POTTER PAD100-ZM Zone Module Instruction Manual

June 9, 2024
POTTER

POTTER PAD100-ZM Zone Module Instruction

Installation Manual: PAD100-ZM Zone Module

NOTICE TO THE INSTALLER

This manual provides an overview and the installation instructions for the PAD100-ZM module. This module is only compatible with addressable fire systems that utilize the PAD Addressable Protocol. All terminals are power limited and should be wired in accordance with the requirements of NFPA 70 (NEC) and NFPA 72 (National Fire Alarm Code). Failure to follow the wiring diagrams in the following pages will cause the system to not operate as intended. For further information, refer to the control panel installation instructions. The module shall only be installed with listed control panels. Refer to the control panel installation manual for proper system operation.

Description

The PAD100-ZM uses one (1) SLC loop address when monitoring two (2) Class B or one (1) Class A circuit. The module is used to supervise a zone of conventional 2-wire smoke detectors on an Initiating Device Circuit (IDC). The module requires and supervises a 24VDC auxiliary power connection. The 24VDC power source must be either a Potter IPA series addressable panel, or a Potter PSN series power supply. The IDC may be wired as two individual Class B circuits or one Class A circuit which is selectable by an on board DIP switch. The module mounts on either an UL Listed 2-1/2″ deep 2-gang box or 1-1/2″ deep 4″ square box. The PAD100-ZM includes one red LED to indicate the module’s status. In normal condition, the LED flashes when the device is being polled by the control panel. When an input is activated, the LED will flash at a fast rate. If the LED blink has been disabled via the programming software, in a normal condition the LED of the device will be off. All other conditions remain the same.

Setting the Address

All PAD protocol detectors and modules require an address prior to connection to the panel’s SLC loop. Each PAD device’s address (i.e., detector and/or module) is set by changing the dip switches located on the device. PAD device addresses are comprised of a seven (7) position dip switch used to program each device with an address ranging from 1–127.POTTER-PAD100-ZM-Zone-Module-
Instruction-FIG-1

Note: Each “gray” box indicates that the dip switch is “On,” and each “white” box indicates “Off.”
The examples shown below illustrate a PAD device’s dip switch settings: the 1st example shows a device not addressed where all dip switch settings are in the default “Off” position, the 2nd illustrates an addressed PAD device via the dip switch settings.POTTER-PAD100-ZM-Zone-Module-Instruction-
FIG-2

When the PAD100-ZM is used to monitor two individual Class B circuits a single device address is assigned; each input is then identified as a sub-point of the module address. For example, if the address number is assigned as “8”, the “B1” input will be “8.1”, and the “B2” input will be “8.2.”
Before connecting a device to the SLC loop, take the following precautions to prevent potential damage to the SLC or device.

  • Power to the SLC is removed.
  • Field wiring on module is correctly installed.
  • Field wiring has no open or short circuits.

Technical Specifications

Operating Voltage 24.0V
Max SLC Standby Current 240 μ A
Max SLC Alarm Current 240 μ A
Aux Power Required 19 – 28V
Max Detector Standby Current of IDC at 24 VDC 1mA
Max Module Alarm Current of IDC at 24 VDC 50mA
Max Wiring Resistance of IDC 100 Ω
Max Wiring Capacitance of IDC 1μF
Smoke Detector Compatibility Identifier A
EOL Resistor 5.1K Ω
Operating Temperature Range 32̊ to 120̊ F (0̊ to 49̊ C)
Operating Humidity Range 0 to 93% (non-condensing)
Max no. of Module Per Loop 127 units
Dimensions 4.17″ L x 4.17″ W x 1.14″ D
Mounting Options UL Listed 2-1/2″ deep 2-gang box or 1-1/2″ deep 4″ square

box
Shipping Weight| 0.6 lbs

Wiring Diagrams

The wiring diagrams shown below illustrate how to wire a PAD100-ZM module as Class A and Class B. Additionally, an installation diagram shows how to install the module using a compatible electrical box.POTTER-PAD100-ZM-Zone-
Module-Instruction-FIG-4POTTER-PAD100-ZM-Zone-
Module-Instruction-FIG-5

Notes:

  • SLC wiring style supports the Class A, Class B and Class X.
  • DC wiring style supports Class A and Class B.
  • SLC loop wiring (SLC+, SLC-) and initiating device wiring (B1, B2 and A1) are power limited.
  • Wiring for terminals SLC+, SLC- are supervised.
  • Wiring for terminals (PWR) are supervised.
  • Wiring for terminals (B1, B2 and A1) are supervised.
  • All wiring is between #12 (max.) and #22 (min.).
  • Wire Preparation – Strip all wires 1/4 inch from their edges as shown here:
    • Stripping too much insulation may cause a ground fault.
    • Stripping too little may cause a poor connection and subsequently an open circuit.

These instructions do not purport to cover all the details or variations in the equipment described, nor provide for every possible contingency to be met in connection with installation, operation and maintenance. Specifications subject to change without prior notification. For Technical Assistance contact Potter Electric Signal Company at 866-956-1211. Actual performance is based on proper application of the product by a qualified professional. Should further information be desired or should particular problems arise, which are not covered sufficiently for the purchaser’s purpose, the matter should be referred to a distributor in your region.

Table 1: Compatible Conventional Smoke Detectors & Bases

Detector Model| Identifier| Base Model| Identifier
System Sensor (Brk) (Max. No. Of Detectors Per Zone is 10)
1400| A| N/A| N/A
2400| A| N/A| N/A
2400TH| A| N/A| N/A
2W-B| A| N/A| N/A
2WT-B| A| N/A| N/A
Detection System (Max. No. Of Detectors Per Zone is 11)
DS250| A| MB2W/MB2WL| A
DS250TH| A| MB2W/MB2WL| A
ESL (Max. No. Of Detectors Per Zone is 20)
611U| S10| 601U| S00
611UD| S10| 601U| S00
611UT| S10| 601U| S00
612U| S10| 601U| S00
612UD| S10| 601U| S00
613U5| S10| 601U| S00
611UD| S10| 609U10| S00
612UD| S10| 609U10| S00
425C| S10| N/A| N/A
425CT| S10| N/A| N/A
HOCHIKI (Max. No. Of Detectors Per Zone is 20)
SLR-24| HD-3| HSC-221R| HB-71
 |  | HSB-221| HB-54
 |  | HSB-221N| HB-54
 |  | NS6-221|
 |  | NS4-221|
 |  | NS6-220| HB-3
SLR-24H| HD-3| HSC-221R| HB-71
 |  | HSB-221| HB-54
 |  | HSB-221N| HB-54
 |  | NS6-221|
 |  | NS4-221|
SIJ-24| HD-3| HSC-221R| HB-71
 |  | HSB-221| HB-54
 |  | HSB-221N| HB-54
 |  | NS6-221|
 |  | NS4-221|
FENWAL (Max. No. Of Detectors Per Zone is 14)
CPD-7051| 151FE1| 2-WIRE| FE51A
PSD-7155| P55FE1| 2WRLT| FE52A
PSD-7156| P56FE1| 2WRB| FE55A
All of the above Fenwal detectors and bases can be used in any combination.

Retrofit Base Adaptor 70-501000-003, Identifier MAFE1 (for series 70-201000 Bases, Models -001,-002,-003 and -005). Duct Housing with Detector Base DN-51, Identifier DH22FE5 (for CPD-7051 and PSD-7155 detectors only).

POTTER (Max. No. Of Detectors Per Zone is 25)
PS-24| HD-3 (HOCHIKI)| SB-46| HB-71 (HOCHIKI)
 |  |  | HB-54 (HOCHIKI)
 |  | SB-93| HB-3 (HOCHIKI)
PS-24H| HD-3 (HOCHIKI)| SB-46| HB-71 (HOCHIKI)
 |  |  | HB-54 (HOCHIKI)
IS-24| HD-3 (HOCHIKI)| SB-46| HB-71 (HOCHIKI)
 |  |  | HB-54 (HOCHIKI)
NOTE: If using a mix of System Sensor and other smoke detectors, a maximum of 20 detectors shall be permitted.

Potter Electric Signal Company, LLC
St. Louis, MO
Phone: 800-325-3936
www.pottersignal.com
firealarmresources.com

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals