SIEMENS REL-EOL Releasing End Line Module

Installation Instructions

MODEL REL-EOL
Releasing End of Line Module

The REL-EOL Releasing End of Line module (shown in Figure 1) comes with one diode that is preinstalled and an additional diode which is only used for releasing applications using the CRM-4 and CSM-4 (See Figure 2). Also contained are three end of line resistors to be field installed depending on use with the following releasing modules:

| REL-EOL RESISTORS
---|---
Releasing Module| Part Number| Value
| CSM-4| 140-034679| 2.2K, 1/2W
| ZIC-4A| 140-034677| 24K, 1/2W
R X | FS-REL

MPC-REL

| 140-034677

140-034677

| 24K, 1/2W

24K, 1/2W

| XCI2 001-U1| 140-034677| 24K, 1/2W
| RM-30U/RU| 140-050720| 5.6K, 1/2W

SIEMENS REL-EOL-Releasing-End-Line-Module-01 R X TO BE FIELD INSTALLED DEPENDING ON MODEL USED WITH REFERENCE TO RELEASING MODULE INSTALLATION INSTRUCTIONS.
Figure 1
EOLR Detail

For specific wiring instructions, refer to the following installation instructions:

RELEASING INSTALLATION INSTRUCTIONS

System| Releasing Module| Installation Instruction
System 3 (CP-35)| RM-30U/RU| P/N 315-085100
MXL/MXLV| CSM-4| P/N 315-090854
FireFinder XLS| ZIC-4A| P/N 315-033050
FS-250| FS-REL| P/N 315-049570
MPC-6000| MPC-REL| P/N 315-049570FA
FS-20| XCI2 001-U1| P/N A6V10315050

THIS ADDITIONAL DIODE IS ONLY TO BE USED FOR RELEASING APPLICATIONS USING THE CRM-4 AND CSM-4.
Figure 2
Diode Detail

Siemens Industry, Inc. Building Technologies Division Florham Park, NJ
P/N 315-096357-6

Siemens Canada Limited
Building Technologies Division
2 Kenview Boulevard
Brampton, Ontario L6T 5E4 Canada