SKYWORKS Si5345-D-EVB Evaluation Board User Guide

June 4, 2024
SKYWORKS

SKYWORKS Si5345-D-EVB Evaluation Board

SKYWORKS-Si5345-D-EVB-Evaluation-Board

Functional Block Diagram

Below is a functional block diagram of the Si5345-D-EB. This evaluation board can be connected to a PC via the main USB connector for programming, control, and monitoring. See section “3. Quick Start” or section “10.3. Overview of ClockBuilder Pro Applications” for more information.SKYWORKS-Si5345-D-EVB-
Evaluation-Board-1

Si5345-D-EVB Support Documentation and ClockBuilder Pro Software
All Si5345-D-EVB schematics, BOMs, User’s Guides, and software can be found online at the following link: www.skyworksinc.com/support- ia

Quick Start

  1. Install ClockBuilder Pro desktop software from www.skyworksinc.com/en/application-pages/clockbuilder-pro-software.
  2. Connect a USB cable from Si5345-D-EB to the PC where the software was installed.
  3. Confirm jumpers are installed as shown in Table 1.
  4. Launch the ClockBuilder Pro Software.
  5. You can use ClockBuilder Pro to create, download, and run a frequency plan on the Si5345-D-EB.
  6. For the Si5345 data sheet, go to www.skyworksinc.com/en/Products/Timing.

Jumper Defaults

**Table 1. Si5345-D-EB Jumper Defaults***

Location| Type| I = Installed 0 = Open|  | Location| Type| I = Installed 0 = Open
---|---|---|---|---|---|---
JP1| 2 pin| O|  | JP23| 2 pin| O
JP2| 2 pin| I|  | JP24| 2 pin| O
JP3| 2 pin| O|  | JP25| 2 pin| O
JP4| 2 pin| I|  | JP26| 2 pin| O
JP5| 2 pin| I|  | JP27| 2 pin| O
JP6| 2 pin| I|  | JP28| 2 pin| O
JP7| 2 pin| I|  | JP29| 2 pin| O
JP8| 2 pin| O|  | JP30| 2 pin| O
JP9| 2 pin| O|  | JP31| 2 pin| O
JP10| 2 pin| I|  | JP32| 2 pin| O
JP13| 2 pin| O|  | JP33| 2 pin| O
JP14| 2 pin| I|  | JP34| 2 pin| O
JP15| 3 pin| 1 to 2|  | JP35| 2 pin| O
JP16| 3 pin| 1 to 2|  | JP36| 2 pin| O
JP17| 2 pin| O|  | JP38| 3 pin| All Open
JP18| 2 pin| O|  | JP39| 2 pin| O
JP19| 2 pin| O|  | JP40| 2 pin| O
JP20| 2 pin| O|  | JP41| 2 pin| O
JP21| 2 pin| O|  | J36| 5 x 2 Hdr| All 5 installed
JP22| 2 pin| O|  |  |  |
*Note: Refer to the Si5345-D-EB schematics for the functionality associated with each jumper.

Status LEDs

Table 2. Si5345-D-EB Status LEDs

Location Silkscreen Color Status Function Indication
D27 5VUSBMAIN Blue Main USB +5 V present
D22 3P3V Blue DUT +3.3 V is present
D26 VDD DUT Blue DUT VDD voltage present
D25 INTR Red MCU INTR (Interrupt) active
D21 READY Green MCU Ready
D24 BUSY Green MCU Busy

D27, D22, and D26 are illuminated when USB +5 V, Si5345 +3.3 V, and Si5345 VDD supply voltages, respectively, are present. D25, D21, and D24 are status LEDs showing on-board MCU activity.

External Reference Input (XA/XB)

An external reference (XTAL) is used in combination with the internal oscillator to produce an ultra-low jitter reference clock for the DSPLL and for providing a stable reference for the free-run and holdover modes. The Si5345-D-EVB can also accommodate an external reference clock instead of a crystal. To evaluate the device with a REFCLK, C111 and C113 must be populated and the XTAL removed (see Figure 4 below). The REFCLK can then be supplied to J39 and J40.SKYWORKS-Si5345-D-EVB-Evaluation-Board-4

Clock Input Circuits (INx/INxB)

The Si5345-D-EB has eight SMA connectors (IN0, IN0B–IN3, IN3B) for receiving external clock signals. All input clocks are terminated as shown in Figure 5 below. Note input clocks are ac-coupled and 50  terminated. This represents four differential input clock pairs. Single-ended clocks can be used by appropriately driving one side of the differential pair with a single-ended clock. For details on how to configure inputs as single-ended, please refer to the Si5345 data sheet.SKYWORKS-Si5345-D-EVB-Evaluation-
Board-5

Clock Output Circuits (OUTx/OUTxB)

Each of the twenty output drivers (10 differentia pairs) is ac-coupled to its respective SMA connector. The output clock termination circuit is shown in Figure 6 below. The output signal will have no dc bias. If dc coupling is required, the ac coupling capacitors can be replaced with a resistor of appropriate value. The Si5345-D-EVB provides pads for optional output termination resistors and/or low frequency capacitors. Note that components with schematic “NI” designation are not normally populated on the Si5345-D-EB and provide locations on the PCB for optional dc/ac terminations by the end user.SKYWORKS-Si5345-D-EVB-Evaluation-Board-6

Installing ClockBuilder Pro Desktop Software

To install the CBOPro software on any Windows 7 (or above) PC:
Go to www.skyworksinc.com/en/application-pages/clockbuilder-pro- software and download ClockBuilder Pro software.
Installation instructions and User’s Guide for ClockBuilder Pro can be found at the download link shown above. Please follow the instructions as indicated.

Using the Si5345-D-EVB

Connecting the EVB to Your Host PC
Once ClockBuilder Pro software is installed, connect to the EVB with a USB cable as shown below.

Additional Power Supplies
Although additional power (besides the power supplied by the host PC’s USB port) is not needed for most configurations, two additional +5 VDC power supplies (MAIN and AUX) can be connected to J33 and J34 (located on the bottom of the board, near the USB connector). Refer to the Si5345-D-EB schematic for details.
The Si5345-D-EB comes pre-configured with jumpers installed at JP15 and JP16 (pins 1-2 in both cases) in order to select “USB”. These jumpers, together with the components installed, configure the evaluation board to obtain all+5 V power solely through the main USB connector at J37. This setup is the default configuration and should normally be sufficient.
Figure 8 shows the correct installation of the jumper shunts at JP15 and JP16 for default or standard operation.SKYWORKS-Si5345-D-EVB-Evaluation-
Board-8

Errata Note:Some early versions of the 64-pin Si534x-EVBs may have the silkscreen text at JP15-JP16 reversed regarding EXT and USB, i.e., USB EXT instead of EXT USB. Regardless, the correct installation of the jumper shunts for default or standard operation is on the right hand side as read and viewed in Figure 8.
The general guidelines for single USB power supply operation are listed below:

  • Use either a USB 3.0 or USB 2.0 port. These ports are specified to supply 900 mA and 500 mA respectively at +5 V.
  • If you are working with a USB 2.0 port and you are current limited, turn off enough DUT output voltage regulators to drop the total DUT current ≤ 470 mA. (Note: USB 2.0 ports may supply > 500 mA. Provided the nominal +5 V drops gracefully by less than 10%, the EVB will still work.)
  • If you are working with a USB 2.0 and you are current limited and need all output clock drivers enabled, re-configure the EVB to drive the DUT output voltage regulators from an external +5 V power supply as follows:
    • Connect external +5 V power supply to terminal block J33 on the back side of the PCB.
    • Move the jumper at JP15 from pins 1-2 USB to pins 2-3 EXT.

Overview of ClockBuilder Pro Applications
Note: The following instructions and screen captures may vary slightly depending on your version of ClockBuilder Pro. The ClockBuilder Pro installer will install two main applications:SKYWORKS-Si5345-D-EVB-Evaluation-
Board-23

Use the CBPro Wizard to:

  • Create a new design
  • Review or edit an existing design
  • Export: create in-system programming SKYWORKS-Si5345-D-EVB-Evaluation-Board-10

Use the EVB GUI to:

  • Download configuration to EVB’s DUT (Si5345)
  • Control the EVB’s regulators
  • Monitor voltage, current, power on the EVB

Common ClockBuilder Pro Work Flow Scenarios
There are three common workflow scenarios when using CBPro and the Si5345-D-EVB. These workflow scenarios are:

  • Workflow Scenario #1: Testing a Skyworks-Created Default Configuration
  • Workflow Scenario #2: Modifying the Default Skyworks-Created Device Configuration
  • Workflow Scenario #3: Testing a User-Created Device Configuration
    Each is described in more detail in the following sections.

Workflow Scenario #1: Testing a Skyworks-Created Default Configuration
The flow for using the EVB GUI to initialize and control a device on the EVB is as follows. Once the PC and EVB are connected, launch ClockBuilder Pro by clicking on this icon on your PC’s desktop.SKYWORKS-Si5345-D-EVB-Evaluation-
Board-11

If an EVB is detected, click on the “Open Default Plan” button on the Wizard’s main menu. CBPro automatically detects the EVB and device type.SKYWORKS-
Si5345-D-EVB-Evaluation-Board-12

Once you open the default plan (based on your EVB model number), a popup will appear.SKYWORKS-Si5345-D-EVB-Evaluation-Board-13

Select “Yes” to write the default plan to the Si5345 device mounted on your EVB. This ensures the device is completely reconfigured per the Skyworks default plan for the DUT type mounted on the EVB.SKYWORKS-Si5345-D-EVB-
Evaluation-Board-14

After CBPro writes the default plan to the EVB, click on “Open EVB GUI” as shown below.SKYWORKS-Si5345-D-EVB-Evaluation-Board-15

The EVB GUI will appear. Note all power supplies will be set to the values defined in the device’s default CBPro project file created by Skyworks, as shown below.SKYWORKS-Si5345-D-EVB-Evaluation-Board-16

Verify Free-Run Mode Operation
Assuming no external clocks have been connected to the INPUT CLOCK differential SMA connectors (labeled “INx/INxB”) located around the perimeter of the EVB, the DUT should now be operating in free-run mode, as the DUT will be locked to the crystal in this case.
You can run a quick check to determine if the device is powered up and generating output clocks (and consuming power) by clicking on the Read All button highlighted above and then reviewing the voltage, current and power readings for each VDDx supply.
Note: Shutting “Off” then “On” of the VDD and VDDA supplies will power- down and reset the DUT. Every time you do this, to reload the Skyworks-created default plan into the DUT’s register space, you must go back to the Wiz-ard’s main menu and select “Write Design to EVB”:SKYWORKS-Si5345-D-EVB-Evaluation-
Board-17

Failure to do the step above will cause the device to read in a pre-programmed plan from its non-volatile memory (NVM). However, the plan loaded from the NVM may not be the latest plan recommended by Skyworks for evaluation.
At this point, you should verify the presence and frequencies of the output clocks (running to free-run mode from the crystal) using appropriate external instrumentation co nnected to the output clock SMA connectors. To verify the output clocks are toggling at the correct frequency and signal format, click on View Design Report as highlighted below.SKYWORKS-Si5345-D-EVB-Evaluation-
Board-18

Your configuration’s design report will appear in a new window, as shown below. Compare the observed output clocks to the frequencies and formats noted in your default project’s Design Report.SKYWORKS-Si5345-D-EVB-Evaluation-
Board-19

Verify Locked Mode Operation
Assuming you connect the correct input clocks to the EVB (as noted in the Design Report shown above), the DUT on your EVB will be running in “locked” mode.

Workflow Scenario #2: Modifying the Default Skyworks-Created Device

Configuration

To modify the “default” configuration using the CBPro Wizard, click on Edit Configuration with Wizard:SKYWORKS-Si5345-D-EVB-Evaluation-
Board-20

You will now be taken to the Wizard’s step-by-step menus to allow you to change any of the default plan’s operating configurations.SKYWORKS-Si5345-D
-EVB-Evaluation-Board-21

Note you can click on the icon on the lower left hand corner of the menu to confirm if your frequency plan is valid. After making your desired changes, you can click on Write to EVB to update the DUT to reconfigure your device real-time. The Design Write status window will appear each time you make a change.SKYWORKS-Si5345-D-EVB-Evaluation-Board-22

Workflow Scenario #3: Testing a User-Created Device Configuration

To test a previously created user configuration, open the CBPro Wizard by clicking on the icon on your desktop and then selecting Open Design Project FileSKYWORKS-Si5345-D-EVB-Evaluation-Board-23

Locate your CBPro design file in the Windows file browser.SKYWORKS-Si5345-D
-EVB-Evaluation-Board-24

Select Yes when the WRITE DESIGN to EVB popup appears:

The progress bar will be launched. Once the new design project file has been written to the device, verify the presence and frequencies of your output clocks and other operating configurations using external instrumentation.

Exporting the Register Map File for Device Programming by a Host Processor
You can also export your configuration to a file format suitable for in-system programming by selecting Export as shown below:SKYWORKS-Si5345-D-EVB-
Evaluation-Board-26

You can now write your device’s complete configuration to file formats suitable for in-system programming.SKYWORKS-Si5345-D-EVB-Evaluation-
Board-27

Writing a New Frequency Plan or Device Configuration to Non-Volatile

Memory (OTP)

Note: Writing to the device non-volatile memory (OTP) is NOT the same as writing a configuration into the Si5345 using ClockBuilder Pro on the Si5345-D-EB. Writing a configuration into the EVB from ClockBuilder Pro is done using Si5345 RAM space and can be done virtually unlimited numbers of times. Writing to OTP is limited as described below.
Refer to the Si534x/8x Family Reference Manuals and device data sheets for information on how to write a configuration to the EVB DUT’s non-volatile memory (OTP). The OTP can be programmed a maximum of two times only. Care must be taken to ensure the configuration desired is valid when choosing to write to OTP.

Si5345-D-EVB Schematic, Layout, and Bill of Materials (BOM)

The Si5345-D-EVB Schematic, Layout, and Bill of Materials (BOM) can be found online at: www.skyworksinc.com/support-ia
Note: Please be aware that the Si5345-D-EB schematic is in OrCad Capture hierarchical format and not in a typical “flat” schematic format.

ClockBuilder Pro
Customize Skyworks clock generators, jitter attenuators and network synchronizers with a single tool. With CBPro you can control evaluation boards, access documentation, request a custom part number, export for
in-system programming and more! www.skyworksinc.com/CBProSKYWORKS-
Si5345-D-EVB-Evaluation-Board-28

Copyright © 2021 Skyworks Solutions, Inc. All Rights Reserved.
Information in this document is provided in connection with Skyworks Solutions, Inc. (“Skyworks”) products or services. These materials, including the information contained herein, are provided by Skyworks as a service to its customers and may be used for informational purposes only by the customer. Skyworks assumes no responsibility for errors or omissions in these materials or the information contained herein. Skyworks may change its documentation, products, services, specifications or product descriptions at any time, without notice. Skyworks makes no commitment to update the materials or information and shall have no responsibility whatsoever for conflicts, incompatibilities, or other difficulties arising from any future changes.
No license, whether express, implied, by estoppel or otherwise, is granted to any intellectual property rights by this document. Skyworks assumes no liability for any materials, products or information provided hereunder, including the sale, distribution, reproduction or use of Skyworks products, information or materials, except as may be provided in Skyworks’ Terms and Conditions of Sale.
THE MATERIALS, PRODUCTS AND INFORMATION ARE PROVIDED “AS IS” WITHOUT WARRANTY OF ANY KIND, WHETHER EXPRESS, IMPLIED, STATUTORY, OR OTHERWISE, INCLUDING FITNESS FOR A PARTICULAR PURPOSE OR USE, MERCHANTABILITY, PERFORMANCE, QUALITY OR NON-INFRINGEMENT OF ANY INTELLECTUAL PROPERTY RIGHT; ALL SUCH WARRANTIES ARE HEREBY EXPRESSLY DISCLAIMED. SKYWORKS DOES NOT WARRANT THE ACCURACY OR COMPLETENESS OF THE INFORMATION, TEXT, GRAPHICS OR OTHER ITEMS CONTAINED WITHIN THESE MATERIALS. SKYWORKS SHALL NOT BE LIABLE FOR ANY DAMAGES, INCLUDING BUT NOT LIMITED TO ANY SPECIAL, INDIRECT, INCIDENTAL, STATUTORY, OR CONSEQUENTIAL DAMAGES, INCLUDING WITHOUT LIMITATION, LOST REVENUES OR LOST PROFITS THAT MAY RESULT FROM THE USE OF THE MATERIALS OR INFORMATION, WHETHER OR NOT THE RECIPIENT OF MATERIALS HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGE.
Skyworks products are not intended for use in medical, lifesaving or life- sustaining applications, or other equipment in which the failure of the Skyworks products could lead to personal injury, death, physical or environmental damage. Skyworks customers using or selling Skyworks products for use in such applications do so at their own risk and agree to fully indemnify Skyworks for any damages resulting from such improper use or sale.
Customers are responsible for their products and applications using Skyworks products, which may deviate from published specifications as a result of design defects, errors, or operation of products outside of published parameters or design specifications. Customers should include design and operating safeguards to minimize these and other risks. Skyworks assumes no liability for applications assistance, customer product design, or damage to any equipment resulting from the use of Skyworks products outside of Skyworks’ published specifications or parameters.
Skyworks, the Skyworks symbol, Sky5®, SkyOne®, SkyBlue™, Skyworks Green™, Clockbuilder®, DSPLL®, ISOmodem®, ProSLIC®, and SiPHY® are trademarks or registered trademarks of Skyworks Solutions, Inc. or its subsidiaries in the United States and other countries. Third-party brands and names are for identification purposes only and are the property of their respective owners. Additional information, including relevant terms and conditions, posted at www.skyworksinc.com, are incorporated by reference.
Skyworks Solutions, Inc. | Nasdaq: SWKS
[email protected]
www.skyworksinc.com
USA: 781-376-3000
Asia: 886-2-2735 0399
Europe: 33 (0)1 43548540 |

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

SKYWORKS User Manuals

Related Manuals