Breaburn 4235 Premier Series Programmable Thermostats User Manual
- June 9, 2024
- Breaburn
Table of Contents
Breaburn 4235 Premier Series Programmable Thermostats User Manual
Warning
For installation by experienced service technicians only.
Caution
Possible electric shock or damage to equipment can occur. Disconnect power
before beginning installation.
This thermostat requires 24 Volt AC Power or 2 properly installed “AA” Alkaline batteries for proper operation. When connecting 24 Volt AC Power, the batteries may be installed as a backup.
For use only as described in this manual. Any other use will void warranty.
This manual is for Installer use only – do not leave with end user.
SPECIFICATIONS
This thermostat is compatible with:
- Single stage conventional and heat pump systems
- Single stage heat pumps with auxiliary heat
- Heat pump systems with 2 compressors and auxiliary heat (4235 only)
- Conventional systems up to 2 stages of heat and 2 stages of cool (4235 only)
- 250 – 750 millivolt heating only systems
- 2 or 3 wire hydronic zone systems
Electrical and Control Specifications
- Electrical Rating: 24 Volt AC
- 1 amp maximum load per terminal
- AC Power: 18 – 30 Volts AC
- DC Power: 3.0 Volt DC (2 “AA” Alkaline Batteries Included)
- Control Range: 45° to 90° F (7° to 32° C)
- Temperature Accuracy: +/- 1° F (+/- .5° C)
- Outdoor Temperature Display Range:
- 40° to 120° F (-40° to 49° C)
- DRY1, DRY2 Terminals: Dry Contact Relay
Humidity Control Specifications
- Humidification Control Range: 10% – 50% RH
- Dehumidification Control Range: 40% – 80% RH
Terminations
4030:
Rc, Rh, W1/E, Y1, G, O/B/V3, L, C, S1, S2, DRY1, DRY2
4235:
Rc, Rh, W1/E, W2/AUX, Y1, Y2, G, O/B/V3, L, C, S1, S2, DRY1, DRY2
INSTALLATION
Warning Disconnect power before beginning installation
Thermostat Location
Install the thermostat approximately 5 feet (1.5m) above the floor in an area that has a good amount of air circulation and maintains an average room temperature.
Avoid installation in locations where the thermostat can be affected by
drafts, dead air spots, hot or cold air ducts, sunlight, appliances, concealed
pipes, chimneys and outside walls.
Install the Sub-Base:
- Remove the sub-base from the body of the thermostat.
- Mount the sub-base as shown below:
Drill 3/16” pilot holes in your desired location. Use supplied anchors for drywall or plaster.
Provide Power
24VAC Power Terminal (C)
Batteries Installed as Shown
- Battery Power – Insert the 2 supplied “AA” type alkaline batteries into the battery compartment located in the rear housing of the thermostat. Make sure to position the Positive (+) andNegative (-) sides of the batteries correctly with the +/- symbols in the battery compartment.
- Optional 24 Volt AC power – Connect the common side of the transformer to the C terminal on the thermostat sub-base. In dual transformer installations, the transformer common must come from the cooling transformer.
Attach to Thermostat Sub-Base
NOTE: This thermostat ships configured as a 1 Heat / 1 Cool conventional (CONV 11) thermostat.
Once you complete the wiring in Section 3, attach thermostat to sub-base and then configure the Installer Settings in Section 5.
- Line up the thermostat body with the sub-base.
- Carefully push the thermostat body against the sub-base until it snaps in place.
WIRING
Conventional Systems – Typical Wiring Configurations| 4030
/ 4235| 4235|
---|---|---|---
Heat Only or Millivolt System Type: CONV 11| Hydronic Heat Only
System Type: HD 1| Hydronic Heat/Cool System Type: HD 11|
1 Heat/ 1 Cool System Type: CONV 11| 2 Heat/ 2 Cool
System Type: CONV 22|
Wiring Terminal| Terminal Description|
Rh| 24 VAC Heating Transformer| Rh| Rh| Rh 1| Rh 1| Rh 1|
Rc| 24 VAC Cooling Transformer| –| –| Rc 1,2| Rc 1,2| Rc
1,2|
W1/E| (W1) Conventional Heat Relay(E) Emergency Heat Relay| W1| W1| W1|
W1| W1|
W2/AUX | (W2) 2nd Stage Conventional Heat (AUX) Heat Pump Auxiliary
Heat| –| –| –| –| W2|
Y1| 1st Stage Compressor Relay| –| –| Y1| Y1| Y1|
Y2| 2nd Stage Compressor Relay| –| –| –| –| Y2 3|
G| Fan Relay| G 3| G 3| G| G| G|
O/B/V3| (O) Cool Active Reversing Valve(B) Heat Active Reversing Valve
(V3) Zone Valve Power Close| –| V3 3| V3 3| –| –|
L| System Malfunction Indicator| –| –| –| –| –|
C| 24 VAC Transformer Common| C 4| C 4| C 4,5| C 4,5|
C 4,5|
*4235 Only. “System Type” is configured in the Installer Settings – See section 5.
NOTES – Conventional Systems
- Remove factory installed jumper wire for dual transformer systems
- Only required for dual transformer systems
- Only connect if needed for system
- Optional 24 VAC transformer common connection
- For dual transformer systems, common must come from cooling transformer
Provide disconnect and overload protection as required
Additional Wiring Options
Wiring Terminal | Terminal Description | Notes |
---|---|---|
S1 | __ Remote Sensor (Indoor or Outdoor) | These terminals can be |
used to connect a Braeburn® indooror outdoor remote sensor. For indoor remote
sensor configuration, refer to installer setting 23 in section 5. No
configuration is required for an outdoor sensor.
S2
__**H/D*| (H) Humidification Relay(D) Dehumidification Relay| This
terminal can be used to control an external humidifier or dehumidifier relay.
Overcooling is also available.For configuration, refer to Installer Settings
25-29 in section 5.
DRY1| Dry Contact Relay (no voltage)| These terminals can be used to
connect a condensate overflow monitor, door switch, spring timer or occupancy
sensor. For dry contact configuration, refer to Installer Settings 30-32 in
section 5.
DRY2**
*4235 Only.
NOTE: Use 18-22 gauge unshielded wire with a 200-foot maximum wire length. Avoid running wire along with 120 VAC wiring or near magnetic ballasts.
Heat Pump Systems – Typical Wiring Configurations| 4030 /
4235| 4235
---|---|---
1 Heat/1 Cool| 2 Heat/1 Cool (w/Aux Heat) System Type: HP
21| 2 Heat/2 Cool (No Aux Heat) System Type: HP 32| 3 Heat/2
Cool (w/Aux Heat) System Type: HP 32
Wiring Terminal| Terminal Description| Syste HP| m
Type: 11
Rh| 24 VAC Heating Transformer| Rh 1| Rh 1| Rh 1| Rh
1
Rc| 24 VAC Cooling Transformer| –| –| –| –
W1/E| (W1) Conventional Heat Relay(E) Emergency Heat Relay| –| E 2|
–| E 2
W2/AUX | (W2) 2nd Stage Conventional Heat (AUX) Heat Pump Auxiliary
Heat| –| AUX 2| –| AUX 2
Y1| 1st Stage Compressor Relay| Y1| Y1| Y1| Y1
Y2| 2nd Stage Compressor Relay| –| –| Y2| Y2
G| Fan Relay| G| G| G| G
O/B/V3| (O) Cool Active Reversing Valve(B) Heat Active Reversing Valve
(V3) Zone Valve Power Close| O/B 3| O/B 3| O/B 3| O/B 3
L| System Malfunction Indicator| L 4| L 4| L 4| L 4
C| 24 VAC Transformer Common| C 5| C 5| C 5| C 5
*4235 Only. “System Type” is configured in the Installer Settings – See section 5.
NOTES – Heat Pump Systems
- Do not remove factory installed jumper wire
- If no separate emergency heat relay, connect to AUX and Install a field supplied jumper wire from AUX to E
- O (cool active) or B (heat active) is selected in the Installer Settings – See section 5
- If using optional L terminal, the 24 VAC common must be connected (C terminal)
- Optional 24 VAC transformer common connection
Provide disconnect and overload protection as required
Additional Wiring Options
Wiring Terminal | Terminal Description | Notes |
---|---|---|
S1 | __ Remote Sensor (Indoor or Outdoor) | These terminals can be |
used to connect a Braeburn® indooror outdoor remote sensor. For indoor remote
sensor configuration, refer to installer setting 23 in section 5. No
configuration is required for an outdoor sensor.
S2
__**H/D*| (H) Humidification Relay(D) Dehumidification Relay| This
terminal can be used to control an external humidifier or dehumidifier relay.
Overcooling is also available.For configuration, refer to Installer Settings
25-29 in section 5.
DRY1| Dry Contact Relay (no voltage)| These terminals can be used to
connect a condensate overflow monitor, door switch, spring timer or occupancy
sensor. For dry contact configuration, refer to Installer Settings 30-32 in
section 5.
DRY2**
*4235 Only.
NOTE: Use 18-22 gauge unshielded wire with a 200-foot maximum wire length. Avoid running wire along with 120 VAC wiring or near magnetic ballasts.
QUICK REFERENCE
Thermostat
-
SYSTEM Button …………………Selects the system you want to control
-
PROG Button……………………..Enters programming mode or hold for 3 seconds to enter SpeedSet® mode
BACK Button*……………………Secondary function of the PROG button – Moves to previous setting -
HOLD Button……………………..Enters / Exits the HOLD mode (program bypass mode)
**NEXT Button* ……………………Secondary function of the HOLD button – Moves to next setting
FAN Button** ……………………….Selects the system fan mode -
RETURN Button*………………..Secondary function of the FAN button – Exits program or setting modes
-
Up / DownArrow Buttons…..Increases or decreases settings (time, temperature, etc.)
-
MENU Button…………………….Used to access thermostat User / Installer setting modes
-
Lock / Unlock Thermostat…. Access user Lock / Unlock screen by holding PROG and HOLD together for 5 seconds
Battery Compartment………..Located on the back side of thermostat (if installed)
- BACK, NEXT and RETURN are secondary functions of the PROG, HOLD and FAN buttons When in programming or configuration modes, BACK, NEXT and RETURN appear in the display screen indicating that the PROG, HOLD and FAN buttons now function as BACK, NEXT and RETURN
Thermostat Display
- Room Temperature ………………………..Displays the current room temperature
- Set Temperature ……………………………Displays the current setpoint temperature
- Outdoor Temperature …………………….If a Braeburn® outdoor sensor was connected the outdoor temperature will be displayed
- Room Humidity (4235 only) ……………. Displays the current room Relative Humidity level
- Humidity Call Indicator (4235 only) ….Indicates when there is a call for Humidification or Dehumidification (in enabled)
- Override Indicator ………………………… Indicates that the current program schedule has been temporarily overridden
- Time of Day …………………………………. Displays the current time of day
- Message Center …………………………… Displays various thermostat status and maintenance information
- System Mode ………………………………..Displays the system mode and current system status
- Fan Mode Indicator ……………………….Indicates the current system fan mode
- Fan Status Indicator …………………….. Indicates that the system fan is running
- Lock Mode Indicator …………………….. Indicates if the thermostat is locked
- Low Battery Indicator …………………… Indicates when the batteries need to be replaced
INSTALLER SETTINGS
The Installer Settings must be properly configured in order for this thermostat to operate correctly. The Installer Settings are menu driven. The portion of these settings that do not apply to your setup will be skipped.
To Enter Installer Settings Menu
- Press and hold down the MENU button for 5 seconds.
- Release the MENU button after the first installer setting is displayed.
- Change settings as required using the or buttons.
- Press NEXT (HOLD) or BACK (PROG) to move to the next or previous setting.
- Press RETURN (FAN) to exit. Menu will exit automatically after last setting.
*If UNLOCK 0000 is displayed, you must enter your 4-digit installer lock code to proceed (see Installer Settings 39 and 40).
| No.| Installer Setting| Displayed| Default Setting|
Available Settings| Description of Available Settings
---|---|---|---|---|---|---
| 1| Residential or Commercial Profile| MODE| ES| ES| Select
for Residential profile
| COMM| Select for Commercial profile
| If residential mode is selected, 4 programming events per day are available
(MORN, DAY, EVE, NITE). If commercial profile is selected, 2 programming
events per day are available (OCC, UNOC).
| 2| Programming Mode| OG AM DAYS| 7| 7| Select for
7-day programming mode
| 52| Select for 5-2 day programming mode
| O| Select for non-programmable mode
| [Only available if a Residential (RES) profile was selected in setting
1] Selects the programming capabilities of the thermostat, either full 7
individual days, 5-2 day (weekday/weekend) programming or non-programmable.
| 3| Pre-Occupancy Purge| E U GE| OFF| OFF| Pre-Occupancy Purge is
disabled
| :15 – 3:00| Select :15 – 3:00 Pre-Occupancy Purge
| [Only available if a Commercial (COMM) profile was selected in setting
1] Selects the amount of time the system fan will run before the start of
the Occupied (OCC) program period (15 minute increments).
| 4| Clock Format| CLOCK| 12H| 12H| Select for a 12-hour clock
| 24H| Select for a 24-hour clock
| Selects either a 12 hour or 24 hour clock format.
| 5| Temperature Scale| DEG EE| F| F| Select for Fahrenheit
temperature display
| C| Select for Celsius temperature display
| Selects a temperature scale of either °F or °C.
| 6| Auto Changeover| AUTO C G| OFF| OFF| Auto-Changeover disabled
| O| Auto-Changeover enabled
| When auto-changeover mode is enabled and selected, the system can
automatically switch between heating and cooling modes. There is a 5 minute
delay when switching modes if auto changeover is selected.
| 7| Auto Changeover Dead Band| DEADBA D| 3| 2, 3, 4, 5|
Select an Auto Changeover Dead Band of 2°, 3°, 4° or 5˚ F (1°, 1.5°, 2° or
2.5° C)
| [Only available if Auto Changeover was enabled in setting
6] When using auto changeover mode, the dead band is a forced separation
between the heating and cooling setpoints so that the systems do not work
against each other.This setting selects the amount of this dead band in
degrees. If using the dehumidification overcooling feature in setting 28, the
allowable deadband will be limited based on your dehumidification overcooling
limit selection.
| __8| __System Type| __ SYSTEM| __ CO V 11| CO V
11| Select for 1H/1C Conventional system|
| CO V 22| Select for 2H/2C Conventional system (4235)|
| H 11| Select for 1H/1C Heat Pump system|
| H 21| Select for 2H/1C Heat Pump system|
| H 32| Select for 3H/2C Heat Pump system (4235)|
| HD 1| Select for heat-only Hydronic system|
| HD 11| Select for Hydronic system with cooling|
| Select the type of equipment you are controlling. The HP 32 system type is
for a 2-stage heat pump compressor (stage 1 and 2) with auxiliary heat (stage
3). System types CONV 22 and HP 32 are not available in model 4030.|
| 9| 1st Stage Differential| DEG EE DIF1| 0.5| 0.5, 1.0, 2.0|
Select a 1st stage temperature differential of 0.5°, 1° or 2° F (0.2°, 0.5° or
1.0° C)|
| Selects a 1st stage temperature differential which controls the degree of
separation between the setpoint temperature and the 1st stage of heating or
cooling.|
| 10| 2nd Stage Differential| DEG EE DIF2| 2.0| 1.0, 2.0, 3.04.0,
5.0, .0| Select a 2nd stage temperature differential of 1°, 2°, 3°, 4°, 5° or
6° F (0.5°, 1.0°, 1.5°, 2.0°, 2.5° or 3.0° C)|
| [Only available if a 2 or 3 stage system was selected in setting 8]
Selects a 2nd stage temperature differential which controls the degree of
separation between the 1st and 2nd stage of heating or cooling.|
| 11| 3rd Stage Differential| DEG EE DIF3| 2.0| 1.0, 2.0, 3.04.0,
5.0, .0| Select a 3rd stage temperature differential of 1°, 2°, 3°, 4°, 5° or
6° F (0.5°, 1.0°, 1.5°, 2.0°, 2.5° or 3.0° C)|
| [Only available if a 3 stage system was selected in setting 8]
Selects a 3rd stage temperature differential which controls the degree of
separation between the 2nd and 3rd stage of heating.|
| 12| Conventional Heat Fan Control| FA 1| GAS| GAS| Select
for conventional Gas heating|
| ELEC| Select for conventional Electric heating|
| [Only available if a conventional system was selected in setting 8]
Selects a 1st stage fan control of either gas or electric heat. If Electric is
selected, the thermostat turns on the system fan with a call for heating.|
| 13| Emergency Heat Fan Control| EME FA| ELEC| ELEC| Select
for Electric Emergency Heat|
| GAS| Select for Gas Emergency Heat|
| [Only available if a 2 or 3 stage heat pump system was selected in
setting 8] Selects emergency heat fan controlof either gas or electric
heat. If Electric is selected, the thermostat turns on the system fan with a
call for emergency heat.|
| 14| Finish with High Stage| AUX F SH| O| 0| Finish with High
Stage is disabled|
| YES| Finish with High Stage is enabled|
| [Only available if a 2 or 3 stage system was selected in setting
8] When Finish with High Stage is enabled, once engaged, the
supplemental heat source (2nd or 3rd stage) will remain on until temperature
is satisfied. When disabled, these supplemental heat source(s) will turn off
approximately 0.5 degrees before setpoint to let the 1st stage heat source
complete the heat call.|
| 15| Reversing Valve (O/B Terminal)| VALVE| 0| 0| Select for
cool active Reversing Valve|
| B| Select for heat active Reversing Valve|
| [ Only available if a heat pump system was selected in setting 8]
Selects the output state of the O/B terminal. Select O for this terminal to be
active in the cool mode or select B for this terminal to be active in the heat
mode.|
| 16| Fossil Fuel Backup Heat| AUX HEAT| ELEC| ELEC| Select for
Electric Auxiliary heat (with compressor)|
| GAS| Select for Gas Auxiliary heat (without compressor)|
| [Only available if a 2 or 3 stage heat pump system was selected in
setting 8] When set to electric, both the compressor and
auxiliary stage will run when a call for auxiliary heat is made. When set to
gas, the compressor stage(s) will be locked out one minute after a call for
auxiliary heat. This setting can be overridden if setting an auxiliary heat
balance point in setting 34.|
| 17| Compressor Power Outage Protection| C O| OFF| 0FF| Power
outage lockout delay is disabled|
| 0| Power outage lockout delay is enabled|
| [Only available if a heat pump system was selected in setting 8 and
thermostat is powered with a 24 VAC common (C) wire] When enabled, this
thermostat will provide cold weather compressor protection by locking out the
compressor stage(s) of heating for a period of time after a power outage
greater than 60 minutes.|
| 18| AC Power Interrupt Warning| OW MO| OFF| OFF| AC Power
Interrupt Warning is disabled|
| O| AC Power Interrupt Warning is enabled|
| [ Only available if thermostat is powered with a 24 VAC common (C)
wire] When enabled, the thermostat will display NO POWER when AC power to
the thermostat is lost. Batteries must also be installed for this feature to
operate.|
| 19| Compressor Short Cycle Protection (CSCP)| CSC MI| 5| 5, 4,
3,2, 1, 0| Select CSCP delay duration in minutes|
| Selects the number of minutes the compressor(s) will be locked out after
turning off. This delay will run simultaneously with any delay built into the
equipment.|
| 20| Residual Cooling Fan Delay| ESIDUAL COOL| 0| 0, 0,30, 0|
Select fan delay duration in seconds|
| Selects a delay for the system fan after the cooling compressor has turned
off. This delay will help remove the remaining cool air out of the ductwork
providing additional efficiency.|
| 21| Circulating Fan Lock| CI CLOCK| OFF| OFF| Circulating Fan
Lock is disabled|
| O| Circulating Fan Lock is enabled|
| [Not available if 1 HD was selected in setting 8] When enabled, the
only user fan settings available are ON and CIRC (Circulation). The AUTO and
PROG fan settings are not available with this setting enabled.|
| 22| Adaptive Recovery Mode (ARM TM )| ECOVE| OFF|
OFF| Adaptive Recovery Mode is disabled|
| O| Adaptive Recovery Mode is enabled|
| [Not available if non-programmable was selected in setting 2] During
ARM, room temperature is recovered by turning on the heating or cooling up to
3-hours before the end of the set back period. The setpoint temperature is
changed to that of the upcoming program temperature.|
| 23| Indoor Remote Sensor| EMOTE SE S| I| I|
Temperature is sensed from thermostat only (Internal)|
| E| Temperature is sensed from remote sensor only (External)|
| A| Temperature is averaged between thermostat and remote sensor (Average)|
| [Only available if Braeburn model 5390 remote indoor sensor is
connected] If a Braeburn indoor remote sensor is connected, the thermostat
will automatically detect the sensor. When an indoor sensor is detected, you
may select between thermostat only (1), remote sensor only (E) or the average
of the thermostat and remote sensor (A).|
| 24| User Lock Security Level| USE LOCK LVL| 3| 3|
If locked, all buttons are disabled|
| 2| If locked, all buttons except and are disabled|
| 1| If locked, only the PROG, HOLD and MENU buttons are disabled|
| Selects the level of keypad lockout when the thermostat has been locked by
the user. See the User Manual for instructions on setting the 3-digit lock
code and locking/unlocking the thermostat.|
25| Humidification (4235 only)| HUMID| OFF| OFF| Humidification
is disabled|
DE| Dependent humidification is enabled|
I D| Independent humidification is enabled|
For use with an external humidifier. Select between disabling humidification,
dependent control or independent control.The DEP setting controls
humidification only during a call for heating. The IND setting allows
humidification output in the heat mode, but does not require a call for
heating. It is recommended that the IND setting only be used with systems
designed for low air temperature humidification such as steam humidification.
Always ensure the heat exchanger or other system parts are not exposed to
excess water from condensation or other sources. When there is any doubt, use
the OFF or DEP setting.|
26| Auto Humidity Set Point Limit (4235 only)| HUMID| MA| MA|
Maximum humidity setpoint is not limited|
AUTO| Maximum humidity setpoint is limited based on outdoor temperature|
[Only available if Braeburn ® model 5490 remote outdoor
sensor is connected] When AUTO is selected, the humidity setpoint maximum
is limited based on the outdoor temperature. Selecting MAN allows you to
manually control thelevel of humidity between 10% and 50%.|
27
‘| Dehumidification (4235 only)| DEHUMID| OFF| OFF| Dehumidification
is disabled|
DE| Dependent dehumidification is enabled|
I D| Independent dehumidification is enabled|
[IND (independent) dehumidification is not available if Humidification
was enabled in setting 25] (DEP) If the humidity level is above the
humidity setpoint, cooling stays on until the humidity level drops below the
setpoint or when the over cooling limit in setting 28 is reached in. (IND) For
use with an external dehumidifier – When the humidity level rises above the
dehumidification setpoint, both the G (Fan) and D terminals are activated. Not
available in 1HD system mode.|
28| Dehumidification Overcooling Limit (4235 only)| OVE COOL
LIM| 1.0| 1.0°, 2.0°,or 3.0° F(.5°, 1.0°,or 1.5° C)| Select a dehumidification
overcooling limit in degrees|
[Only available if dependent dehumidification (DEP) was selected in
setting 27] Select the number of degrees the system is allowed to
over cool while attempting to reduce humidity. This setting will affect the
maximum allowable deadband set in setting 7.|
29| Dehumidification (D) Terminal Output (4235 only)| DH ELAY|
:0| :0| Select a normally open relay|
:C| Selects a normally closed relay|
[Only available if independent dehumidification (IND) was selected in
setting 27] Select normally open relay (N:O) or normally closed (N:C) relay
for D terminal output in independent dehumidification mode. This setting can
also be used for dehumidification fan speed control.|
| 30| Dry Contact Type| CO TACT| OFF| OFF| Dry contact is disabled|
| CO D| Select for condensate overflow monitoring|
| DOO| Select for door open monitoring|
| OCC| Select for occupancy monitoring|
| [If a Residential profile was selected in setting 1, only the
condensate (COND) setting will be available] The dry contact can be used to
monitor several conditions. See the table below for an outline of these
conditions. WARNING: DRY1, DRY2 terminals are a dry contact relay and
should never have voltage applied to them. If not using the dry contact, make
sure to select OFF for this setting.|
| | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
| Detailed Description of Dry Contact Settings (Installer Setting 30)
---|---
| Condensate| CO D| This setting is intended for a condensate pan
overflow monitor. When the contact is active, the thermostat will immediately
disable the cooling compressor(s) and display the message OVERFLOW. After the
contact is inactive for 1 minute, the compressor(s) will resume operation and
the thermostat display will return to normal.
| Door Switch| DOO| This setting is intended for a door switch monitor.
When this mode is selected, the thermostat will only run the occupied (OCC)
portion of the program schedule while the contact is inactive (door closed).
When the contact becomes active (door open), the thermostat will turn OFF and
display the message DOOROPEN until the contact becomes inactive again. There
is a 3-minute delay before the thermostat turns OFF. Temperature override is
not permitted while the contact is active (door open).
| Occupancy| OCC| This setting is intended for the use of an occupancy
sensor or mechanical spring-wound timer switch. When active, the thermostat
will be forced into the occupied (OCC) portion of the program schedule until
the contact becomes inactive. In setting 32 below, the Occupancy Trigger
Controlcan be selected (PROG or UNOC).
| 31| Dry Contact Relay State| CO TACT| :0| :0| Selects a normally
open relay
| :C| Selects a normally closed relay
| [Not available if OFF was selected in setting 30] Select normally
open (N:O) or normally closed (N:C) for the dry contact relay terminals (DRY1,
DRY2).
| 32| Occupancy Trigger Control| OCCU IED| OG| OG| Follows
current program schedule until the occupied state is triggered
| U OC| Follows the unoccupied (UNOC) program schedule until the occupied
state is triggered
| [Only available if occupancy monitoring (OCC) was selected in setting
30] If the dry contact type was set to occupied (OCC) in setting 30, there
will be 2 selections for the occupied state. If PROG is selected (default),
the thermostat will follow its normal program schedule until the dry contact
is active. When the dry contact is active, the thermostat will only operatethe
occupied portion of the program schedule and ignore the unoccupied portion of
the program schedule. If UNOC is selected, the thermostat will ignore the
program schedule and always operate in the unoccupied state. When the dry
contact is active, the thermostat will operate in the occupied state for the
duration of the contact being active.
33| Compressor Balance Point| BAL OI T COM| O| O| Compressor
balance point is disabled|
0 to 50(-18˚ to 10˚C)| Select a Compressor Balance Point of 0˚ to 50˚ (-18˚ to
10˚C)|
[Only available for 2 or 3 stage heat pump systems with a Braeburn
® 5490 outdoor sensor connected] Locks out the use of the heat pump
compressor’s heat stage(s) when the outside air temperature is less than the
selected setting. During this lockout period, only the auxiliary heat stage
will operate.|
34| Auxiliary Heat Balance Point| BAL OI T AUX| O| O| Auxiliary
heat balance point is disabled|
70 to 40(21 ˚ to 4˚C)| Select a Auxiliary Heat Balance Point of 70° to 40°F
(21° to 4°C)|
[Only available for 2 or 3 stage heat pump systems with a Braeburn 5490
outdoor sensor connected] Locks out the use of the auxiliary heat stage
when the outside air temperature exceeds the selected setting. This balance
point overrides the fossil fuel compressor lockout in setting 16. If setting
16 is set to gas and the outdoor temperature is over the auxiliary balance
point, the compressor will remain on during a call for auxiliary heat.|
35| Heat Setpoint Upper Limit| HIGH LIM HEAT| 0| 0 – 45(32˚ to
7˚C)| Select a Heat Setpoint Upper Limit of 90° to 45°F (32° to 7°C)|
Selects the upper setpoint adjustment limit that cannot be exceeded in heat
mode.|
36| Heat Setpoint Lower Limit| LOW LIM HEAT| 45| 45 – 0(7˚ to
32˚C)| Select a Heat Setpoint Lower Limit of 45° to 90°F (7° to 32°C)|
Selects the lower setpoint adjustment limit that cannot be exceeded in heat
mode.|
37| Cool Setpoint Lower Limit| LOW LIM COOL| 45| 45 – 0(7˚
to 32˚C)| Select a Cool Setpoint Lower Limit of 45° to 90°F (7° to 32°C)|
[Not available for heat-only hydronic systems] Selects the lower
setpoint adjustment limit that cannot be exceeded in cool mode.|
38| Cool Setpoint Upper Limit| HIGH LIM COOL| 0| 0 – 45(32˚ to
7˚C)| Select a Cool Setpoint Upper Limit of 90° to 45°F (32° to 7°C)|
[Not available for heat-only hydronic systems] Selects the upper
setpoint adjustment limit that cannot be exceeded in cool mode.|
39| Installer Lock| I STLOCK| O| O| Installer Lock disabled|
YES| Installer Lock enabled|
When enabled, a 4-digit lock code can be entered in setting 40. This lock code
will be required the next time the Installer Settings menu is accessed. Select
NO to skip the installer lock.|
40| Installer Lock Code| IL CODE| 0000| 0-| Select 0-9 for each
digit|
[Only available if Installer Lock was enabled in setting 39] Select a
4-digit lock code (0-9 for each digit) to lock the Installer Settings menu.
The code 0000 is not a valid lock code and cannot be used.|
41| Installer Clear (factory reset)| CLEA| O E| O E| Clear
disabled – No changes made|
ALL| Clear enabled – Factory Reset|
Selecting ALL will return thermostat to all factory default settings. Factory
reset will take affect upon exiting Installer settings menu.|
Additional options such as Service Monitors, setting the lock code, etc. are located in the User Settings – See User Manual.
SYSTEM TESTING
Warning Read Before Testing
- Do not short (or jumper) across terminals on the gas valve or at the heating or cooling system control board to test the thermostat installation. This could damage the thermostat and void the warranty.
- Do not select the COOL mode of operation if the outside temperature is below 50º F (10º C). This could possibly damage the controlled cooling system and may cause personal injury.
- This thermostat includes an automatic compressor protection feature to avoid potential damage to the compressor from short cycling. When testing the system, make sure to take this delay into account.
NOTE: The compressor delay can be bypassed by adjusting Installer Setting 19 – See section 4.
- Press the SYSTEM button until the thermostat is in HEAT mode.
- Press the button to raise the set temperature a minimum of 3 degrees above the current room temperature. The system should start within a few seconds. With a gas heating system, the fan may not start right away.
- Press the SYSTEM button until the thermostat is in the OFF mode. Allow the heating system to fully shut down.
- Press the SYSTEM button until the thermostat is in the COOL mode.
- Press the button to lower the set temperature a minimum of 3 degrees below the current room temperature. The system should start within a few seconds (unless compressor short cycle protection is active – See note above).
- Press the SYSTEM button until the thermostat is in the OFF mode. Allow thcooling system to fully shut down.
- Press the FAN button until the thermostat is in FAN ON mode. The system fan should start within a few seconds.
- Press the FAN button until the thermostat is in FAN AUTO mode. Allow the system fan to turn off.
- If the thermostat is controlling auxiliary equipment such as a humidifier, adjust settings to test these devices.
Limited Warranty
When installed by a professional contractor, this product is backed by a 5 year limited warranty. Limitations apply. For limitations, terms and conditions, you may obtain a full copy of this warranty:
-
Call us:
866.268.5599 -
Write us:
Braeburn Systems LLC
2215 Cornell Avenue
Montgomery, IL 60538
Installer – store this manual for future reference
Braeburn Systems LLC
2215 Cornell Avenue • Montgomery, IL 60538
Technical Assistance:
www.braeburnonline.com
Call us toll-free : 866-268-5599
(U.S.)
630-844-1968 (Outside the U.S.)
©2022 Braeburn Systems LLC • All Rights Reserved