aspar Mini Modbus 1AI Expansion Module User Manual

June 9, 2024
aspar

aspar logo Mini Modbus 1AI
Expansion Module – 1 analog input, 1 digital output
Version 1.5
User Manual

Mini Modbus 1AI Expansion Module

RS485 MODBUS Module 8AI
Thank you for choosing our product.
This manual will help you with proper support and proper operation of the device.
The information contained in this manual have been prepared with utmost care by our professionals and serve as a description of the product without incurring any liability for the purposes of commercial law.
This information does not release you from the obligation of own judgement and verification.
We reserve the right to change product specifications without notice.
Please read the instructions carefully and follow the recommendations contained therein.
WARNING!
Failure to follow instructions can result in equipment damage or impede the use of the hardware or software.

Safety rules

  • Before first use, refer to this manual
  • Before first use, make sure that all cables are connected properly
  • Please ensure proper working conditions, according to the device specifications (eg: supply voltage, temperature, maximum power consumption)
  • Before making any modifications to wiring connections, turn off the power supply

Module Features

2.1. Purpose and description of the module
1AI module allows voltage or current measurement and has one digital put-put.
Values are read via RS485 (Modbus), so we can easily integrate the module with popular PLCs, HMI or PC equipped with the appropriate adapter.
The device has 1 input to voltage measurement and 1 input for current measurement (both inputs can be used in this same time). In addition, the module is equipped with 1 configurable digital output (PNP or NPN type).
This module is connected to the RS485 bus with twisted-pair wire.
Communication is via MODBUS RTU or MODBUS ASCII. The use of 32-bit ARM core processor provides fast processing and quick communication. The baud rate is configurable from 2400 to 115200.
The module is designed for mounting on a DIN rail in accordance with DIN EN 5002.
The module is equipped with a set of LEDs used to indicate the status of inputs and outputs useful for diagnostic purposes and helping to find errors.
Module configuration is done via USB by using a dedicated computer program.
You can also change the parameters using the MODBUS protocol.
2.2. Technical Specifications

Power Supply Voltage 10-38VDC; 20-28VAC
Maximum Current 70 mA @ 12V / 38 mA @ 24V
Inputs No of inputs 2
Voltage input -10V to 10V
Current input -20mA to 20mA
Measurement resolution 16 bits
ADC processing time 70ms / channel
Voltage measurement error Max ±1.7%
Current measurement error Max ±0.1%
Digital outputs Maximum current and voltage 250mA / 50V
Temperature Work -10 °C – +50°C
Storage -40 °C – +85°C
Connectors Power Supply 2 pin
Communication 3 pin
Inputs & Outputs 2 x 3 pin
Configuration Mini USB
Size Height 90 mm
Length 56 mm
Width 17 mm
Interface RS485 Up to 128 devices

2.3. Dimensions of the product
Look and dimensions of the module are shown below. The module is mounted directly to the rail in the DIN industry standard.

Communication configuration

3.1. Grounding and shielding
In most cases, IO modules will be installed in an enclosure along with other devices which generate electromagnetic radiation. Examples of these devices are relays and contactors, transformers, motor controllers etc. This electromagnetic radiation can induce electrical noise into both power and signal lines, as well as direct radiation into the module causing negative effects on the system. Appropriate grounding, shielding and other protective steps should be taken at the installation stage to prevent these effects. These protective steps include control cabinet grounding, module grounding, cable shield grounding, protective elements for electromagnetic switching devices, correct wiring as well as consideration of cable types and their cross sections.
3.2. Network Termination
Transmission line effects often present a problem on data communication networks. These problems include reflections and signal attenuation.
To eliminate the presence of reflections from the end of the cable, the cable must be terminated at both ends with a resistor across the line equal to its characteristic impedance. Both ends must be terminated since the direction of propagation is bidirectional. In the case of an RS485 twisted pair cable this termination is typically 120 Ω.
3.3. Types of Modbus Registers
There are 4 types of variables available in the module

Type| Beginning address| Variable| Access| Modbus Command
---|---|---|---|---
1| 00001| Digital Outputs| Bit Read & Write| 1, 5, 15
2| 10001| Digital Inputs| Bit Read| 2
3| 30001| Input Registers| Registered Read| 3
4| 40001| Output Registers| Registered Read & Write| 4, 6, 16

3.4. Communication settings
The data stored in the modules memory are in 16-bit registers. Access to registers is via MODBUS RTU or MODBUS ASCII.
3.4.1. Default settings

Parameter name Value
Address 1
Baud rate 19200
Parity No
Data bits 8
Stop bits 1
Reply Delay [ms] 0
Modbus Type RTU

3.4.2. Configuration registers

Modbus Dec Hex Name Values

Address
40002| 1| 0x01| Address| From 0 to 255
40003| 2| 0x02| Baud rate| 0 – 2400
1 – 4800
2 – 9600
3 – 19200
4 – 38400
5 – 57600
6 – 115200
other – value * 10
40005| 4| 0x04| Parity| 0 – none
1 – odd
2 – even
3 – always 1
4 – always 0
40004| 3| 0x03| Stop Bits LSB| 1 – one stop bit
2 – two stop bits
40004| 3| 0x03| Data Bits MSB| 7 – 7 data bits
8 – 8 data bits
40006| 5| 0x05| Response delay| Time in ms
40007| 6| 0x06| Modbus Mode| 0 – RTU
1 – ASCII

Indicators

Indicator Description
ON LED indicates that the module is correctly powered.
TX The LED lights up when the unit received the correct packet and sends the

answer.
AIV, AII| LED indicates that the signal to input is connected and is different from 0
DO| LED indicates that the output is on.

Block diagram

Module Connection

aspar Mini Modbus 1AI Expansion Module - Module
Connection

Modules Registers

7.1. Registered access

Modbus| Dec| Hex| Register Name| Access| Description
---|---|---|---|---|---
30001| 0| 0x00| Version/Type| Read| Version and Type of the device
30002| 1| 0x01| Address| Read| Module Address
40003| 2| 0x02| Baud rate| Read & Write| RS485 baud rate
40004| 3| 0x03| Stop Bits & Data Bits| Read & Write| No of Stop bits & Data Bits (see 3.4.2)
40005| 4| 0x04| Parity| Read & Write| Parity bit
40006| 5| 0x05| Response Delay| Read & Write| Response delay in ms
40007| 6| 0x06| Modbus Mode| Read & Write| Modbus Mode (ASCII or RTU)
40010| 9| 0x09| Filter| Read & Write| Measurement filtering, value from 1 to 10
40033| 32| 0x20| Received packets LSB| Read & Write| No of received packets
40034| 33| 0x21| Received packets MSB| Read & Write
40035| 34| 0x22| Incorrect packets LSB| Read & Write| No of received packets with error
40036| 35| 0x23| Incorrect packets MSB| Read & Write
40037| 36| 0x24| Sent packets LSB| Read & Write| No of sent packets
40038| 37| 0x25| Sent packets MSB| Read & Write
30051| 50| 0x32| Inputs| Read| Connected inputs
Bit in high state → signal is connected
40052| 51| 0x33| Outputs| Read & Write| Alarms state bit no. 3 digital output
30053| 52| 0x34| Voltage| Read| Voltage in μV
30054| 53| 0x35| Current| Read| Current in μA or ‰
30055| 54| 0x36| Alarm – max voltage| Read & Write| Maximum value of voltage excess which causes set bit no 1 in the register 40052
30056| 55| 0x37| Alarm – min voltage| Read & Write| Minimum value of voltage. If voltage drops below this voltage bit no 1 in the register 40052 is set.
30057| 56| 0x38| Alarm – max current| Read & Write| Maximum value of current excess which causes set bit no 1 in the register 40052
30058| 57| 0x39| Alarm – min current| Read & Write| Minimum value of current. If current drops below this voltage bit no 1 in the register 40052 is set.
30059| 58| 0x3A| Voltage alarm configuration| Read & Write| Alarms configuration

0 – alarms state depends on actual values 1 – alarms state need to clear by master

30060| 59| 0x3B| Current alarm configuration| Read & Write
30061| 60| 0x3C| Voltage input configuration| Read & Write| 0 – OFF
1 – 0 .. 10V
2 – -10 .. 10V
3 – 0 .. 1V
4 – -1 .. 1V
40062| 61| 0x3D| Current input configuration| Read & Write| 0 – OFF
1 – 0 .. 20mA (in μA)
2 – 4 .. 20mA (in ‰)
3 – -20mA .. 20mA (in μA)
40063| 62| 0x3E| Digital output configuration| Read & Write| Digital output configuration
0 – output controlled by master
1 – output state depends voltage
2 – output state depends current
+256 – output set if value is greater than alarm value (40065 register) („cooling”) +512 – output set if value is below than alarm value (40065 register) („warming”)
40064| 63| 0x3F| Alarm value| Read & Write| Alarm value
40065| 64| 0x40| Alarm hysteresis| Read & Write| Hysteresis for alarm

7.2. Bit access

Modbus Address| Dec Address| Hex Address| Register name| Access| Description
---|---|---|---|---|---
801| 800| 0x320| Voltage input| Read| Voltage input state
802| 801| 0x321| Current input| Read| Current input state
817| 816| 0x330| Voltage alarm| Read & Write| Voltage alarm state
818| 817| 0x331| Current alarm| Read & Write| Current alarm state
819| 818| 0x332| Digital output| Read & Write| Digital output state

Configuration software

Modbus Configurator is software that is designed to set the module registers responsible for communication over Modbus network as well as to read and write the current value of other registers of the module. This program can be a convenient way to test the system as well as to observe real-time changes in the registers.
Communication with the module is done via the USB cable. The module does not require any drivers.

aspar Mini Modbus 1AI Expansion Module - Configuration
softwareConfigurator is a universal program, whereby it is possible to configure all available modules.aspar
Mini Modbus 1AI Expansion Module - universal program

Manufactured for: Aspar s.c.
ul. Oliwska 112
80-209 Chwaszczyno Poland
ampero@ampero.eu
www.ampero.eu
tel. +48 58 351 39 89; +48 58 732 71 73
Expansion Module – 1 analog input, 1 digital output
aspar logo

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals