INTRODUCTION

The FDBZ492-RTL Remote Alarm Indicator (Figure 1) works with the FDBZ492-R or FDBZ492-PR Air Duct Housing with Relays. The LED on the remote indicator mimics the color of the LED on the detector. Use the re-mote indicator in applications where the detector is not easily viewed, such as air ducts and drop ceilings.

The FDBZ492-RTL also works with FDBZ492-HR to monitor and test its relay output. Its LED will indicate if the relay is in standby (GRN) or alarm (RED) state. The FDBZ492-RTL provides a key operated detector test function. When this key is turned to the Test posi-tion, the relay on the FDBZ492-R, FDBZ492-PR and FDBZ492-HR Air Duct Housing will activate and the LED will flash red.
When the key is turned to the Normal position, the relay on the FDBZ492-R, FDBZ492-PR and FDBZ492-HR Air Duct Housing will deactivate and the LED will flash green.

Each FDBZ492-R or FDBZ492-PR Air Duct Housing with Relays can drive one FDBZ492-RTL; however, the total number of detectors and remote indicators must not exceed 30 devices on an initiating zone. The FDBZ492-RTL contains an LED indicator that flashes in one of three colors: green, yellow, or red. When the FDBZ492-R or FDBZ492-PR Air Duct Hous-ing with Relays flashes, the remote indicator flashes in the same color. The flashes occur approximately every 7 seconds and are described in Table 1.

LED Status Indicates
Green Normal supervisory operation. Smoke sensitivity within rated limits.
Yellow Detector requires service or is operating beyond its environmental

specifications or outside of the detector sensitivity range.
Red| Alarm condition. LED flashes every 2.5 seconds
No flash| Detector or FDBZ492-RTL is not powered or requires repair.

Applicable to conventional detectors only

INSTALLATION

The remote indicator may be placed up to 25 feet away from its associated detector using 14-18 gauge wire.

  1. Use a single-gang switch box (user supplied) for mounting the FDBZ492-RTL.
  2. Wire as shown in Figure 2.
  3. Electrical Ratings: 0.2mA (max) @ 24VDC
  4. Refer to the FDBZ492 Installation Instructions, P/N A6V10336866, for connection to the addressable detector air duct housing.SIEMENS-FDBZ492-RTL-Remote-Alarm-Indicator-FIG-1

Siemens Industry, Inc. Building Technologies Division Florham Park, NJ.
P/N A6V10335450_b_en.

Siemens Canada Limited
Building Technologies Division 2 Kenview Boulevard Brampton, Ontario L6T 5E4 Canada.

firealarmresources.com.