aspar Mini Modbus 1AI Expansion Module User Manual
- June 9, 2024
- aspar
Table of Contents
Mini Modbus 1AI
Expansion Module – 1 analog input, 1 digital output
Version 1.5
User Manual
Mini Modbus 1AI Expansion Module
RS485 MODBUS Module 8AI
Thank you for choosing our product.
This manual will help you with proper support and proper operation of the
device.
The information contained in this manual have been prepared with utmost care
by our professionals and serve as a description of the product without
incurring any liability for the purposes of commercial law.
This information does not release you from the obligation of own judgement and
verification.
We reserve the right to change product specifications without notice.
Please read the instructions carefully and follow the recommendations
contained therein.
WARNING!
Failure to follow instructions can result in equipment damage or impede the
use of the hardware or software.
Safety rules
- Before first use, refer to this manual
- Before first use, make sure that all cables are connected properly
- Please ensure proper working conditions, according to the device specifications (eg: supply voltage, temperature, maximum power consumption)
- Before making any modifications to wiring connections, turn off the power supply
Module Features
2.1. Purpose and description of the module
1AI module allows voltage or current measurement and has one digital put-put.
Values are read via RS485 (Modbus), so we can easily integrate the module with
popular PLCs, HMI or PC equipped with the appropriate adapter.
The device has 1 input to voltage measurement and 1 input for current
measurement (both inputs can be used in this same time). In addition, the
module is equipped with 1 configurable digital output (PNP or NPN type).
This module is connected to the RS485 bus with twisted-pair wire.
Communication is via MODBUS RTU or MODBUS ASCII. The use of 32-bit ARM core
processor provides fast processing and quick communication. The baud rate is
configurable from 2400 to 115200.
The module is designed for mounting on a DIN rail in accordance with DIN EN
5002.
The module is equipped with a set of LEDs used to indicate the status of
inputs and outputs useful for diagnostic purposes and helping to find errors.
Module configuration is done via USB by using a dedicated computer program.
You can also change the parameters using the MODBUS protocol.
2.2. Technical Specifications
Power Supply | Voltage | 10-38VDC; 20-28VAC |
---|---|---|
Maximum Current | 70 mA @ 12V / 38 mA @ 24V | |
Inputs | No of inputs | 2 |
Voltage input | -10V to 10V | |
Current input | -20mA to 20mA | |
Measurement resolution | 16 bits | |
ADC processing time | 70ms / channel | |
Voltage measurement error | Max ±1.7% | |
Current measurement error | Max ±0.1% | |
Digital outputs | Maximum current and voltage | 250mA / 50V |
Temperature | Work | -10 °C – +50°C |
Storage | -40 °C – +85°C | |
Connectors | Power Supply | 2 pin |
Communication | 3 pin | |
Inputs & Outputs | 2 x 3 pin | |
Configuration | Mini USB | |
Size | Height | 90 mm |
Length | 56 mm | |
Width | 17 mm | |
Interface | RS485 | Up to 128 devices |
2.3. Dimensions of the product
Look and dimensions of the module are shown below. The module is mounted
directly to the rail in the DIN industry standard.
Communication configuration
3.1. Grounding and shielding
In most cases, IO modules will be installed in an enclosure along with other
devices which generate electromagnetic radiation. Examples of these devices
are relays and contactors, transformers, motor controllers etc. This
electromagnetic radiation can induce electrical noise into both power and
signal lines, as well as direct radiation into the module causing negative
effects on the system. Appropriate grounding, shielding and other protective
steps should be taken at the installation stage to prevent these effects.
These protective steps include control cabinet grounding, module grounding,
cable shield grounding, protective elements for electromagnetic switching
devices, correct wiring as well as consideration of cable types and their
cross sections.
3.2. Network Termination
Transmission line effects often present a problem on data communication
networks. These problems include reflections and signal attenuation.
To eliminate the presence of reflections from the end of the cable, the cable
must be terminated at both ends with a resistor across the line equal to its
characteristic impedance. Both ends must be terminated since the direction of
propagation is bidirectional. In the case of an RS485 twisted pair cable this
termination is typically 120 Ω.
3.3. Types of Modbus Registers
There are 4 types of variables available in the module
Type| Beginning address| Variable| Access| Modbus
Command
---|---|---|---|---
1| 00001| Digital Outputs| Bit Read & Write| 1, 5, 15
2| 10001| Digital Inputs| Bit Read| 2
3| 30001| Input Registers| Registered Read| 3
4| 40001| Output Registers| Registered Read & Write| 4, 6, 16
3.4. Communication settings
The data stored in the modules memory are in 16-bit registers. Access to
registers is via MODBUS RTU or MODBUS ASCII.
3.4.1. Default settings
Parameter name | Value |
---|---|
Address | 1 |
Baud rate | 19200 |
Parity | No |
Data bits | 8 |
Stop bits | 1 |
Reply Delay [ms] | 0 |
Modbus Type | RTU |
3.4.2. Configuration registers
Modbus | Dec | Hex | Name | Values |
---|
Address
40002| 1| 0x01| Address| From 0 to 255
40003| 2| 0x02| Baud rate| 0 – 2400
1 – 4800
2 – 9600
3 – 19200
4 – 38400
5 – 57600
6 – 115200
other – value * 10
40005| 4| 0x04| Parity| 0 – none
1 – odd
2 – even
3 – always 1
4 – always 0
40004| 3| 0x03| Stop Bits LSB| 1 – one stop bit
2 – two stop bits
40004| 3| 0x03| Data Bits MSB| 7 – 7 data bits
8 – 8 data bits
40006| 5| 0x05| Response delay| Time in ms
40007| 6| 0x06| Modbus Mode| 0 – RTU
1 – ASCII
Indicators
Indicator | Description |
---|---|
ON | LED indicates that the module is correctly powered. |
TX | The LED lights up when the unit received the correct packet and sends the |
answer.
AIV, AII| LED indicates that the signal to input is connected and is different
from 0
DO| LED indicates that the output is on.
Block diagram
Module Connection
Modules Registers
7.1. Registered access
Modbus| Dec| Hex| Register Name| Access|
Description
---|---|---|---|---|---
30001| 0| 0x00| Version/Type| Read| Version and Type of the device
30002| 1| 0x01| Address| Read| Module Address
40003| 2| 0x02| Baud rate| Read & Write| RS485 baud rate
40004| 3| 0x03| Stop Bits & Data Bits| Read & Write| No of Stop bits & Data
Bits (see 3.4.2)
40005| 4| 0x04| Parity| Read & Write| Parity bit
40006| 5| 0x05| Response Delay| Read & Write| Response delay in ms
40007| 6| 0x06| Modbus Mode| Read & Write| Modbus Mode (ASCII or RTU)
40010| 9| 0x09| Filter| Read & Write| Measurement filtering, value from 1 to
10
40033| 32| 0x20| Received packets LSB| Read & Write| No of received packets
40034| 33| 0x21| Received packets MSB| Read & Write
40035| 34| 0x22| Incorrect packets LSB| Read & Write| No of received packets
with error
40036| 35| 0x23| Incorrect packets MSB| Read & Write
40037| 36| 0x24| Sent packets LSB| Read & Write| No of sent packets
40038| 37| 0x25| Sent packets MSB| Read & Write
30051| 50| 0x32| Inputs| Read| Connected inputs
Bit in high state → signal is connected
40052| 51| 0x33| Outputs| Read & Write| Alarms state bit no. 3 digital output
30053| 52| 0x34| Voltage| Read| Voltage in μV
30054| 53| 0x35| Current| Read| Current in μA or ‰
30055| 54| 0x36| Alarm – max voltage| Read & Write| Maximum value of voltage
excess which causes set bit no 1 in the register 40052
30056| 55| 0x37| Alarm – min voltage| Read & Write| Minimum value of voltage.
If voltage drops below this voltage bit no 1 in the register 40052 is set.
30057| 56| 0x38| Alarm – max current| Read & Write| Maximum value of current
excess which causes set bit no 1 in the register 40052
30058| 57| 0x39| Alarm – min current| Read & Write| Minimum value of current.
If current drops below this voltage bit no 1 in the register 40052 is set.
30059| 58| 0x3A| Voltage alarm configuration| Read & Write| Alarms
configuration
0 – alarms state depends on actual values 1 – alarms state need to clear by master
30060| 59| 0x3B| Current alarm configuration| Read & Write
30061| 60| 0x3C| Voltage input configuration| Read & Write| 0 – OFF
1 – 0 .. 10V
2 – -10 .. 10V
3 – 0 .. 1V
4 – -1 .. 1V
40062| 61| 0x3D| Current input configuration| Read & Write| 0 – OFF
1 – 0 .. 20mA (in μA)
2 – 4 .. 20mA (in ‰)
3 – -20mA .. 20mA (in μA)
40063| 62| 0x3E| Digital output configuration| Read & Write| Digital output
configuration
0 – output controlled by master
1 – output state depends voltage
2 – output state depends current
+256 – output set if value is greater than alarm value (40065 register)
(„cooling”) +512 – output set if value is below than alarm value (40065
register) („warming”)
40064| 63| 0x3F| Alarm value| Read & Write| Alarm value
40065| 64| 0x40| Alarm hysteresis| Read & Write| Hysteresis for alarm
7.2. Bit access
Modbus Address| Dec Address| Hex Address| Register name|
Access| Description
---|---|---|---|---|---
801| 800| 0x320| Voltage input| Read| Voltage input state
802| 801| 0x321| Current input| Read| Current input state
817| 816| 0x330| Voltage alarm| Read & Write| Voltage alarm state
818| 817| 0x331| Current alarm| Read & Write| Current alarm state
819| 818| 0x332| Digital output| Read & Write| Digital output state
Configuration software
Modbus Configurator is software that is designed to set the module registers
responsible for communication over Modbus network as well as to read and write
the current value of other registers of the module. This program can be a
convenient way to test the system as well as to observe real-time changes in
the registers.
Communication with the module is done via the USB cable. The module does not
require any drivers.
Configurator is a universal program, whereby it is possible to configure all available modules.
Manufactured for: Aspar s.c.
ul. Oliwska 112
80-209 Chwaszczyno Poland
ampero@ampero.eu
www.ampero.eu
tel. +48 58 351 39 89; +48 58 732 71 73
Expansion Module – 1 analog input, 1 digital output
References