 2x threaded sleeves for the shield connection kit (EBA2001) FHA2045
- C 11x threaded sleeves for the booster amplifier mainboard (100W) EBA2004
- D 2x fixing holes for the battery bracket (EBA2001) FHA2044
- E 4x installation holes for the back box
- F 2x threaded rods for connecting the ground cable
- G 4x fixing holes for the cable channels
The installation depth is 105 mm/4.13″ and the total depth to the front of the door when closed is 132 mm/5.2″.
Dimension drawing for cable entries
Dimensions of the cable entries
-
A B … G H, N 49.5 mm/1.95″ 60 mm/2.36″ 46 mm/1.81″
-
I, J, K 60 mm/2.36″
-
O, P, Q 60 mm/2.36″
-
R, L 358 mm/14.1″
-
M 43.1 mm/1.7″ from the installation holes on the back or from the wall for all cable openings *
-
All cable openings are pre-stamped to a diameter of 25.4 mm/1″.
1.3 Installing the power supply (170W) FP2011
The FP2011 is supplied ready to install with 4 locknuts and a pre-assembled
connecting cable for the 24 V connection.
Installation of the power supply (170W) FP2011
in the enclosure (EBA2001) FH2016
- 4x threaded rods in the back box of the enclosure FH2016
- 4x fixing holes
- 4x #10 locknuts
- Power supply (170 W) FP2011
- Ground cable for earthing the power supply (170W) FP2011
- 1. Position the FP2011 (4) as shown with the mains connection on the right.
- 2. Install the FP2011 (4) to the threaded rods (1) for the back box using the four nuts (3).
- 3. Connect the ground cable (5) to the FP2011 (4).
Information on how to wire the FP2011 can be found in the A6V10407858 installation instructions.
1.4 Technical data
Issued by Siemens Industry, Inc. Building Technologies Division 8 Fernwood Road Florham Park, NJ 07932 Tel. +1 973-593-2600 www.sbt.siemens.com/FIS
© 2014 Siemens Industry, Inc. Technical specifications and availability subject to change without notice.
Document ID Edition
A6V10437426_en–_a 2014-10-02
SAP order no.: A5Q00056914