BV 471S Indirect Oil Fired Air Heaters User Manual
TECHNICAL DATA TABLE
| BV 471S| BV 471SR| BV 691S
---|---|---|---
| 136 kW-kW 116,900 kcal/h-kcal/h
464,000 Btu/h-BTE/h| 136 kW-kW 116,900 kcal/h-kcal/h
464,000 Btu/h-BTE/h| 225 kW-kW 193,500 kcal/h-kcal/h
768,000 Btu/h-BTE/h
| 8.500 m³/h-m³/h| 8.500 m³/h-m³/h| 12.800 m³/h-m³/h
| 10.8 kg/h-kg/h| 10.8 kg/h-kg/h| 17.9 kg/h-kg/h
| DIESEL-KEROSENE| DIESEL-KEROSENE| DIESEL-KEROSENE
| ~220-240 V-V (-15%÷10%) 50 Hz-Hz
6.9 A 1.5 kW-kW| ~220-240 V-V (-15%÷10%)
50 Hz-Hz 16 A 3.7 kW-kW| ~220-240 V-V (-15%÷10%)
50 Hz-Hz 12.6 A 2.8 kW-kW
| 2,5 gal/h 60°W DELAVAN| 2,5 gal/h 60°W DELAVAN| 4,5 gal/h 60°W DELAVAN
| 1.250 kPa-kPa 12.5 bar| 1.250 kPa-kPa 12.5 bar| 1.000 kPa-kPa
10 bar
| 250 Pa-Pa| 400 Pa-Pa| 250 Pa-Pa
| 0.1 mbar-mbar| 0.1 mbar-mbar| 0.1 mbar-mbar
| 270 kg-kg| 300 kg-kg| 380 kg-kg
| ø 2,5 mm² (MAX. 30m)
ø 4 mm² (MAX. 50m)| ø 2,5 mm² (MAX. 30m)
ø 4 mm² (MAX. 50m)| ø 2,5 mm² (MAX. 30m)
ø 4 mm² (MAX. 50m)
IMPORTANT: In order to have a correct function you must use an electrical generator in class G3 or more (frequency va- riation ±1%, tension variation ±2%). The maximum power of electrical generator must be three time the nominal power of device that you must connect.
- The extension cords are suggested according rated input voltage. Do only use approved cables and plugs. Do not connect more than one extension cord.
| BV 691T| BV 691TR
---|---|---
| 225 kW-kW 193,500 kcal/h-kcal/h 768,000 Btu/h-BTE/h| 225 kW-kW 193,500
kcal/h-kcal/h 768,000 Btu/h-BTE/h
| 12.800 m³/h-m³/h| 12.800 m³/h-m³/h
| 17.9 kg/h-kg/h| 17.9 kg/h-kg/h
| DIESEL-KEROSENE| DIESEL-KEROSENE
| 3N~380-400 V-V (-15%÷10%) 50 Hz-Hz 6.5 A 2.3 kW-kW| 3N~380-400 V-V
(-15%÷10%) 50 Hz-Hz 7.6 A 4.2 kW-kW
| 4,5 gal/h 60°W DELAVAN| 4,5 gal/h 60°W DELAVAN
| 1.000 kPa-kPa 10 bar| 1.000 kPa-kPa 10 bar
| 250 Pa-Pa| 400 Pa-Pa
| 0.1 mbar-mbar| 0.1 mbar-mbar
| 380 kg-kg| 420 kg-kg
| ø 2,5 mm² (MAX. 30m)
ø 4 mm² (MAX. 50m)| ø 2,5 mm² (MAX. 30m)
ø 4 mm² (MAX. 50m)
IMPORTANT: In order to have a correct function you must use an electrical generator in class G3 or more (frequency variation ±1%, tension variation ±2%). The maximum power of electrical generator must be three time the nominal power of device that you must connect.
- The extension cords are suggested according rated input voltage. Do only use approved cables and plugs. Do not connect more than one extension cord.
PICTURES
IMPORTANT: READ AND UNDERSTAND THIS OPERATIONAL MANUAL PRIOR TO ASSEMBLING, STARTING UP OR CONDUCTING MAINTENANCE ON THIS HEATER. USING THE HEATER INCORRECTLY CAN CAUSE SERIOUS OR FATAL INJURIES. KEEP THIS MANUAL FOR FURTHER REFERENCE.
►►►DESCRIPTION
This series of heaters is particularly suited to heating medium to large-sized rooms or areas. Thanks to an internal heat exchanger, indirect heaters (PIC.
- separate combustion gases from the hot air released into the environment. This way it is possible to have a flow of clean hot air in the area that needs to be heated up and direct combustion products outside. These heaters have been designed in line with the most recent safety, operating and duration criteria. The safety devices ensure the heater always operates correctly.
►►► SAFETY INFORMATION WARNINGS
IMPORTANT: This air heater has been designed for mobile and temporary
professional applications. It has not been designed for domestic use nor for
thermal comfort of human.
IMPORTANT: This appliance is not suitable for use by persons (including
children) with reduced physical, sensory or mental capacities or who lack
experience or knowledge unless supervised by a person responsible for their
safety. Children must be supervised to make sure they do not play with the
appliance.
DANGER: Suffocation by carbon monoxide can be fatal.
The first symptoms of suffocation by carbon monoxide are similar to those of
flu with headache, light-headedness and/or nausea. These symptoms could be
caused by the faulty functioning of the heater. IF THESE SYMPTOMS OCCUR, GO
OUTDOORS IMMEDIATELY and have the heater repaired by the technical support
centre.
►►2.1. REFUELLING:
►2.1.1. Personnel appointed to carry out refuelling must be qualified and
fully familiar with the manufacturer’s instructions and current regulations on
how to refuel heaters safely.
►2.1.2. Only use the type of fuel specified on the heater’s identification
plate.
►2.1.3. Before refuelling, turn off the heater and wait for it to cool down.
►2.1.4. The tanks used to store the fuel must be stored in a separate place.
►2.1.5. Fuel tanks must be kept at a minimum distance from the heater, in
accordance with current standards.
►2.1.6. The fuel must be stored in an area where the floor does not allow it
to penetrate or drip onto flames underneath it, which may ignite the fuel.
►2.1.7. The fuel must be stored in accordance with current regulations.
►►2.2. SAFETY:
►2.2.1. Never use the heater in areas with petrol, paint solvents or other
highly flammable vapours.
►2.2.2. Comply with all local legislation and current regulations when using
the heater.
►2.2.3. Heaters used near tarpaulins, curtains or other similar covering
materials must be a safe distance from them. It is advised to use fire-proof
covering material.
►2.2.4. Only use in well-ventilated areas. Set-up a suitable opening in line
with current standards, with the purpose of introducing fresh air from
outdoors.
►2.2.5. Power on the heater only with a current which has the voltage and
frequency values specified on the identification plate.
►2.2.6. Only use suitably earthed extension cables.
►2.2.7. Recommended safety distances between the heater and flammable
substances: front output 2.5 m; on the side, at the top and at the back = 1.5
m.
►2.2.8. Avoid fire hazards by placing the hot or functioning heater on a
steady level surface.
►2.2.9. Keep animals at a safe distance from the heater.
►2.2.10. Disconnect the heater from the mains power supply when not in use.
►2.2.11. When it is controlled by a thermostat, the heater can turn on at any
time.
►2.2.12. Never use the heater in frequently used rooms nor in bedrooms.
►2.2.13. Never block the heater’s air vent or the air outlet.
►2.2.14. Never move, handle, refuel or conduct maintenance on the heater when
it is hot, connected to the mains or in operation.
►2.2.15. Only use original kits to direct the air coming in and/or going out
(where applicable).
►2.2.16. Keep the hot parts of the heater at a suitable distance from
inflammable or thermolabile materials (including the power supply cable).
►2.2.17. If the power supply cable is damaged, it must be replaced by a
technical support centre to prevent any risk.
►2.2.18. During operation, make sure that the firefighting devices are ready
for use.
►2.2.19. Use original spare parts when replacing the burner, strictly
complying with indications regarding capacity, type of nozzles and pump
pressure. An increase in burner power could damage the heater.
►►► UNPACKING
WARNING: THE PACKAGING MATERIAL IS NOT A TOY. KEEP THE PLASTIC BAG OUT OF
REACH OF CHILDREN; DANGER OF SUFFOCATION!
►3.1. Remove all packaging materials used to package and ship the heater.
Dispose of them in compliance with current standards.
►3.2. If the heater is placed on the platform, lower it gently using suitable
devices and instruments, in accordance with national regulations and current
standards. It can be lifted with the forklift truck, by using suitable chains
and suspension hooks (the heater is equipped with eyebolts).
►3.3. Check for any damage incurred during transport. If the heater appears
damaged, immediately inform the dealer from whom it was purchased.
►►► ASSEMBLY
(PIC. 2)
These heaters are equipped with handles, brackets, supports, etc. depending on
the model. These parts, which come with the relative nuts and bolts, are in
the heater’s packaging.
►►► FUEL
WARNING: THE HEATER ONLY WORKS WITH DIESEL OR KEROSENE.
Only use diesel or kerosene to avoid any fire or explosion hazard. Never use
petrol, naphtha, solvents for paints, alcohol or other highly inflammable
fuels.
Use non-toxic, anti-freeze additives in case of very low temperatures.
It is recommended to use winter diesel oil below 5°C.
►►►OPERATING PRINCIPLES
The burner pump draws the fuel from the tank and sends it to the pressurised
nozzle where it is nebulised and mixed with comburent air in the combustion
chamber. A spark triggers combustion while the waste fumes are expelled from
the chimney. A series of sensors constantly checks the correct operation of
the heater, stopping the cycle in the case of a fault. The fan, located at the
rear of the heater, cools the combustion chamber and the flue gas pass,
transferring the heat from the latter into the environment.
►►► CONTROL PANEL
(PIC. 3)
A. Electronic regulator.
B. Hour meter.
C. Power switch.
D. Ventilation control button.
E. Electric voltage presence light.
F. Burner block alarm light.
G. Ventilation block alarm light.
H. Overtemperature alarm light.
I. Overtemperature thermostat reset.
L. Burner connector.
M. Fuse.
N. Room thermostat remote connector.
►►►OPERATION
WARNING: CAREFULLY READ THE “SAFETY INFORMATION” BEFORE SWITCHING ON THE
HEATER.
►►8.1. IGNITING THE HEATER:
►8.1.1. Follow all the safety instructions.
►8.1.2. Connect the fuel pipes respecting the correct inlet and outlet
connections (PIC. 4).
►8.1.3. Check if there is any fuel in the tank.
►8.1.4. Connect the supply plug to the power mains (PIC. 5) (SEE VOLTAGE IN
THE “TECHNICAL DATA TABLE”).
►8.1.5. Set the “ON/OFF” switch to “FLAME” (C PIC. 3). The heater should turn
on within a few seconds.
If the heater does not start, refer to paragraph “TROUBLESHOOTING”.
►8.1.6. The heater can be used in ventilation mode, which is activated by
setting the ON/OFF switch to “FAN” (C PIC. 3).
►8.1.7. The heater has a ventilation control button (D PIC. 3). -BUTTON ON:
The ventilation works continuously (ideal for extreme conditions of use).
-BUTTON OFF: The ventilation works automatically (normal operation).
►8.1.8. For models with a room thermostat, check the set temperature (PIC. 6).
NOTE: IF THE HEATER SWITCHES OFF DUE TO LACK OF FUEL, TOP UP THE TANK AND
RESET THE HEATER (SEE PAR. “RESET THE HEATER”).
IMPORTANT: IN INDIRECT MODELS, COMBUSTION PRODUCTS CAN BE DIRECTED OUTSIDE VIA
THE DUCTS. CARRY OUT THE DUCTING IN
ACCORDANCE WITH CURRENT REGULATIONS AND FOLLOW THE INSTRUCTIONS IN THE
RELEVANT SECTION OF THE MANUAL.
►►8.2. TURNING OFF THE HEATER:
Turn the “ON/OFF” switch to “0” (C PIC. 3). The flame turns off and the fan
keeps on working until the combustion chamber has fully cooled down. Do not
pull out the electrical plug until the cooling cycle has ended.
►►► RESET THE HEATER
In the event of an anomaly during the normal operation, the heater switches
off. To restart the heater, identify and eliminate the cause that caused the
stop (for instance, obstruction of the air intake and/or outlet, fan stop,
lack of fuel, etc.). If it is not possible to eliminate the problem that
caused the stoppage, contact a support centre for technical assistance.
In order to reset the heater, we recommend following the procedure below
(follow all safety-related instructions):
►OVERTEMPERATURE THERMOSTAT RESET [Light on (H PIC. 3)]: The heater has
reached the maximum operating temperature. To reset the heater, eliminate the
cause of the block (if necessary, contact the support centre), remove the
cover (PIC. 7), loosen the plug and press the button all the way (I PIC. 3).
Then tighten the plug again and restore the cover (PIC. 8).
►RESET THE BURNER [Light on (F PIC. 3) (PIC.
9)]: The burner has had an operation anomaly. To reset the burner, eliminate
the cause of the block (if necessary, contact the support centre), remove the
cover (PIC. 7) and fully press the button for a few seconds (PIC. 10). Then
restore the cover (PIC. 8).
►RESET THE VENTILATION MOTOR [Light on (G PIC. 3)]: The ventilation motor is
blocked or works abnormally. To reset the heater, turn the “ON/OFF” switch to
“0” (C PIC. 3), eliminate the cause of the block (if necessary, contact the
support centre) and switch the heater on again.
►►►ELECTRONIC REGULATOR CONFIGURATION
IMPORTANT: THE ELECTRONIC REGULATOR (ALREADY SET UP BY THE MANUFACTURER),
IF IT IS NOT RE-SET UP, DOES NOT COMPROMISE
THE CORRECT OPERATION OF THE HEATER. The electronic regulator (A PIC. 3)
controls the start-up and shutdown of the ventilation in the preheating and
post-ventilation stages of the heater. Depending on the room temperature (very
cold weather or very hot weather, SEE TAB. ”CONFIGURING THE ELECTRONIC
REGULATOR”), it may be required to change the reference parameter.
Configuration procedure:
►10.1. Make sure that the on/off switch is at “0” and the power plug is
connected to the power mains.
►10.2. Perform the following key sequence:
- Press the “SET” key.
- Display “SP2“ by scrolling with the “▼“ / “▲“ keys.
- Press the “SET” key to access.
- Set the desired temperature using the “▼“ / “▲“ keys.
- Press the “SET” key to confirm.
IMPORTANT: THE ELECTRONIC REGULATOR DOES NOT HAVE THE ROOM THERMOSTAT FUNCTION.
►►► CLEANING THE FILTERS
►►11.1. INTAKE FILTER, DEPENDING ON THE MODEL: (PIC. 11)
The filters may need to be cleaned depending on the quality of the fuel used:
►11.1.1. Remove the cup (A).
►11.1.2. Take out the filter (B) from the cup. Make sure you preserve the
gaskets.
►11.1.3. Clean the filter (B) with clean fuel; make sure you do not damage it.
►11.1.4. Put the filter (B) back into the cup.
►11.1.5. Put the glass (A) back, make sure you reassemble the gaskets
correctly.
►►11.2. FUEL PUMP FILTER:
See the preventive maintenance schedule.
►►►12. STORAGE AND TRANSPORT
WARNING: BEFORE ANY MOVEMENT, STOP THE HEATER (SEE PAR. “TURNING OFF THE
HEATER”), DISCONNECT THE POWER SUPPLY BY REMOVING THE PLUG FROM THE POWER
SOCKET (PIC. 12) AND WAIT FOR THE HEATER TO COOL DOWN COMPLETELY. KEEP THE
HEATER IN A LEVEL POSITION WHEN MOVING IT.
In order to keep the heater in the best possible conditions, we recommend
following the procedure below (follow all safety-related instructions):
►12.1. It can be lifted with the forklift truck, by using suitable chains and
suspension hooks (the heater is equipped with eyebolts).
►12.2. In order to keep the heater in the best conditions possible, we
recommend placing it in a dry place away from potential external damage.
►►►CONNECTING THE ROOM THERMOSTAT
In models with a room thermostat connection, remove the plug connected to
the heater and connect the room thermostat (optional) (PIC. 13-14).
►►►14. TIPS FOR DUCTING (PIC. 15)
IMPORTANT: ONLY USE ORIGINAL KITS TO DIRECT THE AIR COMING IN AND/OR GOING OUT
(WHERE APPLICABLE).
In order to avoid heater operating problems or harm to people, pay attention
to the layout of the air ducting pipes. To reduce the air flow resistance, we
recommend positioning the ducting pipes reducing the number of curves and
avoiding bends with sharp corners. The first. meters must be without curves.
WARNING: BEFORE PERFORMING ANY MAINTENANCE OR REPAIRS, DISCONNECT THE
POWER SUPPLY CABLE FROM THE MAINS AND MAKE SURE THAT THE HEATER IS COLD.
►►►PREVENTIVE MAINTENANCE SCHEDULE
COMPONENT | MAINTENANCE FREQUENCY | MAINTENANCE PROCEDURE |
---|---|---|
Filters | Clean or replace once a year or as required (make sure they are | |
intact) | Clean the filters (SEE PAR. “CLEANING THE FILTERS”) | |
Fuel pump filter | Clean or replace once a year or as required (make sure they | |
are intact) | Contact a support centre | |
Electrodes | Clean as required | Contact a support centre |
Fan | Clean as required | Contact a support centre |
Combustion chamber | Clean as required | Contact a support centre |
►►►TROUBLESHOOTING
PROBLEM | POSSIBLE CAUSE | POSSIBLE SOLUTION |
---|---|---|
The heater does not start or does not remain on | 1.”ON/OFF” switch at “0” |
2.No power supply
3.Interrupted power cable
4.Electronics need to be reset or are faulty
5.Incorrect setting of the room thermostat (if applicable)
6.No fuel
7.Foreign substances in the fuel circuit
8.Temperature set on the digital thermostat too high
9.Electronics blocked| 1. Set the “ON/OFF” switch to “FLAME” (C PIC. 3)
2a.Plug the power cable into the mains socket (PIC. 5)
2b.Check your system is powered correctly
3.Contact a support centre
4a.Reset the heater (SEE PAR. “RESET THE HEATER”)
4b.Contact a support centre
5.Set the room thermostat to a temperature higher than the temperature of the
working environment (PIC. 6)
6.Refuel and, if necessary, reset the heater (SEE PAR. “RESET THE HEATER”)
7a.Empty and fill the tank with clean fuel
7b.Clean the filters (SEE PAR. “CLEANING THE FILTERS”)
7c.Contact a support centre
8.Lower the set temperature of the digital thermostat (SEE PAR. “ELECTRONIC
REGULATOR CONFIGURATION”)
9.Reset the electronics (SEE PAR. “RESET THE HEATER”)
The heater generates smoke during operation| 1.Foreign substances in the fuel
circuit
2.Obstruction of inlet air vent| 1 a.Empty and fill the tank with clean fuel
1 b.Clean the filters (SEE PAR. “CLEANING THE FILTERS”)
1 c.Contact a support centre
2. Remove all possible obstructions from the air vent
The heater does not switch off| 1.Temperature set on the digital thermostat
too low
2.Electronics are faulty| 1.Raise the set temperature of the digital
thermostat (SEE PAR. “ELECTRONIC REGULATOR CONFIGURATION”)
2.Contact a support centre
FLUE CONNECTIONS DIAGRAM
DUCTING INSTRUCTIONS
A | > 1 m-м |
---|---|
B | ≥ 1 m-м |
C | As short as possible |
D | > 5° |
E | Windproof terminal |
WIRING DIAGRAMS –
BV 471S – BV 471SR – BV 691S
BV 691T – BV 691TR
ELECTRONIC REGULATOR CONFIGURATION
CE CONFORMITY CERTIFICATE ****
CE CONFORMITY CERTIFICATE
DANTHERM S.p.A. Via Gardesana 11, -37010- Pastrengo (VR), ITALY
Product:
BV 471S – BV 471SR – BV 691S – BV 691T – BV 691TR
We declare that it is compliant with:
2014/30/EU, 2014/35/EU
EN 62233:2008, EN 61000-3-2:2014, EN 61000-3-3:2013, EN 55014-1:2006/
A2:2011, EN 55014-2:2015, EN 60335-1:2012/A11:2014, EN 60335-2102:2016
Pastrengo, 2022
Stefano Verani (Member of the Board)
UKCA CONFORMITY CERTIFICATE
DANTHERM S.p.A. Via Gardesana 11, -37010- Pastrengo (VR), ITALY
Product:
BV 471S – BV 471SR – BV 691S – BV 691T – BV 691TR
We declare that it is compliant with:
2014/30/EU, 2014/35/EU
BS EN 62233:2008, BS EN 61000-3-2:2014, BS EN 61000-3-3:2013,
BS EN 55014-1:2017+A11:2020, BS EN 55014-2:2015, BS EN 603351:2012+A2:2019, BS
EN 60335-2-102:2006+A2:2016
Pastrengo, 2022
Stefano Verani (Member of the Board)
DISPOSAL OF THE PRODUCT
- This product has been designed and manufactured with top-quality materials and components, which can be re-cycled and re-used.
- When a crossed-wheely bin symbol is attached to the product, it means that the product is protected by the, 2012/19/UE European Directive.
- Please obtain information regarding the local differentiated collection system for electrical and electronic products.
- Respect local Standards in force and do not dispose of old products as normal domestic waste. Correct disposal of the product helps to prevent possible negative consequences for health, the environment and mankind.
Dantherm Ltd.
Unit 12, Galliford Road
Maldon CM9 4XD
United Kingdom t. +44 (0)1621 856611