PYLON TECH Kodak and Pylontech User Guide
- June 9, 2024
- PYLON TECH
Table of Contents
PYLON TECH Kodak and Pylontech
WIRING EXAMPLE
BMS Communication Setup
Dipswitch Settings:
BMS Communication pinouts:
Settings
Settings– Newer versions
- Enter programming mode
- Set 05 : Select PYL for Pylontech Batteries
- If there is parallel inverters, please select ‘USE’ on slave inverters
- Select suitable frequency in the 9th setting-set to 50Hz.
- If you apply ‘SBU’ mode, except for the first steps, the 11th setting, the maximum charge current from grid should be set according to battery numbers.
- The 12th setting, discharge voltage limit is recommended to not be set below 46V.
- The 13th setting, charge voltage limit recommended to be set at 53V.
- Enter programming mode
- Set 05 : Select PYL for Pylontech Batteries
- If there is parallel inverters, please select ‘USE’ on slave inverters
- Select suitable frequency in the 9th setting-set to 50Hz.
- If you apply ‘SBU’ mode, except for the first steps, the 11th setting, the maximum charge current from grid should be set according to battery numbers.
- The 12th setting, discharge voltage limit is recommended to not be set below 46V.
- The 13th setting, charge voltage limit recommended to be set at 53V.
Troubleshooting – Most common communication error
“Error 61 – BMS communication failed”
POSSIBLE CAUSES:
- Incorrect/damaged BMS cable used – cable tester
- Incorrect DIP switches set on battery – Consult documentation on product page
- Incorrect battery type selected – Program 05
- Incorrect port used on battery/inverter – User manual on product page
NOTE:
- OG range only uses RS485 with a Baud rate of 9600
- BMS cable included with battery/inverter or bought from SegenSolar – Ask your account manager or technical support advisor for assistance