SKYWORKS Si5345-D-EVB Evaluation Board User Guide
- June 4, 2024
- SKYWORKS
Table of Contents
- SKYWORKS Si5345-D-EVB Evaluation Board
- Functional Block Diagram
- Quick Start
- Jumper Defaults
- Status LEDs
- External Reference Input (XA/XB)
- Clock Input Circuits (INx/INxB)
- Clock Output Circuits (OUTx/OUTxB)
- Installing ClockBuilder Pro Desktop Software
- Using the Si5345-D-EVB
- Writing a New Frequency Plan or Device Configuration to Non-Volatile
- Si5345-D-EVB Schematic, Layout, and Bill of Materials (BOM)
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
SKYWORKS Si5345-D-EVB Evaluation Board
Functional Block Diagram
Below is a functional block diagram of the Si5345-D-EB. This evaluation board can be connected to a PC via the main USB connector for programming, control, and monitoring. See section “3. Quick Start” or section “10.3. Overview of ClockBuilder Pro Applications” for more information.
Si5345-D-EVB Support Documentation and ClockBuilder Pro Software
All Si5345-D-EVB schematics, BOMs, User’s Guides, and software can be found
online at the following link: www.skyworksinc.com/support-
ia
Quick Start
- Install ClockBuilder Pro desktop software from www.skyworksinc.com/en/application-pages/clockbuilder-pro-software.
- Connect a USB cable from Si5345-D-EB to the PC where the software was installed.
- Confirm jumpers are installed as shown in Table 1.
- Launch the ClockBuilder Pro Software.
- You can use ClockBuilder Pro to create, download, and run a frequency plan on the Si5345-D-EB.
- For the Si5345 data sheet, go to www.skyworksinc.com/en/Products/Timing.
Jumper Defaults
**Table 1. Si5345-D-EB Jumper Defaults***
Location| Type| I = Installed 0 = Open| | Location|
Type| I = Installed 0 = Open
---|---|---|---|---|---|---
JP1| 2 pin| O| | JP23| 2 pin| O
JP2| 2 pin| I| | JP24| 2 pin| O
JP3| 2 pin| O| | JP25| 2 pin| O
JP4| 2 pin| I| | JP26| 2 pin| O
JP5| 2 pin| I| | JP27| 2 pin| O
JP6| 2 pin| I| | JP28| 2 pin| O
JP7| 2 pin| I| | JP29| 2 pin| O
JP8| 2 pin| O| | JP30| 2 pin| O
JP9| 2 pin| O| | JP31| 2 pin| O
JP10| 2 pin| I| | JP32| 2 pin| O
JP13| 2 pin| O| | JP33| 2 pin| O
JP14| 2 pin| I| | JP34| 2 pin| O
JP15| 3 pin| 1 to 2| | JP35| 2 pin| O
JP16| 3 pin| 1 to 2| | JP36| 2 pin| O
JP17| 2 pin| O| | JP38| 3 pin| All Open
JP18| 2 pin| O| | JP39| 2 pin| O
JP19| 2 pin| O| | JP40| 2 pin| O
JP20| 2 pin| O| | JP41| 2 pin| O
JP21| 2 pin| O| | J36| 5 x 2 Hdr| All 5 installed
JP22| 2 pin| O| | | |
*Note: Refer to the Si5345-D-EB schematics for the functionality
associated with each jumper.
Status LEDs
Table 2. Si5345-D-EB Status LEDs
Location | Silkscreen | Color | Status Function Indication |
---|---|---|---|
D27 | 5VUSBMAIN | Blue | Main USB +5 V present |
D22 | 3P3V | Blue | DUT +3.3 V is present |
D26 | VDD DUT | Blue | DUT VDD voltage present |
D25 | INTR | Red | MCU INTR (Interrupt) active |
D21 | READY | Green | MCU Ready |
D24 | BUSY | Green | MCU Busy |
D27, D22, and D26 are illuminated when USB +5 V, Si5345 +3.3 V, and Si5345 VDD supply voltages, respectively, are present. D25, D21, and D24 are status LEDs showing on-board MCU activity.
External Reference Input (XA/XB)
An external reference (XTAL) is used in combination with the internal oscillator to produce an ultra-low jitter reference clock for the DSPLL and for providing a stable reference for the free-run and holdover modes. The Si5345-D-EVB can also accommodate an external reference clock instead of a crystal. To evaluate the device with a REFCLK, C111 and C113 must be populated and the XTAL removed (see Figure 4 below). The REFCLK can then be supplied to J39 and J40.
Clock Input Circuits (INx/INxB)
The Si5345-D-EB has eight SMA connectors (IN0, IN0B–IN3, IN3B) for receiving external clock signals. All input clocks are terminated as shown in Figure 5 below. Note input clocks are ac-coupled and 50 terminated. This represents four differential input clock pairs. Single-ended clocks can be used by appropriately driving one side of the differential pair with a single-ended clock. For details on how to configure inputs as single-ended, please refer to the Si5345 data sheet.
Clock Output Circuits (OUTx/OUTxB)
Each of the twenty output drivers (10 differentia pairs) is ac-coupled to its respective SMA connector. The output clock termination circuit is shown in Figure 6 below. The output signal will have no dc bias. If dc coupling is required, the ac coupling capacitors can be replaced with a resistor of appropriate value. The Si5345-D-EVB provides pads for optional output termination resistors and/or low frequency capacitors. Note that components with schematic “NI” designation are not normally populated on the Si5345-D-EB and provide locations on the PCB for optional dc/ac terminations by the end user.
Installing ClockBuilder Pro Desktop Software
To install the CBOPro software on any Windows 7 (or above) PC:
Go to www.skyworksinc.com/en/application-pages/clockbuilder-pro-
software and download ClockBuilder Pro software.
Installation instructions and User’s Guide for ClockBuilder Pro can be found
at the download link shown above. Please follow the instructions as indicated.
Using the Si5345-D-EVB
Connecting the EVB to Your Host PC
Once ClockBuilder Pro software is installed, connect to the EVB with a USB
cable as shown below.
Additional Power Supplies
Although additional power (besides the power supplied by the host PC’s USB
port) is not needed for most configurations, two additional +5 VDC power
supplies (MAIN and AUX) can be connected to J33 and J34 (located on the bottom
of the board, near the USB connector). Refer to the Si5345-D-EB schematic for
details.
The Si5345-D-EB comes pre-configured with jumpers installed at JP15 and JP16
(pins 1-2 in both cases) in order to select “USB”. These jumpers, together
with the components installed, configure the evaluation board to obtain all+5
V power solely through the main USB connector at J37. This setup is the
default configuration and should normally be sufficient.
Figure 8 shows the correct installation of the jumper shunts at JP15 and JP16
for default or standard operation.
Errata Note:Some early versions of the 64-pin Si534x-EVBs may have the
silkscreen text at JP15-JP16 reversed regarding EXT and USB, i.e., USB EXT
instead of EXT USB. Regardless, the correct installation of the jumper shunts
for default or standard operation is on the right hand side as read and viewed
in Figure 8.
The general guidelines for single USB power supply operation are listed
below:
- Use either a USB 3.0 or USB 2.0 port. These ports are specified to supply 900 mA and 500 mA respectively at +5 V.
- If you are working with a USB 2.0 port and you are current limited, turn off enough DUT output voltage regulators to drop the total DUT current ≤ 470 mA. (Note: USB 2.0 ports may supply > 500 mA. Provided the nominal +5 V drops gracefully by less than 10%, the EVB will still work.)
- If you are working with a USB 2.0 and you are current limited and need all output clock drivers enabled, re-configure the EVB to drive the DUT output voltage regulators from an external +5 V power supply as follows:
- Connect external +5 V power supply to terminal block J33 on the back side of the PCB.
- Move the jumper at JP15 from pins 1-2 USB to pins 2-3 EXT.
Overview of ClockBuilder Pro Applications
Note: The following instructions and screen captures may vary slightly
depending on your version of ClockBuilder Pro. The ClockBuilder Pro installer
will install two main applications:
Use the CBPro Wizard to:
- Create a new design
- Review or edit an existing design
- Export: create in-system programming
Use the EVB GUI to:
- Download configuration to EVB’s DUT (Si5345)
- Control the EVB’s regulators
- Monitor voltage, current, power on the EVB
Common ClockBuilder Pro Work Flow Scenarios
There are three common workflow scenarios when using CBPro and the
Si5345-D-EVB. These workflow scenarios are:
- Workflow Scenario #1: Testing a Skyworks-Created Default Configuration
- Workflow Scenario #2: Modifying the Default Skyworks-Created Device Configuration
- Workflow Scenario #3: Testing a User-Created Device Configuration
Each is described in more detail in the following sections.
Workflow Scenario #1: Testing a Skyworks-Created Default Configuration
The flow for using the EVB GUI to initialize and control a device on the EVB
is as follows. Once the PC and EVB are connected, launch ClockBuilder Pro by
clicking on this icon on your PC’s desktop.
If an EVB is detected, click on the “Open Default Plan” button on the Wizard’s main menu. CBPro automatically detects the EVB and device type.
Once you open the default plan (based on your EVB model number), a popup will appear.
Select “Yes” to write the default plan to the Si5345 device mounted on your EVB. This ensures the device is completely reconfigured per the Skyworks default plan for the DUT type mounted on the EVB.
After CBPro writes the default plan to the EVB, click on “Open EVB GUI” as shown below.
The EVB GUI will appear. Note all power supplies will be set to the values defined in the device’s default CBPro project file created by Skyworks, as shown below.
Verify Free-Run Mode Operation
Assuming no external clocks have been connected to the INPUT CLOCK
differential SMA connectors (labeled “INx/INxB”) located around the perimeter
of the EVB, the DUT should now be operating in free-run mode, as the DUT will
be locked to the crystal in this case.
You can run a quick check to determine if the device is powered up and
generating output clocks (and consuming power) by clicking on the Read All
button highlighted above and then reviewing the voltage, current and power
readings for each VDDx supply.
Note: Shutting “Off” then “On” of the VDD and VDDA supplies will power-
down and reset the DUT. Every time you do this, to reload the Skyworks-created
default plan into the DUT’s register space, you must go back to the Wiz-ard’s
main menu and select “Write Design to EVB”:
Failure to do the step above will cause the device to read in a pre-programmed
plan from its non-volatile memory (NVM). However, the plan loaded from the NVM
may not be the latest plan recommended by Skyworks for evaluation.
At this point, you should verify the presence and frequencies of the output
clocks (running to free-run mode from the crystal) using appropriate external
instrumentation co nnected to the output clock SMA connectors. To verify the
output clocks are toggling at the correct frequency and signal format, click
on View Design Report as highlighted below.
Your configuration’s design report will appear in a new window, as shown below. Compare the observed output clocks to the frequencies and formats noted in your default project’s Design Report.
Verify Locked Mode Operation
Assuming you connect the correct input clocks to the EVB (as noted in the
Design Report shown above), the DUT on your EVB will be running in “locked”
mode.
Workflow Scenario #2: Modifying the Default Skyworks-Created Device
Configuration
To modify the “default” configuration using the CBPro Wizard, click on Edit Configuration with Wizard:
You will now be taken to the Wizard’s step-by-step menus to allow you to change any of the default plan’s operating configurations.
Note you can click on the icon on the lower left hand corner of the menu to confirm if your frequency plan is valid. After making your desired changes, you can click on Write to EVB to update the DUT to reconfigure your device real-time. The Design Write status window will appear each time you make a change.
Workflow Scenario #3: Testing a User-Created Device Configuration
To test a previously created user configuration, open the CBPro Wizard by clicking on the icon on your desktop and then selecting Open Design Project File
Locate your CBPro design file in the Windows file browser.
Select Yes when the WRITE DESIGN to EVB popup appears:
The progress bar will be launched. Once the new design project file has been written to the device, verify the presence and frequencies of your output clocks and other operating configurations using external instrumentation.
Exporting the Register Map File for Device Programming by a Host
Processor
You can also export your configuration to a file format suitable for in-system
programming by selecting Export as shown below:
You can now write your device’s complete configuration to file formats suitable for in-system programming.
Writing a New Frequency Plan or Device Configuration to Non-Volatile
Memory (OTP)
Note: Writing to the device non-volatile memory (OTP) is NOT the same as
writing a configuration into the Si5345 using ClockBuilder Pro on the
Si5345-D-EB. Writing a configuration into the EVB from ClockBuilder Pro is
done using Si5345 RAM space and can be done virtually unlimited numbers of
times. Writing to OTP is limited as described below.
Refer to the Si534x/8x Family Reference Manuals and device data sheets for
information on how to write a configuration to the EVB DUT’s non-volatile
memory (OTP). The OTP can be programmed a maximum of two times only. Care must
be taken to ensure the configuration desired is valid when choosing to write
to OTP.
Si5345-D-EVB Schematic, Layout, and Bill of Materials (BOM)
The Si5345-D-EVB Schematic, Layout, and Bill of Materials (BOM) can be found
online at: www.skyworksinc.com/support-ia
Note: Please be aware that the Si5345-D-EB schematic is in OrCad Capture
hierarchical format and not in a typical “flat” schematic format.
ClockBuilder Pro
Customize Skyworks clock generators, jitter attenuators and network
synchronizers with a single tool. With CBPro you can control evaluation
boards, access documentation, request a custom part number, export for
in-system programming and more!
www.skyworksinc.com/CBPro
Copyright © 2021 Skyworks Solutions, Inc. All Rights Reserved.
Information in this document is provided in connection with Skyworks
Solutions, Inc. (“Skyworks”) products or services. These materials, including
the information contained herein, are provided by Skyworks as a service to its
customers and may be used for informational purposes only by the customer.
Skyworks assumes no responsibility for errors or omissions in these materials
or the information contained herein. Skyworks may change its documentation,
products, services, specifications or product descriptions at any time, without
notice. Skyworks makes no commitment to update the materials or information
and shall have no responsibility whatsoever for conflicts, incompatibilities,
or other difficulties arising from any future changes.
No license, whether express, implied, by estoppel or otherwise, is granted to
any intellectual property rights by this document. Skyworks assumes no
liability for any materials, products or information provided hereunder,
including the sale, distribution, reproduction or use of Skyworks products,
information or materials, except as may be provided in Skyworks’ Terms and
Conditions of Sale.
THE MATERIALS, PRODUCTS AND INFORMATION ARE PROVIDED “AS IS” WITHOUT WARRANTY
OF ANY KIND, WHETHER EXPRESS, IMPLIED, STATUTORY, OR OTHERWISE, INCLUDING
FITNESS FOR A PARTICULAR PURPOSE OR USE, MERCHANTABILITY, PERFORMANCE, QUALITY
OR NON-INFRINGEMENT OF ANY INTELLECTUAL PROPERTY RIGHT; ALL SUCH WARRANTIES
ARE HEREBY EXPRESSLY DISCLAIMED. SKYWORKS DOES NOT WARRANT THE ACCURACY OR
COMPLETENESS OF THE INFORMATION, TEXT, GRAPHICS OR OTHER ITEMS CONTAINED
WITHIN THESE MATERIALS. SKYWORKS SHALL NOT BE LIABLE FOR ANY DAMAGES,
INCLUDING BUT NOT LIMITED TO ANY SPECIAL, INDIRECT, INCIDENTAL, STATUTORY, OR
CONSEQUENTIAL DAMAGES, INCLUDING WITHOUT LIMITATION, LOST REVENUES OR LOST
PROFITS THAT MAY RESULT FROM THE USE OF THE MATERIALS OR INFORMATION, WHETHER
OR NOT THE RECIPIENT OF MATERIALS HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH
DAMAGE.
Skyworks products are not intended for use in medical, lifesaving or life-
sustaining applications, or other equipment in which the failure of the
Skyworks products could lead to personal injury, death, physical or
environmental damage. Skyworks customers using or selling Skyworks products
for use in such applications do so at their own risk and agree to fully
indemnify Skyworks for any damages resulting from such improper use or sale.
Customers are responsible for their products and applications using Skyworks
products, which may deviate from published specifications as a result of design
defects, errors, or operation of products outside of published parameters or
design specifications. Customers should include design and operating safeguards
to minimize these and other risks. Skyworks assumes no liability for
applications assistance, customer product design, or damage to any equipment
resulting from the use of Skyworks products outside of Skyworks’ published
specifications or parameters.
Skyworks, the Skyworks symbol, Sky5®, SkyOne®, SkyBlue™, Skyworks Green™,
Clockbuilder®, DSPLL®, ISOmodem®, ProSLIC®, and SiPHY® are trademarks or
registered trademarks of Skyworks Solutions, Inc. or its subsidiaries in the
United States and other countries. Third-party brands and names are for
identification purposes only and are the property of their respective owners.
Additional information, including relevant terms and conditions, posted at
www.skyworksinc.com, are incorporated by reference.
Skyworks Solutions, Inc. | Nasdaq: SWKS
sales@skyworksinc.com
www.skyworksinc.com
USA: 781-376-3000
Asia: 886-2-2735 0399
Europe: 33 (0)1 43548540 |