Zennio Z50 Full Color Capacitive Touch Panel User Guide

June 9, 2024
Zennio

Z50 Full Color Capacitive Touch Panel

Z50 / Z70 v2 / Z100
Full Color Capacitive Touch Panel with 5″/7″/10″ display
ZVIZ50 / ZVIZ70V2 / ZVIZ100
Application Program Version: [3.6] User Manual Version: [3.6]_a www.zennio.com

USER MANUAL

Z50 / Z70 v2 / Z100

CONTENTS

Contents ………………………………………………………………………………………………………………………. 2 Document updates………………………………………………………………………………………………………… 5 1 Introduction ………………………………………………………………………………………………………….. 7
1.1 Z50 / Z70 v2 / Z100………………………………………………………………………………………….. 7 1.2 Functionality…………………………………………………………………………………………………. 10 1.3 Installation……………………………………………………………………………………………………. 11 1.4 Start- up………………………………………………………………………………………………………… 14
1.4.1 EULA …………………………………………………………………………………………………………… 14 2 Configuration……………………………………………………………………………………………………….. 15
2.1 General ………………………………………………………………………………………………………… 15 2.1.1 Configuration……………………………………………………………………………………………….. 15 2.1.2 Locale …………………………………………………………………………………………………………. 21 2.1.3 Backlight ……………………………………………………………………………………………………… 25 2.1.4 Security……………………………………………………………………………………………………….. 25 2.1.5 Schedulers …………………………………………………………………………………………………… 28 2.1.6 Screensaver …………………………………………………………………………………………………. 31 2.1.7 Internal Temperature Sensor …………………………………………………………………………. 33 2.1.8 Ambient Luminosity Sensor …………………………………………………………………………… 34 2.1.9 Touch Locking………………………………………………………………………………………………. 34 2.1.10 Sounds ………………………………………………………………………………………………………. 35 2.1.11 Update Setting …………………………………………………………………………………………… 37 2.1.11.1 Firmware Update………………………………………………………………………….. 38 2.1.11.2 Licence Setup……………………………………………………………………………….. 38 2.1.11.3 Import and export translations ………………………………………………………. 39 2.1.11.4 Custom Icons ……………………………………………………………………………….. 41 2.1.12 IP Configuration………………………………………………………………………………………….. 43 2.1.13 VoIP Calls (License required) ………………………………………………………………………… 46 2.1.13.1 Video Intercom (License required) ………………………………………………….. 48
2.1.13.1.1 Outdoor Unit n ………………………………………………………………………………………..50 2.1.13.1.2 General Outdoor Unit……………………………………………………………………………….52

https://www.zennio.com

Tecnical Support: https://support.zennio.com 2

Z50 / Z70 v2 / Z100

2.1.13.2 Internal Call (License required) ………………………………………………………. 53

2.1.13.2.1 Contact n ………………………………………………………………………………………………..55

2.1.14 Avanced…………………………………………………………………………………………………….. 56

2.1.14.1 Cleaning Function …………………………………………………………………………. 56

2.1.14.2 Pop-ups……………………………………………………………………………………….. 58

2.1.14.2.1 Pop-Up n…………………………………………………………………………………………………59

2.1.14.3 Welcome back object ……………………………………………………………………. 60

2.2 Display …………………………………………………………………………………………………………. 62

2.2.1 Pages ………………………………………………………………………………………………………….. 62

2.2.1.1

Menu ………………………………………………………………………………………….. 64

2.2.1.2

Configuration Page ……………………………………………………………………….. 65

2.2.1.2.1 Device ………………………………………………………………………………………………………70

2.2.1.2.2 Profile ………………………………………………………………………………………………………72

2.2.1.2.3 VoIP Calls (License Required)……………………………………………………………………….73

2.2.1.3

Page n …………………………………………………………………………………………. 75

2.2.2 Controls ………………………………………………………………………………………………………. 77

2.2.2.1

Control i ………………………………………………………………………………………. 78

2.2.2.1.1 INDICATORS ………………………………………………………………………………………………80

2.2.2.1.1.1 Binary ………………………………………………………………………………………………80

2.2.2.1.1.2 Enumeration……………………………………………………………………………………..80

2.2.2.1.1.3 Numerical Indicators ………………………………………………………………………….81

2.2.2.1.1.4 Text………………………………………………………………………………………………….83

2.2.2.1.2 1-BUTTON CONTROL ………………………………………………………………………………….83

2.2.2.1.2.1 Switch………………………………………………………………………………………………83

2.2.2.1.2.2 Two Objects (Short Press/Long Press) ………………………………………………….84

2.2.2.1.2.3 Hold & Release ………………………………………………………………………………….85

2.2.2.1.2.4 Scene ……………………………………………………………………………………………….85

2.2.2.1.2.5 Constant Numerical Controls ………………………………………………………………86

2.2.2.1.2.6 Room State……………………………………………………………………………………….87

2.2.2.1.2.7 Enumeration……………………………………………………………………………………..88

2.2.2.1.3 2-BUTTON CONTROL ………………………………………………………………………………….89

2.2.2.1.3.1 Switch………………………………………………………………………………………………89

2.2.2.1.3.2 Switch + Indicator………………………………………………………………………………90

2.2.2.1.3.3 Two Objects (Short Press/Long Press) ………………………………………………….91

https://www.zennio.com

Tecnical Support: https://support.zennio.com 3

Z50 / Z70 v2 / Z100
2.2.2.1.3.4 Numerical Controls ……………………………………………………………………………92 2.2.2.1.3.5 Enumeration……………………………………………………………………………………..93 2.2.2.1.3.6 Two Scene ………………………………………………………………………………………..94 2.2.2.1.3.7 Shutter …………………………………………………………………………………………….95 2.2.2.1.3.8 Dimmer ……………………………………………………………………………………………96 2.2.2.1.3.9 Room State……………………………………………………………………………………….97 2.2.2.1.4 CLIMATE CONTROL …………………………………………………………………………………….98 2.2.2.1.4.1 Temperature Setpoint………………………………………………………………………..98 2.2.2.1.4.2 Mode ……………………………………………………………………………………………..100 2.2.2.1.4.3 Fan Control……………………………………………………………………………………..102 2.2.2.1.4.4 Special Mode…………………………………………………………………………………..105 2.2.2.1.5 OTHER…………………………………………………………………………………………………….106 2.2.2.1.5.1 RGB Control…………………………………………………………………………………….106 2.2.2.1.5.2 RGBW Control …………………………………………………………………………………108 2.2.2.1.5.3 Page Direct Link……………………………………………………………………………….109 2.2.2.1.5.4 Alarm……………………………………………………………………………………………..109 2.2.2.1.5.5 Video Intercom………………………………………………………………………………..111 2.2.2.1.5.6 Internal Call …………………………………………………………………………………….112 2.2.2.1.5.7 Chronothermostat …………………………………………………………………………..114 2.2.2.1.5.8 Scheduler ……………………………………………………………………………………….116 2.2.2.1.5.9 Macro …………………………………………………………………………………………….116 2.2.2.1.5.10 Timer ……………………………………………………………………………………………..119
2.3 Inputs…………………………………………………………………………………………………………. 123 2.3.1 Binary Input ……………………………………………………………………………………………….. 123 2.3.2 Temperature Probe …………………………………………………………………………………….. 123 2.3.3 Motion Detector…………………………………………………………………………………………. 123
2.4 Thermostat n ………………………………………………………………………………………………. 124 ANNEX I. Video Intercom Operation …………………………………………………………………………….. 125 ANNEX II. Internal Call Operation…………………………………………………………………………………. 130 ANNEX III. Remote Control via IP …………………………………………………………………………………. 135 ANNEX IV. Graphs………………………………………………………………………………………………………. 139 ANNEX V. Differences with Z50 / Z100………………………………………………………………………….. 143 ANNEX VI. Communication Objects ……………………………………………………………………………… 145

https://www.zennio.com

Tecnical Support: https://support.zennio.com 4

DOCUMENT UPDATES

Z50 / Z70 v2 / Z100

Version

Changes

Changes in the application program:

[3.6]_a

· New devices: Z50 y Z100

Changes in the application program:

[3.5]_a

· New control: timer. · Graphs functionality is added.

· RGBW control with independent objects.

Changes in the application program:

[3.4]_a

· New control: Macros. · Rename of the control Timer to Scheduler.

· Optimisation of Temp probe module.

· Changes in the application program:

· New monochromatic icons.

· Schedulers functionality is added

· New IP address management

[3.3]_a

· The number of configurable controls has been increased to 180.
· Shutter control: New object for precise control. Only used by schedulers.

· Dimmer control: New object for precise control. Only used by schedulers.

· The chronothermostat enable control and its status indicator are unified.

· Optimisation of Thermostat module.

Changes in the application program:

[3.1]_a

· New parameter to enable/disable temperature probe. · Screensaver

Page(s)


https://www.zennio.com

Tecnical Support: https://support.zennio.com 5

Z50 / Z70 v2 / Z100

· Automatic Page Shaping

· The “title” field of the controls is added to the prefix of their communication objects.

· New 4-bytes numerical indicators and text indicator.

· Chronothermostat.

Changes in the application program:

[3.0]_a · Date/time synchronisation via NTP

· Remote control of the device

https://www.zennio.com

Tecnical Support: https://support.zennio.com 6

1 INTRODUCTION

Z50 / Z70 v2 / Z100

1.1 Z50 / Z70 V2 / Z100

Z50, Z70 v2 and Z100 are the easily and intuitively controllable high- performance colour touch screens from Zennio. The built-in features and functions make them the ideal solution for integral room control in hotels, offices or any other environments where controlling climate systems, lighting systems, shutters, scenes, etc. is required.

The most outstanding features of these screens are:
5-inch, 7-inch and 10-inch backlit capacitive touch panel, with 16 million colour LCD Display and screen resolution of 480 x 854 pixels (Z50) and 1280 x 800 pixels (Z70 v2 and Z100).
Multiple direct-action functions, fully customisable.
Control distribution across up to 12 customisable pages + 1 configuration page.

Possibility to parameterise boxes of different sizes.

Customised icons.

Full climate management. Scene control. Alarm control. Light/Dark theme.

Screensaver.

Chronothermostat.

Direct links to other pages.

Locale and language configuration.

2 independent thermostats.

https://www.zennio.com

Tecnical Support: https://support.zennio.com 7

Z50 / Z70 v2 / Z100
Built-in temperature sensor Ambient luminosity sensor for brightness automatic adjustment. Proximity sensor for quick start. Buzzer for an audible acknowledgement of user actions (with the possibility of disabling it either by parameter or by object). Possibility of locking / unlocking the touch panel through binary orders or scenes, and setting a timed/automatic locking of the device (cleaning function). Pop-ups and Welcome Back object (binary or scene). Celsius and Fahrenheit scales for the on-screen temperature indicators, being possible to select them in parameters or through communication object. 4 customisable analogue-digital inputs (2 in the case of Z50). Heartbeat or periodic “still-alive” notification. Elegant design, available in various colours. Possibility of scheduling actions. Macros. Graphs associated with controls. There are also additional functionalities that require the use of a license in order to operate: Video Intercom compatible with GetFace IP. Internal Calls between different Z50, Z70 v2 or Z100 (also compatible with Z41 COM). Remote control from a mobile device. Voice Control.

https://www.zennio.com

Tecnical Support: https://support.zennio.com 8

Z50 / Z70 v2 / Z100
This manual is focused on the features of Z70 v2, most of which are shared with the Z50 and Z100. ANNEX V. DIFFERENCES WITH Z50 / Z100 lists the main differences between them.

https://www.zennio.com

Tecnical Support: https://support.zennio.com 9

1.2 FUNCTIONALITY

Z50 / Z70 v2 / Z100

Screens application program feature the following functions:

12 General-Purpose Pages, with up to 12 Fully-Customisable Boxes each, which the integrator may configure as indicators or controls.

Indicators:

o Binary. o Enumeration. o Integer. o Percentage.

o Float. o Temperature. o Cost. o Text.

1-Button Controls:
o Switch.

o Scene.

o Two Object (Short Press/Long Press).

o Constant (Counter / Scaling / Float).

o Hold & Release.

o Room State.

o Enumeration.

2-Button Controls:
o Switch.

o Float.

o Switch + Indicator (Counter / Scaling / Float / Temperature)
o Two Object (Short Press/Long Press).
o Counter. o Scaling.

o Enumeration. o Two Scenes. o Shutter. o Dimmer.
o Room State.

Climate Specific Controls:

o Temperature Setpoint control. o Mode.

o Special modes. o Fan.

Other Controls:

o RGB Control. o RGBW Control. o Page Direct Link. o Chronothermostat. o Macro.

o Alarm. o Video Intercom (License required). o Internal Calls (License required). o Scheduler. o Timer

https://www.zennio.com

Tecnical Support: https://support.zennio.com 10

Z50 / Z70 v2 / Z100
1 Configuration Page (optional), which contains the time/date settings, the calibration of the built-in temperature probe, and the brightness and doorbell volume and tone adjustment, among others.
1.3 INSTALLATION
shows the connection outline of Z70 v2 (For Z50 and Z100, please refer to the ANNEX V. DIFFERENCES WITH Z50 / Z100):

1. Touch screen.

1

2. Luminosity and proximity sensor.

3. Inputs connector.

4. Power supply.

5. Prog./Test button.

6. Prog./Test LED.

7. KNX connector.

8. Micro-USB connector.

9. Ethernet connector.

2

10. Temperature probe.

8

11. Loudspeakers.

9

12. Microphone.

10

Figure 1 Schematic diagram (Z50)

11 3 4
12 5 67

https://www.zennio.com

Tecnical Support: https://support.zennio.com 11

Z50 / Z70 v2 / Z100

1. Touch screen. 2. Luminosity and proximity sensor. 3. Inputs connector. 4. Power supply. 5. Prog./Test button. 6. Prog./Test LED. 7. KNX connector. 8. Micro-USB connector. 9. Ethernet connector. 10. Temperature probe. 11. Loudspeakers. 12. Microphone.

2 1
9

8

3 7 Figure 2 Schematic diagram (Z50)

1 1. Touch screen.

2. Luminosity and proximity sensor.

3. Inputs connector.

4. Power supply.

5. Prog./Test button.

6. Prog./Test LED.

7. KNX connector.

8. Micro-USB connector.

9. Ethernet connector.

2

10. Temperature probe.

11. Loudspeakers.

12. Microphone.

8 9
5 6

11
10 12 4 5 6
10
11 12
3 4
7

Figure 3 Schematic diagram (Z100)
The screens are connected to the KNX bus through the built-in terminal (7). An external DC power supply (24V / 29V) which delivers at least 200 mA of current is also required. The KNX power and the external power must be provided by separate supplies, in order

https://www.zennio.com

Tecnical Support: https://support.zennio.com 12

Z50 / Z70 v2 / Z100
to avoid interference to the KNX bus. This external power must be supplied to the device through the corresponding terminal (4) provided within the original packaging.
Note: although the device will not turn functional until it is powered with the external supply, the KNX bus power should be enough to perform downloads from ETS (application program, group addresses, etc.).
A short press on the Prog./Test button (5) will make the device enter the programming mode. The Prog./Test LED (6) will then light in red. On the contrary, if this button is held while the device gets connected to the bus, Z70 v2 will enter the safe mode. In such case, the programming LED will blink in red colour.
Firmware updates (see section 2.1.11) can be performed through the Micro-USB (8) connector. It is important to take into account that USB memories must be formatted in FAT32.
For detailed information about the technical features of Z50 / Z70 v2 / Z100, as well as on security and installation procedures, please refer to the device Datasheet, bundled within the device packaging and also available at www.zennio.com.

https://www.zennio.com

Tecnical Support: https://support.zennio.com 13

Z50 / Z70 v2 / Z100
1.4 START-UP
1.4.1 EULA
After the first start-up of the device, a dialog with the text EULA (End User License Agreement) will be displayed. The legal conditions of use described in EULA must be accepted by the end user before using the screen, so during the installation must be postponed. Once postponed, the EULA dialog will be displayed again after two hours or after a power failure. As long as the EULA is not accepted or postponed, screen navigation is not allowed. If the terms of use change, a dialog with the new text EULA to be accepted will be displayed on the screen.

https://www.zennio.com

Tecnical Support: https://support.zennio.com 14

2 CONFIGURATION

Z50 / Z70 v2 / Z100

After importing the corresponding database in ETS and adding the device into the topology of the desired project, the configuration process begins by entering the Parameters tab of the device.

2.1 GENERAL
This tab is divided into multiple screens, all of which contain a set of global parameters regarding the general functionality of the device, and therefore not specifically related to a particular page of the user interface.
2.1.1 CONFIGURATION
The “Configuration” tab contains general settings. Most are checkboxes for enabling/disabling other functionalities. ETS PARAMETERISATION

https://www.zennio.com

Figure 4. General. Configuration
Tecnical Support: https://support.zennio.com 15

Z50 / Z70 v2 / Z100
The following parameters are shown:
Inputs [disabled/enabled]1: enables or disables the “Inputs” tab in the tree on the left, depending on whether the device will or will not be connected any external accessories. For more information, see section 2.3.
Thermostats [disabled/enabled]: enables or disables the “Thermostat” tab in the tree on the left. For more information, see section 2.4.
Heartbeat (Periodic Alive Notification) [disabled/enabled]: incorporates a onebit object to the project (“[Heartbeat] Object to Send `1′”) that will be sent periodically with value “1” to notify that the device is still working (still alive).

Figure 5. Heartbeat
Note: the first sending after download or bus failure takes place with a delay of up to 255 seconds, to prevent bus overload. The following sendings match the period set.
Internal Probe [disabled/enabled]: enables the internal temperature probe of the device.
Default Theme (After Download) [Light / Dark]: enables choosing the device theme after download.
Icons Type [Colourful / Monochromatic]: enables to choose whether the set of icons will be displayed in color or grayscale.
Note: even if the monochrome option is chosen, some icons will still keep the colour, such as RGB or some pop-up icons.

1 The default values of each parameter will be highlighted in blue in this document, as follows: [default/rest of options].

https://www.zennio.com

Tecnical Support: https://support.zennio.com 16

Z50 / Z70 v2 / Z100
Show Time [disabled/enabled]: permits setting whether the current time is displayed in the upper-left corner of any page or not.
Important: the time will not be displayed on the top bar until both a time and a valid date have been set.
Show Temperature [No / Internal Temperature Probe/ External Value]: sets whether the current temperature should show or not in the upper right corner of every page. If “External Value” is chosen, an object named “[General] External Temperature” will be enabled, so that it can be grouped with any other object that sends temperature values.
Enables to choose whether the source of the current temperature measurement will be an “External value” or the value provided by the “Internal temperature probe”.
Synchronize Clock Master via NTP [disabled/enabled]: if enabled, the device will update the date and time obtained from the NTP server according to the configured time zone. In addition, the following parameters will be displayed:
Time Zone: drop-down list to select a time zone from the UTC (Coordinated Universal Time) time standard.
· Daylight Saving Time (DST) [disabled] / [disabled/enabled]: enables or disables the automatic time change during the summer season. It will only be available in the time zones that have summer time changeover.
Domain of NTP Server [0.pool.ntp.org]: NTP server used for internal clock synchronisation.
Date and Time Periodical Sending [0 … 10 … 65535] [x 1min]: time period after which the date and time objects (“[General] Date” and “[General] Time of Day”) will be sent to the bus.
If the parameter Synchronize Clock Master via NTP is disabled, the following parameter is displayed:
Date and Time Update Request Delay [disabled/enabled]: allows selecting a delay [1…65535] [s/min/h] for the date and time request to the

https://www.zennio.com

Tecnical Support: https://support.zennio.com 17

Z50 / Z70 v2 / Z100
bus. These requests will be made after updating the firmware or after power failure.
Update Objects: enables the sending of read requests to update status objects and indicators. There are four options available, some of them with a configurable delay:
[Disabled]: no read request, therefore objects are not updated.
[After Programming]: read requests are sent after a complete or partial download (or when pressing the reset button in the configuration page, if set as “Parameters Reset”, see section 2.2.1.2.1).
[After Reset]: read request are sent when a reset occurs (bus failure, the Reset Device ETS option or when pressing the reset button in the configuration page, if set as “Application Reboot”, see section 2.2.1.2.1), after the parameterised delay [0…10…65535] [s/min/h].
[After Programming and Reset]: combination of the two above options.
Bus Fail Notification Message [disabled/enabled]: enables an informative message to be displayed on the screen with each press during a bus failure.
Message [Bus Fail]: textbox to enter the desired message.

Figure 6. Bus Fail Message
Screensaver [disabled/enabled] / [disabled]: enables the screensaver. This parameter is only available if the internal temperature sensor is disabled. See section 2.1.6.

https://www.zennio.com

Tecnical Support: https://support.zennio.com 18

Z50 / Z70 v2 / Z100
Time to Consider Inactivity: time that must elapse since the last press and/or proximity detection to consider inactivity state. Then the display backlight will dim. See section 2.1.3.
With internal probe enabled: [[30…65535] [s] / [1…65535] [min/h]] With internal probe disabled: [[30…600] [s] / [1…10] [min]] Schedulers [disabled/enabled]: enables schedulers functionality. When enabled, a new tab is added in the tree on the left. See section 2.1.5
Proximity Sensor [disabled/enabled]: enables the proximity sensor. This functionality permits “waking up” the device display when detecting presence through the proximity sensor
Please refer to the user manual “Proximity and Luminosity Sensor” (available in the Z70 v2 product section at the Zennio homepage, www.zennio.com) for detailed information about the functionality and the configuration of the related parameters.
Note: After programming or resetting the device, 1 minute is required to carry out the sensors calibration. To achieve a correct calibration, during this time, keeping a distance of more than 50 cm from the sensors and avoiding light falling directly on them is recommended.
Ambient Luminosity Sensor [disabled/enabled]: enables or disables the ambient luminosity sensor. When enabled, a new tab is added in the tree on the left (see section 2.1.8).
Touch Locking [disabled/enabled]: enables or disables the possibility of locking the touch by object. When enabled, a new tab is added in the tree on the left (see section 2.1.9).
Sounds [Default / Custom]: sets whether the sound functions (button beeps and doorbell) should work according to the pre-defined configuration (“Default”) or to a user-defined configuration (“Custom”) (see section 2.1.9).
Enable Web Configuration [disabled/enabled]: enables or disables access to “Webserver Tools”, from which certain configuration and monitoring actions can be performed on Z70 v2.

https://www.zennio.com

Tecnical Support: https://support.zennio.com 19

Z50 / Z70 v2 / Z100
Allow Password Reset [disabled/enabled]: enables the password for accessing the Web server to be set to the factory default.
Please refer to the user manual “Webserver Tools” (available in the Z70 v2 product section at the Zennio homepage, www.zennio.com) for detailed information about its functionality and the configuration.
Note: in the event of a supply failure, the connection with the server will be lost, and waiting for the screen to recover its generic IP to access it again will be necessary.
Remote Control through the Internet [disabled/enabled] (license required): enables or disables remote control function (see ANNEX III. Remote Control via IP).
Pairing Code Expiration Time [60 … 120 … 3600]: sets the time that pairing code will be valid. Advanced Configuration [disabled/enabled]: enables or disables the “Advanced” tab in the tree on the left (see section 2.1.14).
The project topology shows the following objects by default:
“[General] Time of Day”: 3-byte object for setting the internal time of the device, for example, by linking it to a KNX clock. This object is also automatically sent after time changes made by the user from the screen itself.
Note: although the DPT of this object considers a field for setting the day of the week, Z70 v2 calculates it from the date and therefore ignores that field.
Important: Z70 v2 does not have an RTC clock or battery to keep track of the time in the absence of power. Therefore, it is important to receive the time periodically from a device that obtains it through NTP and/or has a battery to prevent delays during bus failures.
“[General] Date”: 3-byte object for setting the internal date of the device, for example, by linking it to a KNX clock. This object is also automatically sent after date changes made by the user from the screen itself.
“[General] Scene: Send” and “[General] Scene: Receive”: objects for respectively sending and receiving scene values from/to the KNX bus whenever it is necessary.

https://www.zennio.com

Tecnical Support: https://support.zennio.com 20

Z50 / Z70 v2 / Z100
“[General] Activity”: 1-bit object to force activity/inactivity state on the device. For further information, please refer to the user manual “Proximity and Luminosity Sensor” and “Brightness” (available in the Z70 v2 product section at the Zennio homepage, www.zennio.com).
“[General] Localization ­ Select” and “[General] Translations ­ Select”: 4-byte and 2-bytes objects to change, respectively, the locale and the language in the screen (see section 2.1.2).
“[Profile] Theme”: 1-byte object to change the theme used in the screen.
“[Profile] Volume”: 1-byte percentage object to change the volume at which the user sounds of device will be emitted.
“[C001][] Switch Indicator”: object associated with Control 1 enabled by default.
“[Profile] Display ­ Brightness”: 1-byte percentage object to change the display brightness level.
“[General] Proximity Sensor”, “[General] External Proximity Detection” and “[General] Proximity Detection”: 1-bit object whose functionality is tied to the proximity sensor. For further information, please refer to the user manual “Proximity and Luminosity Sensor” (available in the Z70 v2 product section at the Zennio homepage, www.zennio.com).
“[Internal Temp. Probe] Current Temperature” (only in Z70 v2): 2-byte object through which the value of the current measurement of the built-in sensor will be sent to the bus, according to the parameterisation (see section 2.1.7).
2.1.2 LOCALE
The locale consists of a language and region identifier, which will determine the language and how certain visual aspects of the device are displayed, such as:
The temperature scale: Celsius or Fahrenheit. Time format: 12 or 24 hours. Date format: dd-mm-yyyy, mm-dd-yyy o yyyy-mm-dd.

https://www.zennio.com

Tecnical Support: https://support.zennio.com 21

Z50 / Z70 v2 / Z100
Use of a point (.) or a comma (,) for decimal separation (except in temperature that will always be shown with a point as separator). Position of the currency symbol in cost indicators. Language of all the texts shown on the screen.
Example 1: Locale: es-ES Language: Spanish ­ Region: Spain.

Figure 7. Locale es-ES
Example 2: Locale: en-US Language: English ­ Region: USA.

Figure 8. Locale en-US
The locale configuration can be selected through three types of communication objects:
A 1-byte object. Enumerated to select the locale and the language from any of the configured in ETS.
A 2-bytes object. Allows changing the language without affecting the region.
A 4-bytes object. Allows changing the locale and the language by sending a language-region pair of values.
Note: if a language change is made while a pop-up is open, this change will not take effect until the pop-up is closed.
Please refer to section 2.1.11.3 for detailed information about the process of importing and exporting language translation files.

https://www.zennio.com

Tecnical Support: https://support.zennio.com 22

ETS PARAMETERISATION

Z50 / Z70 v2 / Z100

Figure 9. Locale
Main Locale [enabled]: read-only parameter to make it evident that the main locale is always enabled. Select Locale: list of the available locales. Locale X [disabled/enabled]: enables the additional locale X. Select Locale: list of the available locales.
The language and locale are changed via the following communication objects:
1-byte object “[General] Localization – Select”. To select the locale and the language from any of the configured in ETS. The expected values in this object are fixed, from 0 to 4. When one of
these values is received, the texts of the file `text_language-region.xlf’ corresponding to the regional configuration associated with this value will be loaded. If the received value does not correspond to any enabled locale, the main locale will be loaded.
Note: this object is only available if more than one locale is enabled in ETS.
4-bytes object “[General] Localization – Select”.
The values expected by this object are four characters, language-region pair, corresponding to ISO 639-1 and 3166-1 respectively.
When a valid language-region code is received, the texts from the ‘text_language-region.xlf’ file and the indicated region will be loaded. In case there is not that file, the main locale configuration will be loaded. If the region does not correspond to the language or it is not valid, the default

https://www.zennio.com

Tecnical Support: https://support.zennio.com 23

Z50 / Z70 v2 / Z100
region associated with that language will be set (and the language file ‘text_language-ZZ.xlf’, if it exists).
2-bytes object “[General] Translations – Select”. To change the Language without affecting the region.
The values expected by this object are the language code corresponding to ISO 639-1.
When a valid language code is received, the texts from the ‘text_languageZZ.xlf’ file will be loaded. In case there is not that file, the language of the main locale configuration (texts from ETS) will be loaded.
Example:
Imported files: text_es-ES.xlf’,text_es-ZZ.xlf’ y text_es-AR.xlf’. ETS Parameterization: Main Locale: en-GB Locale 2: es-AR Locale 3: fr-FR 1-byte object: 1 Language: text_es-AR.xlf’ ­ Region: Argentina. 1-byte object: 2 Language: dflt.xlf’ (ETS texts) ­ Region: Great Britain. 1-byte object: 4 Language: dflt.xlf’ (ETS texts)­ Region: Great Britain. 2-byte object: en Language:dflt.xlf’ (ETS texts) ­ Region: No change. 2-byte object: es Language: text_es-ZZ.xlf’ ­ Region: No change. 2-byte object: fr Language:dflt.xlf’ (ETS texts) ­ Region: No change. 4-byte object: es-ES Language: text_es-ES.xlf’ ­ Region: Spain 4-byte object: es-AR Language:text_es-AR.xlf’ ­ Region: Argentina 4-byte object: fr-FR Language: dflt.xlf’ (ETS texts) ­ Region: Great Britain. 4-byte object: es-VE Language:dflt.xlf’ (ETS texts) ­ Region: Great Britain 4-byte object: es-aa Language: `text_es-ZZ.xlf’ ­ Region: Spain
Note: For further information about the process of importing and exporting translation files into the different languages, see section 2.1.11.3.
Object to change the temperature scale [disabled/enabled]: enables or disables the 1-bit object “[General] Temperature scale”, which permits

https://www.zennio.com

Tecnical Support: https://support.zennio.com 24

Z50 / Z70 v2 / Z100
changing the scale of the temperatures. By receiving one 0′ through this object, the scale will switch to Celsius, while after receiving one1′ it will switch to Fahrenheit.
The selected scale applies to any temperatures shown on the screen and takes precedence over the scale corresponding to the locale.
2.1.3 BACKLIGHT
Z70 v2 enables managing the brightness of the display according to two operating modes: normal mode and night mode.
Note: Contrast is not a configurable feature in the device.
Please refer to the specific manual “Brightness” (available in the Z70 v2 product section at the Zennio website, www.zennio.com) for detailed information about the functionality and the configuration of the related parameters.
2.1.4 SECURITY
Any box or page will be given the possibility of restricted access by password. Up to two security levels can be configured, with the level 2 access password taking priority over the level 1 password, so that any controls page or box can be protected by one or the other, or by none at all.
Buttons that lead to a protected page or box will show a little lock icon overlaid on their lower right corner.
Figure 10 shows the “enter password” dialog shown to the user when trying to access a protected page.

https://www.zennio.com

Tecnical Support: https://support.zennio.com 25

Z50 / Z70 v2 / Z100
Figure 10. Security pop-up
In case of setting up two levels, the first one is assumed to be enclosed by the second one. This means that whenever the device asks the user to type password #1 (to enter a certain item); password #2 will also be accepted. On the contrary, password #1 cannot be used instead of password #2. This behaviour permits, therefore, making password #2 available to users with further privileges while password #1 is assigned to users with fewer privileges. Moreover, when accessing to a protected page, all the boxes and pages with the same or lower access level of the introduced password, are automatically unlocked. It can be set if the elements are relocked after pressing the Home Button. Anyway, security is reactivated when the time for considering inactivity expires. ETS PARAMETERISATION This screen permits selecting how many security levels (one or two) will be available for the configuration of the access to the control pages or the boxes.

https://www.zennio.com

Figure 11. Security
Tecnical Support: https://support.zennio.com 26

Z50 / Z70 v2 / Z100
Security Levels [One Level / Two Levels]: parameter for selecting whether one or two security levels will be available.
Note: with independence of the option selected here, it will be necessary to establish the security level desired for each specific page of controls.
Protect Again after Home Button is Pressed [disabled/enabled]: if enabled, the security of the boxes and/or pages will be restored when the Home Button is pressed.
Password [Level 1: 1234; Level 2: 5678]: parameter made of four additional textboxes, each of which should contain one of the four consecutive digits [0…9] that will compose the password. In case of enabling two security levels, the Password parameter will show twice, being the first one referred to the password of Level 1, and the second one to the password of Level 2.

Figure 12. Two security levels
Important: the password insertion dialog features a specific option (lower left button) that lets the user change, in runtime, the passwords originally set by parameter. After accessing this option and prior to typing the new password, the text box will be set with an orange background and the user will be required to type the corresponding old password (level 1 or level 2). Note that although it will be possible to type password 2 even if the device asks for password 1, the new password typed afterwards will be anyway stored as the new password for level 1.
Security Pad Labels: parameter consisting in six additional textboxes, intended for the customisation of the messages that the device shows (or may show) when the user interacts with the password insertion dialog.
Password 1 [Enter Password 1]: message shown when the user is required to type in the password for level 1.

https://www.zennio.com

Tecnical Support: https://support.zennio.com 27

Z50 / Z70 v2 / Z100
Password 2 [Enter Password 2]: message shown when the user is required to type in the password for level 2.
Error [ERROR]: message shown to the user when the typed password is not valid.
New Password [New Password]: message shown to ask the user for a new password, during the password change process.
Repeat Password [Repeat Password]: message shown when the user is required to re-type the new password.
Password Updated [Updated]: message shown to the user as a confirmation of the password change.

2.1.5 SCHEDULERS

Z70 v2 offers the possibility to enable up to 30 schedulers, within which the execution of up to 30 timed sending actions to the KNX bus can be configured.

Timed actions are performed on the programmable controls that have been configured in the device:

1-Button Controls:
Switch. Scene Two Object (Short Press/Long
Press2).

Hold & Release. Enumeration. Constant (Counter / Scaling / Float).

2-Button Controls:
Switch. Two Object (Short Press/Long
Press2). Counter. Scaling.

Float. Enumeration. Shutter. Dimmer.

Climate Specific Controls: Temperature Setpoint control. Mode.

Special modes. Fan.

2 In the case of two-object controls (Short Press/Long Press), the schedulers only take into account the short press value.

https://www.zennio.com

Tecnical Support: https://support.zennio.com 28

Z50 / Z70 v2 / Z100

Other Controls: RGB Control. Macro.

RGBW Control.

To adjust the scheduler configuration settings, access the configuration panel from any of the boxes that have been parameterised as “scheduler” type (see section 2.2.2.1.5.8). From this panel navigation to the rest of the available schedulers will be possible, each of them represented by its corresponding icon configured from ETS.

2 7

3

4

8 5
6

1

Figure 13. Schedulers panel
The scheduler panel consists of:
1 Navigation area between schedulers by means of the arrow buttons or by clicking directly on the icon of the scheduler to be displayed.
2 General enable button to enable/disable the scheduler without deleting the actions.
3 Days of the week on which the actions configured in the selected scheduler are to be executed.
4 Button to delete all the actions of the scheduler.
5 Navigation area through the scheduler actions.

https://www.zennio.com

Tecnical Support: https://support.zennio.com 29

Z50 / Z70 v2 / Z100 6 Button to add a new action at the end of the list. 7 Checkbox to deactivate an action individually without deleting it.
Timed action which will show the time of execution, the page where the 8 control is located, the control to be timed and the value to be sent once the
configured time has been reached. The configuration of actions is done by entering edit mode. This happens when a new action is added or when clicking on one of the panel visible actions. Entering edit mode expands the action, showing the buttons to modify each field and a new button to delete the action, as shown in Figure 12.
Figure 14. Edit mode for scheduler actions
Saving the configured actions occurs when navigating to another scheduler or closing the panel by clicking outside the editing dialogue. Note: if Z70 v2 has any protected controls, these can only be timed if the panel is accessed with a security level equal to or higher than that of the control. Otherwise, these actions are hidden. Besides, if any action is configured with a higher security level than the current one, it will be notified with a padlock and it will not be allowed to modify the global actions of the scheduler (general enabling, days of the week and deleting all actions).

https://www.zennio.com

Tecnical Support: https://support.zennio.com 30

Z50 / Z70 v2 / Z100 ETS PARAMETERISATION After enabling Schedulers from “Configuration” screen (see section 2.1.1), a new tab will be incorporated into the tree on the left.
Figure 15. Schedulers tab
Title: text displayed at the top of the general scheduler panel. Number of Fixed Schedulers [1…30]: sets the number of schedulers available for setting on the display.
Fixed Scheduler n Icon [Clock]: selects the icon to be displayed in the navigation area for each scheduler.
2.1.6 SCREENSAVER
Z70 v2 offers the possibility to display a screensaver after a period of inactivity, configurable by parameter. The screensaver can be configured to only show the current Time, the current external Temperature or both.

https://www.zennio.com

Tecnical Support: https://support.zennio.com 31

Z50 / Z70 v2 / Z100
Figure 16. Screensaver
There will also be an option to show an image on the screensaver. This image will be loaded from the webserver. Note: Please refer to the user manual “Webserver Tools” (available in the Z70 v2 product section at the Zennio homepage, www.zennio.com) for detailed information about its functionality and the configuration. The screensaver disappears when activity is triggered (either by a pulsation, proximity detection or any other event that triggers activity). Notes:
If a Pop-Up is being displayed (see section 2.1.14.2), screensaver will not become active. If a pop-up is activated when the screensaver is active (see touch locking 2.1.9, cleaning function 2.1.14.1 or Pop-Ups 2.1.14.2) this pop- up will become show up over screensaver.

https://www.zennio.com

Tecnical Support: https://support.zennio.com 32

Z50 / Z70 v2 / Z100
ETS PARAMETERISATION After enabling Screensaver from “Configuration” screen (see section 2.1.1), a new tab will be incorporated into the tree on the left.

Figure 17. Screensaver Tab
Image [disabled]: parameter to show an image in the screensaver. For this functionality to be available, the Enable Web Configuration parameter must be active (see section 2.1.1).
Time/Date [disabled/enabled]: when this parameter is enabled, the current date and time is displayed centered on the screensaver.
External Temperature [disabled/enabled]: when this parameter is enabled, the external temperature received by the “[General] External Temperature” object is displayed centered on the screensaver.
Background Color [#000000]: color set for the background when there is no image in the screensaver.
Text Color [#FFFFFF]: screensaver font color.
2.1.7 INTERNAL TEMPERATURE SENSOR
Z70 v2 is equipped with an internal temperature sensor for monitoring the ambient temperature of the room, so that the device can report it to the KNX bus and trigger several actions when the temperature reaches certain values.
Please refer to the specific documentation of the “Temperature Probe” available at the Zennio homepage, www.zennio.com, for detailed information about the functionality and the configuration of the related parameters.

https://www.zennio.com

Tecnical Support: https://support.zennio.com 33

Z50 / Z70 v2 / Z100 Note: To ensure correct measurement of the temperature probe, when the temperature probe is enabled, the display will be permanently switched on.
2.1.8 AMBIENT LUMINOSITY SENSOR
Z70 v2 includes a sensor to measure the ambient luminosity level, so that the brightness of the display can be adjusted according to the current luminosity of the room.
Please refer to the specific manual “Luminosity and Proximity Sensor” (available in the Z70 v2 product section at the Zennio homepage, www.zennio.com) for detailed information about the functionality and the configuration of the related parameters.
2.1.9 TOUCH LOCKING
The touch panel of Z70 v2 can be optionally locked and unlocked anytime by writing a configurable one-bit value to a specific object provided for this purpose. It can also be done through scene values.
While locked an informative message will be shown. In addition, any user presses on the screen will be ignored: no action associated with controls will be carried out.

Figure 18. Touch Locked Message.
ETS PARAMETERISATION After enabling Touch Locking from “Configuration” screen (see section 2.1.1 a new tab will be incorporated into the tree on the left.

https://www.zennio.com

Tecnical Support: https://support.zennio.com 34

Z50 / Z70 v2 / Z100

Figure 19. Touch Locking.
1-Bit Object [enabled]: enables the 1-bit object “[General] Touch Locking” to trigger the touch lock.
Value [0 = Unlock, 1 = Lock / 0 = Lock, 1 = Unlock]: parameter to select which value should trigger which action when received through the indicated object.
Scene Object [disabled/enabled]: enables the touch locking and unlocking when receiving the configured scene value through the object (“[General] Scene: receive”). Lock: Scene Number (0 = Disabled) [0/1…64]: scene number that locks
the touch. Unlock: Scene Number (0 = Disabled) [0/1…64]: scene number that
unlocks the touch.
Message Notification [Touch Locked]: textbox to enter the desired message.
2.1.10 SOUNDS
Z70 v2 emits 3 types of sounds, depending on the action performed:
Press Confirmation: short beep indicating that the user has pressed a button. This only applies to step controls, i.e., controls that go through a certain range of values and that do not send a value after every touch, and to page accesses.
Sending Confirmation: a slightly longer and sharper beep than the previous one. It indicates the sending of an object to the bus as a result of a press.

https://www.zennio.com

Tecnical Support: https://support.zennio.com 35

Z50 / Z70 v2 / Z100
Doorbell: sharp and longer beep than the previous one, high intensity. The volume and ringtone of the doorbell can be chosen by parameter, object or from the screen itself.
Enabling and disabling of this function can only be done by parameter. If enabled, the volume of the press and sending confirmation sounds will be possible to define.
ETS PARAMETERISATION After enabling the “Custom” configuration of Sounds from “Configuration” screen (see section 2.1.1), a new tab will be incorporated into the tree on the left.

Figure 20. Sounds
The initial configuration of this screen is equivalent to the default option. However, the following parameters will be configurable.
Disable User Sounds [disabled/enabled]: enables or disables acoustic signals when actions derived from button presses are executed. If enabled, the following parameter will be displayed:
Default Volume (after Programming) [No Sound / 1 / 2 / 3]: volume at which press and sending confirmation sounds will be emitted after ETS download.
Object for Doorbell [disabled/enabled]: enables or disables the doorbell function. If enabled, a specific object (“[General] Doorbell”) will be included into the project topology.
Value [0 = No Action, 1 = Doorbell / 0 = Doorbell, 1 = No Action]: parameter to select which value should trigger which action when received through the indicated object.

https://www.zennio.com

Tecnical Support: https://support.zennio.com 36

Z50 / Z70 v2 / Z100 Default Ringtone (after Programming) [Ringtone 1 / … / Ringtone 7]:
desired melody for doorbell after ETS download. Default Volume (after Programming) [No sound / 1 / 2 / 3 / 4 / 5]: volume
of the doorbell sound after ETS download.
2.1.11 UPDATE SETTING
The Z70 v2 enables updates via USB of some of the available functions. These functionalities and how they should be updated are described in the following sections.
ETS PARAMETERISATION

Figure 21. Firmware Update
USB Updating [Disabled / Enabled]: enables or disables the device firmware update through the USB port. Thus, if this parameter is disabled, any action requiring the use of USB will have no effect.
Network Updating: [Disabled / Enabled / Enabled (Password Protected]: the latter brings the option to restrict the updates via Ethernet to those who can provide the required password to the update tool before the firmware download starts. This password, consisting in four numbers, needs to be set in ETS by the integrator.
Note: reading the specific user manual of the firmware update process available at the Zennio webpage is encouraged, as it contains particular remarks regarding the password protection.

https://www.zennio.com

Tecnical Support: https://support.zennio.com 37

Z50 / Z70 v2 / Z100
2.1.11.1 FIRMWARE UPDATE
For detailed information about the update process, please refer to the “Firmware update” specific document, available at www.zennio.com
Note: Firmware updates do not re-set the alarm and error logs, nor does it clear the onscreen user configuration.
Important: firmware updates via USB can be disabled in parameters (see section 2.1.11). Please bear in mind that if such possibility is left disabled and a new version of the application is downloaded before having updated the firmware to the corresponding version, then it will not be possible to re- enable it unless the application program is reverted to the version that corresponds to the current firmware version.
In other words: the device does not apply any further parameter changes in case of a version mismatch between the application program and the firmware. Therefore, it is always advisable to update the firmware (which will imply having the USB option already enabled, if necessary) prior to updating the application program.

2.1.11.2 LICENCE SETUP
Some of the functionalities available in Z70 v2 require the installation of a license for their use. If it is not pre-installed, it will be provided by Zennio in a .lic file.

Functionality Video Intercom

Licence

“Com”

“Remote” “Zenvoice”

Internal Calls

Remote control via IP

Voice control

Table 1. Functionalities associated with licenses

“All”

Note: voice control functionality is only available if the device also has remote licence installed.

To install any of the licenses, the .lic license files must be included in the root directory of a USB memory or in a folder and/or .zip file named license and z_license.zip respectively.

https://www.zennio.com

Tecnical Support: https://support.zennio.com 38

Z50 / Z70 v2 / Z100
When Z70 v2 recognizes the inserted USB flash drive, a USB icon will appear on the top bar and an informative dialogue will appear on the screen. The actions notified in the message will be, for each of the files with extension .lic detected:
License Updated: a new license has been installed.
Invalid license found: a .lic file has been detected but the information it contains is not valid.
After installing all the available licenses in the USB memory, a restart will make the licenses effective.
Additionally, licenses can also be installed on Z70 v2 through a web server utility. The installation process is described in the manual “Webserver Tools”, available in the product section of Z70 v2 in Zennio web portal, www.zennio.com.

2.1.11.3 IMPORT AND EXPORT TRANSLATIONS
The translations will be saved in .xlf files in the Z70 v2. After a download, the ETS parameterised texts will be the ones in the main language, and it will be overwritten.
Other languages files will have to be generated externally and, afterwards, uploaded to the Z70 v2. For this purpose, it will be possible to export and import languages via USB (with the exception of translations from the main language, which shall always correspond to the text of ETS):
Export: it must be created an empty folder named “lang_export” on the root directory of a pen drive and connect it to the Z70 v2. When the Z70 v2 detects the inserted USB flash drive, a USB icon appears in the top bar and an information dialog appears on the screen. The action notified in the message will be:
Translations exported: a copy of all the translation files of the device has been generated in this folder, including the file “text_dflt.xlf”, which will contain the parameterised texts in ETS.
Import: it must be created another folder named “lang_import” containing the files with extension
.xlf of the desired languages to incorporate. The files names should follow the nomenclature “text_language-region.xlf”, where “language” must be the two letters code that correspond to the language and “locale” the two letters code associated to the region.

https://www.zennio.com

Tecnical Support: https://support.zennio.com 39

Z50 / Z70 v2 / Z100
For example, “text_en-GB.xlf” would be the language corresponding to English and United Kingdom locale. A generic translation file can also be generated for a language that is not associated with a particular locale. To do this, it is necessary to follow the nomenclature “text_language-ZZ.xlf”.
Once the translations are finished, plug in the USB to the Z70 v2 and, when the Z70 v2 detects the inserted USB flash drive, a USB icon appears in the top bar and an information dialog appears:
New translations imported: a copy of all translation files stored in the “lang_import” folder has been generated in Z70 v2.
Important: if the language change is done using the 2-byte object, the translation files must follow the nomenclature “text_language-ZZ.xlf”. If the 1-byte or 4-byte objects are used for the language change, the translation files must follow the nomenclature “text_language-region.xlf”.
Notes:
The finalization of the import and export of the translation files will be notified by a message on the Z70 v2 screen.
The USB memories must be formatted in FAT32.
After a download, the .xlf file for the main language is overwritten, but not for the other languages.
Translations files should not include the characters <‘,’>’ or&’. If someone wants to use these characters must use their equivalent valid representation: &lt;’,>’ y `&’, respectively.
The characters that can be displayed on the screen correspond to the alphabets supported by the “Noto” font.
For texts translations, it is recommended to use a translation management tool such as OLT (Open Language Tool), to facilitate the translation process with
.xlf files.

https://www.zennio.com

Tecnical Support: https://support.zennio.com 40

Z50 / Z70 v2 / Z100 2.1.11.4 CUSTOM ICONS Z70 v2 enables to import customised icons. These icons are parameterised from ETS and will appear with the name “Cx” (see sections 2.2.1.3 and 2.2.2.1). In order to display them correctly on the screen, importing all these icons using a USB with FAT32 format is necessary. To do this, a folder named “icons” must be created in the root directory of the USB, which in turn will have a certain folder structure depending on whether or not different icon sets for each theme wants to be differentiated:
Without differentiating theme: in this case the imported icons will be common for both light and dark theme. The structure of the folders must be as follows:
Figure 22. Custom icons (common). Root folder structure.
Differentiating theme: the custom icons will be differentiated between those generated for the light theme (folder “light”) and those generated for the dark theme (folder “dark”). The structure of the folders must be as follows:

Figure 23. Custom icons (light and dark theme). Root folder structure.
Both structures will have other folders in which the custom icons will be saved with the name “custom_icon_1.svg”, “custom_icon_2.svg”, etc.:
Button: icons for the boxes buttons (maximum 15 customised icons).

https://www.zennio.com

Tecnical Support: https://support.zennio.com 41

Z50 / Z70 v2 / Z100 Link: icons for direct link boxes or pages (maximum 40 customised icons).
Status: icons for box indicators (maximum 40 customised icons).
Notes: The maximum size of the icons cannot exceed 20KB. If the name or the format of any of the files is not correct, it will not be imported. Custom icons do not modify when Icons type parameter is set as [Monochromatic] After completing the above steps and connecting the USB to the Z70 v2, as soon as the Z70 v2 identifies the inserted USB flash drive, a USB icon will appear in the top bar and a dialog will inform the user of the action on screen: “New icons imported”.
Recommendations to generate customised icons
When designing and generating custom icons, it is recommended to take into account the following indications to ensure their correct display in Z70 v2:
The viewbox of each of the SVG files should be square (aspect ratio 1:1).
When exporting the icons: Check the “Convert to outlines” option in the font options. Set the number of decimals to 3. Check the “Responsive” option.
Figure 24 shows an example of the options in Illustrator.

https://www.zennio.com

Tecnical Support: https://support.zennio.com 42

Z50 / Z70 v2 / Z100

Figure 24. Configuration to export icon in Illustrator.
2.1.12 IP CONFIGURATION
Z70 v2 is able to communicate with other external (GetFace IP) or internal (Z41 COM o Z70 v2) units via Ethernet connection. Such communications will require correct configuration of certain general IP parameters.
ETS PARAMETERISATION

Figure 25. IP Configuration

Device Description: assigns a name to the device.

IP Address Assignment [DHCP / Static]: selects whether the IP is set by the DHCP protocol or is defined in a static way. If the Static option is chosen, the following parameters will be displayed:

IP Address [192.168.1.101]: is used to uniquely identify the Z70 v2 for functionalities such as Webserver, connection to the display via internet, obtaining the time via NTP or VoIP. Therefore, it is the IP address that will

https://www.zennio.com

Tecnical Support: https://support.zennio.com 43

Z50 / Z70 v2 / Z100
be indicated to access Webserver Tools, on the outdoor unit (GetFace IP) or on a contact of another display to make an internal call.
Note: it is recommended to set this IP address out of the range of addresses assigned by the home router to prevent possible conflicts with the IP address visible to the internet.
Subnet Mask [255.255.255.0]: must match the mask of the network to which Z70 v2.
Specify Gateway [disabled/enabled]: when enabled permits introduce a gateway [192.168.1.1].
Primary DNS [8.8.8.8]: Maintains the authoritative information of a domain name, obtained from its own configuration.
Secondary DNS [8.8.4.4]: copies its configuration from the primary

Figure 26. IP Configuration with VoIP enabled on same network
VoIP [disabled/enabled]: If enabled, allows communication with external (GetFace IP) or internal (Z41 COM or other Z70 v2) units.
Different network [disabled/enabled]: Allows to select whether the network for the VoIP functionality is on a different network than the device. When enabled, the following parameters are displayed:

https://www.zennio.com

Tecnical Support: https://support.zennio.com 44

· IP Address [192.168.1.100].

Z50 / Z70 v2 / Z100

· Subnet Mask [255.255.255.255.0].

· Specify Gateway [Disabled/Enabled]: Enabling this allows you to enter a gateway [192.168.1.1]. This only needs to be enabled if the Z70 v2 is on a different network to the other units it is communicating with.

Note: If VoIP functionality is enabled, 2 scenarios are possible:
Same network: The IP assignment can only be static, and the IP will be the same for both the device (the one used for Webserver, remote functionality, or setting the time via NTP), and the VoIP functionality.

Different network: The IP assignment for the display can be either DHCP or static:

· DHCP: In this case the IP of the display will be assigned via the DCHP protocol, while the IP for the VoIP functionality will be defined by the user statically.

· Static: Both the IP assignment for the display and for the VoIP functionality will be statically assigned (although they will be different), with the user defining all the parameters.

Figure 27. IP Configuration with VoIP enabled on different network

https://www.zennio.com

Tecnical Support: https://support.zennio.com 45

Z50 / Z70 v2 / Z100
2.1.13 VOIP CALLS (LICENSE REQUIRED)
Note: VoIP calls functionality requires a license installation. If not, even being possible to configure it from ETS, its use will not be accessible
Z70 v2 is capable of receiving, over its Ethernet connection, voice and video calls from:
A Zennio indoor unit: Z41 COM or Z70 v2. These calls are referred in this document as internal calls.
A Zennio outdoor unit: GetFace IP. These calls are referred in this document as video intercom calls.
The same GetFace IP outdoor unit can call more than one Z70 v2 at the same time. For that purpose, the different Z70 v2 must be synchronized and connected to the same network. The synchronization will allow actions performed on one of the screens to be notified to the others.
ETS PARAMETERISATION

Figure 28. VoIP Calls
My ID [MY_ID]: identification code of the Z70 v2 required to communicate with other devices.
Note: the characters included in this field must comply RFC 2396 standard.
Video Intercom [disabled/enabled]: enables or disables “Video Intercom” tab for the configuration of external video intercom (GetFace IP). See section 2.1.13.1 for more details.

https://www.zennio.com

Tecnical Support: https://support.zennio.com 46

Z50 / Z70 v2 / Z100
Internal Calls [disabled/enabled]: enables or disables “Internal Call” tab for the configuration of internal calls to other devices (Z41 COM or Z70 v2). See section 2.1.13.2 for more details.
If any of the above parameters are enabled, the following will appear:
Default Ring Volume (after Programming) [No sound / 1 / 2 / 3 / 4 / 5]: define the VoIP calls volume after Programming.
Synchronize with other Devices in the Same Network [disabled/enabled]: enables the device to share the call status and history with all other units connected to the same network that have this functionality enabled. Then the following parameter will also appear:
Synchronization Password: field that must match in all the devices to synchronise.
Note: Synchronisation with other devices is only available for Z70 v2. If there is a Z41 COM in a system, synchronisation will not be performed.
In addition, when the parameters Video Intercom and/or Internal Calls are enabled, the following objects will appear:
“[VoIP] “Do Not Disturb” Mode”: 1-bit object that enables and disables the do not disturb mode of the Z70 v2 VoIP functionality. While this mode is active, Z70 v2 will not receive any incoming calls, but the calls will be recorded in the log.
“[VoIP] Video Intercom Ringtone” or “[VoIP] Internal Call Ringtone”: 1-byte object to change the video intercom or internal call ringtone.
“[VoIP] Ringtone Volume”: object to change the volume of the incomming calls ringtone.
“[VoIP] Active Call”: this object is sent to the bus (with value 1′) when a call starts and (with value0′) ends, indicating whether the call is active or not. The purpose of this object is, for example, to be able to mute a stereo during a call and have the sound resumed at the end of the call.
“[VoIP] Play Video Intercom Ringtone”: 1-bit object that plays the video intercom ringtone once.

https://www.zennio.com

Tecnical Support: https://support.zennio.com 47

Z50 / Z70 v2 / Z100
2.1.13.1 VIDEO INTERCOM (LICENSE REQUIRED)
Note: Video Intercom functionality requires a license installation. If not, even being possible to configure it from ETS, its use will not be accessible.
Z70 v2 will be able to receive calls and show images from the camera of a Zennio outdoor unit, GetFace IP. Moreover, the door can be opened and a common call log is available for all configured video intercom.
Notes: To access the call log and visualization of the image of the camera is required necessary to parameterise a box as a Video Intercom. For further information see section 2.2.2.1.5.5.
In a Z70 v2 up to 21 outdoor units can be enabled, one of them being generic. Each outdoor unit can parameterize up to 4 doors, for a total of 84 doors controllable by one Z70 v2. The GetFace IP is responsible for controlling the power supply to the doors locks.
Meanwhile, each GetFace IP can call to a maximum of 10 Z70 v2 in parallel.
In addition, in ANNEX I. Video Intercom Operation, the functions and controls of the different dialogues that appear in Z70 v2 in relation to the video intercom functionalities are detailed.
For further information about the configuration of Z70 v2 and external units GetFace IP, please refer to the “Z41 COM / Z70 + GetFace IP Configuration Guide” and the specific documentation of “Zennio GetFace IP” (available at www.zennio.com).

https://www.zennio.com

Tecnical Support: https://support.zennio.com 48

Z50 / Z70 v2 / Z100
ETS PARAMETERISATION After enabling Video Intercom in the “VoIP Calls” screen (section 2.1.13), a new tab will be incorporated into the tree on the left.

Figure 29. Video intercom
“Call Accepted” Label [CALL ACCEPTED]: text to be displayed when the call is accepted on a synchronised device.
“Call Rejected” Label [CALL REJECTED]: text to be displayed when the call is rejected on a synchronised device.
Default Ringtone [Ringtone 1 / … / Ringtone 7]: melody played by Z70 v2 when receiving a call from an video intercom. The tone can be changed from the configuration page (see section 2.2.1.2.3) or through the “[VoIP] Video Intercom Ringtone” object.
Numer of Tones [0…3…10]: set how many times will sound the ringtone.
Play Ringtone Object Value [1 = Play Ringtone / 0 = Play Ringtone]: define the polarity of “[VoIP] Play Video Intercom Ringtone” object.
Generic Outdoor Unit [disabled/enabled]: checkbox that enables a new tab with the same name in the left menu where the generic outdoor unit is configured (see section 2.1.13.1.2).
Outdoor Unit n [disabled/enabled]: checkbox that enables a new tab with the same name in the left menu where each video intercom is configured (see section 2.1.13.1.1).

https://www.zennio.com

Tecnical Support: https://support.zennio.com 49

Z50 / Z70 v2 / Z100
2.1.13.1.1 Outdoor Unit n
The video intercom used can be of two types: private or community. The main difference between them is that community video intercom does not enable the camera image to be viewed if there is no incoming or ongoing call. In case the unit does not have a camera, the images will not be viewed in case of any event, no matter what type of video door phone it is. Each outdoor unit enables the setting of up to 4 doors, whose opening can be executed by means of an HTTP command (it is possible to enable secure opening with username and password) sent to the outdoor unit and/or a communication object sent directly to the actuator. It is also possible to enable the sending of a KNX object to the bus each time the door is opened.
ETS PARAMETERISATION
After enabling any of the outdoor units (see section 2.1.13.1), a new sub-tab “Outdoor unit n” is displayed with the following parameters:

Figure 30. Outdoor Unit n
Name: text field identifying the parameterised outdoor unit. This name will be displayed both in the Z70 v2 call log and on the top bar of incoming and ongoing calls.
Type [Private / Community]: The “Private” type enables access at any time to the visualization of images from the camera of the outdoor unit.

https://www.zennio.com

Tecnical Support: https://support.zennio.com 50

Z50 / Z70 v2 / Z100
Unit with Camera [disabled / enabled]: define whether the installed video intercom has camera.
Outdoor Unit ID [ID_n]: alphanumerical identifier of GetFace IP (field Phone Number (ID), in Services Phone).
Note: the characters included in this field must comply RFC 2396 standard.
Set Static IP [disabled / enabled]. If Z70 v2 and GetFace IP are in different networks, IP Address [192.168.1.201] of GetFace IP must be set, in addition to Specifying Gateway, in “IP Configuration” tab (see section 2.1.12).
Opening Settings:
HTTP Command Secure Opening [disabled/enabled]: the order to open a door will be sent via a HTTP command. Setting a username and a password will be required (must match with the ones set in GetFace IP in section Services HTTP API).
KNX Object [disabled / enabled]: enables the 1-bit object “[VI n] Switch n” by means of which the output of a KNX actuator with the door lock connected to it can be controlled. Choosing the Object Value [1 = Open / 0 = Open] that will open the door is possible.
Automatic Door Opening (DOORMATIC) [disabled/enabled]: enables the door/s to be opened automatically when receiving a call.
· Initial Status (After Download) [Disabled / Enabled]: sets whether the automatic opening is enabled or not after ETS Download. It also can be changed at runtime through the object “[VI n] Enable Automatic Door Opening”.
· Disable if “Do Not Disturb” Mode Is Active [disabled/enabled]: disables the automatic door opening when do not disturb mode is active.
· Opening Delay [0…255] [x 1s]: set a time after which the automatic door opening command will be sent.
Enable KNX Objects to Trigger Opening [disabled/enabled]: enables the 1-bit object “[VI n] Trigger Switch n” which can open the door by writing on

https://www.zennio.com

Tecnical Support: https://support.zennio.com 51

Z50 / Z70 v2 / Z100
the KNX object. Choosing the Object Value [1 = Open / 0 = Open] that will open the door is possible.
Important: For safety reasons, it is recommended not to use this communication object or to use it under the responsibility of the integrator.
Door n [disabled/enabled]: enables or disables every door, up to 4 for each outdoor unit.
Note: the door concept in Z70 v2 refers to the switches configured in GetFace IP in section Hardware Switches.
Label: name that will appear on the preview, incoming call and ongoing call panel to identify the door.
HTTP Command Opening [disabled/enabled]: set whether the HTTP command is sent when the door is opened.
Automatic Door Opening (DOORMATIC) [disabled/enabled]: defines whether each of the doors should open automatically with the set delay. Its selection will be available whenever the general parameter for automatic door opening of the outdoor unit is enabled.
For further information about the configuration above parameters of external units GetFace IP, please refer to the “Z41 COM / Z70 + GetFace IP Configuration Guide” and the specific documentation of “Zennio GetFace IP” (available at www.zennio.com).
2.1.13.1.2 General Outdoor Unit
Whenever a call is received from a video intercom whose identification code (ID) does not match any of the parameterized ones for the rest of the enabled outdoor units (see outdoor unit ID, section 2.1.13.1.1), the call will be visualized on the generic outdoor unit panel.
ETS PARAMETERISATION After enabling Generic Outdoor Unit, in “Video Intercom” (see section 2.1.13.1), a new tab with the same name is created:

https://www.zennio.com

Tecnical Support: https://support.zennio.com 52

Z50 / Z70 v2 / Z100

Figure 31. Generic Outdoor Unit
This tab is analogous to “Outdoor unit n”, but the video intercom identification fields (Outdoor unit ID and Set Static IP) are excluded. For more information on the configuration of the parameters see section 2.1.13.1.1.
2.1.13.2 INTERNAL CALL (LICENSE REQUIRED)
Note: Internal Call functionality requires a license installation. If not, even being possible to configure it from ETS, its use will not be accessible. Z70 v2 can, via its Ethernet connection, make and receive calls from others Z41 COM, and Z70 v2 and that will be registered. The access to the internal call history will be enabled as long as, at least one box is configured as an internal call (see section 2.2.2.1.5.6). To receive calls, each of the screens involved in the communication must have the other configured as a contact. In a Z70 v2 up to 8 contacts can enable and configure or be imported up to 100 via web. For further information about the configuration and importation of contacts via web, please refer to the “Webserver Tools” manual (available in the product section of Z70 v2 in Zennio web portal, www.zennio.com). In ANNEX II. Internal Call Operation details the functions and controls of the dialogs that appear in Z70 v2 related to the internal calls functionalities.

https://www.zennio.com

Tecnical Support: https://support.zennio.com 53

Z50 / Z70 v2 / Z100
ETS PARAMETERISATION After enabling Internal Calls, in “VoIP Calls” tab (section 2.1.13), a new tab will be incorporated into the tab tree:

Figure 32. “Internal call” tab
Page Title: Incoming / Outgoing / Ongoing Call: titles of the different dialogues of the internal calls.
“Communication Error” / “End Call” / “Busy Contact” Label: text displayed on screen when a call cannot be established with the contact, the call is terminated or the contact has an ongoing call, respectively.
Default Ringtone [Tone 1 / … / Tone 7]: selects the sound Z70 v2 will make when it receives an internal call from another device. The selected tone will be applied after downloading, but can be changed later from the configuration page (see section 2.2.1.2.3) or by communication object.
Number of Tones [0 / … / 3 / … / 10]: sets how many times the ringtone will sound.
Import Contacts [From ETS / From the Web]: defines how the contacts list will be imported. If the “From ETS” option is chosen, the following parameters will also be displayed:
Contact n [disabled / enabled]: checkbox enabling a new tab (“Contact n”) where the parameters of each indoor unit are configured (see section 2.1.13.2.1).

https://www.zennio.com

Tecnical Support: https://support.zennio.com 54

Z50 / Z70 v2 / Z100
Note: For further information about the configuration and importation of contacts via web, please refer to the “Webserver Tools” manual (available in the product section of Z70 v2 in Zennio web portal, www.zennio.com).
2.1.13.2.1 Contact n
ETS will enable to configure a list of up to 8 contacts for each Z70 v2.
For Z70 v2 to be able to make calls to other screens (Z41 COM or Z70 v2), certain data, such as the ID and IP address of each contact, will need to be correctly configured. Otherwise, communication between devices will not take place.
ETS PARAMETERISATION After enabling Contact n in “Internal Call” subtab, a new tab is created where the name of the contact that is going to appear in Z70 v2 and the necessary data to be able to establish communication with other devices is possible to set.

Figure 33. “Contact n” tab
This tab shows the following parameters:
Name [Contact n]: name that will be displayed both in the call log and in the contact list. ID [IC_n]: Contact identifier. IP Address [192.168.1.111]: IP address of the contact.
Important: both the IP address and ID must match the IP Address and My ID set in the “IP Settings” tab (section 2.1.12) of the device to which the contact refers.

https://www.zennio.com

Tecnical Support: https://support.zennio.com 55

2.1.14 AVANCED

Z50 / Z70 v2 / Z100

Independent tab for the parameterisation of some advanced functions. These functions are explained next.

ETS PARAMETERISATION
After enabling the Advanced Configuration from “Configuration” screen (see section 2.1.1), a new tab will be incorporated into the tree on the left.

Figure 34. Advanced Configuration.
Cleaning Function [disabled/enabled]: enables or disables the “Cleaning Function” tab. See section 2.1.14.1 for details.
Pop-Ups [disabled/enabled]: enables or disables the “Pop-Ups” tab. See section 2.1.14.2 for details.
Welcome Back Object [disabled/enabled]: enables or disables the “Welcome Back Object” tab. See section 2.1.14.3 for details.
2.1.14.1 CLEANING FUNCTION
This feature is very similar to the touch locking, that is, it locks the touch area, thus discarding further button touches. The difference is that this function remains active only during a parameterisable time, and then stops.
This function is intended to let the user clean the touch area with the certainty of not triggering unwanted actions.
A message is shown during the cleaning state. When the timeout is about to end, making this message blink or the device beep (or both) is possible too.

https://www.zennio.com

Tecnical Support: https://support.zennio.com 56

Z50 / Z70 v2 / Z100
Figure 35. Cleaning Function Message
ETS PARAMETERISATION After enabling Cleaning Function from “Advanced” screen (see section 2.1.14), a new tab will be incorporated into the tree on the left.

Figure 36. Cleaning Function.
Time to Exit Cleaning Status [5…15…65535][s] [1…65535][min/h]: timeout to deactivate the cleaning function after triggered.
Message Notification [Cleaning…]: textbox to enter the desired message.
Notify Expiration [No / Blink Message / Play Sound / Both]: sets whether to notify the timeout expiration or not. When any of the three later options is selected, a new parameter shows up: Length of the Warning [1…5…65535][s] [1…65535][min/h]: sets the
ahead-time to start the notification prior to the end of the cleaning function.
The “[General] Cleaning Function” one-bit object triggers the cleaning function when it receives a “1” from the KNX bus.

https://www.zennio.com

Tecnical Support: https://support.zennio.com 57

Z50 / Z70 v2 / Z100
2.1.14.2 POP-UPS
This function permits showing the user a pop-up message of up to four lines of text on the display, each of which can be object-dependant or set in parameters.
It is possible to enable up to 6 pop-ups, each of which can be launched in 3 different ways: by using a 1-bit object, by using a 1-byte object or by modifying the text of one of the messages. They can also be launched when activating the different states of the control of Room State (see section 2.2.2.1.2.6).
The pop-up can be closed pressing the confirmation button inside it or using the 1-bit or 1-byte objects named above.

ETS PARAMETERISATION

Figure 37. Pop-up

After enabling Pop-Ups from “Advanced” screen (see section 2.1.14), a new tab will be incorporated into the tree on the left.

https://www.zennio.com

Figure 38. Pop-ups tab
Tecnical Support: https://support.zennio.com 58

Z50 / Z70 v2 / Z100
Pop-Up n [disabled/enabled]: allows to enable/disable each pop-up. After enabling each pop-up, a new tab will be incorporated into the tree on the left named “Pop-Up n”.
2.1.14.2.1 Pop-Up n

Figure 39. Pop-Up n
Pop-Up Trigger: sets the type of object that is used to show the pop-up message.
[1 Bit Object]: when this option is selected, the object “[General][Pop-Up n] 1 Bit” appears to launch the pop-up message.
· Values to Hide/Show the Pop-Up [0 = Hide Pop-Up; 1 = Shown Pop-Up / 0 = Shown Pop-Up; 1 = Hide Pop-Up]: allows to choose the polarity of the 1-bit object to show/hide pop-up.
[1 Byte Object]: allows to show/hide the pop-up through the object “[General ][Pop-Up n] 1 Byte”. When selected, the following parameters are displayed:
· Object Value to Hide Pop-Up [0…255]: sets the value used to hide the pop-up.
· Object Value to Show Pop-Up [0…255]: sets the value used to show the pop-up.
Note: If the value to hide the pop-up is the same as the value to show it, it won’t be hidden with any value.

https://www.zennio.com

Tecnical Support: https://support.zennio.com 59

Z50 / Z70 v2 / Z100
[Changes in 14 Bytes Objects]: when this option is selected, the pop-up will appear on the screen when a value is received through the objects “[General ][Pop-Up n] Line x”.
Line [1,4] [Fixed Text / Text Received from Object]: sets whether the corresponding text line will be pre-defined or object-dependent. If “Fixed Text” is selected, the following parameter will appear
Text: textbox to enter the desired text for the corresponding line.
The 14-byte object “[General][Pop-Up n] Line x” will be shown up to four times per popup, depending on how many text lines have been assigned the option “Text Received from Object”.
2.1.14.3 WELCOME BACK OBJECT
Z70 v2 can send a specific object to the KNX bus when the user presses a touch button after a significant amount of time since the last press or presence detection (when the proximity sensor is enabled). Sending it or not can also depend on an additional, configurable condition consisting in the evaluation of up to five binary objects.
Any actions that in normal operation may be executed will not be if the welcome back object is sent to the bus. Thus, if the user presses a button and this causes the welcome back object to be sent, the normal action of that button will not be triggered.
ETS PARAMETERISATION
After enabling Welcome Back Object from “Advanced” screen (see section 2.1.14), a new tab will be incorporated into the tree on the left.

https://www.zennio.com

Figure 40. Welcome Back Object.
Tecnical Support: https://support.zennio.com 60

Z50 / Z70 v2 / Z100
Time to Activate the Welcome Object [30…65535][s] [1…65535][min/h] : sets the minimum time that should elapse after the last button touch (or presence detection, when the proximity sensor is enabled) before the next one triggers the execution of the welcome back function.
Send Object Trigger [Press Button / Detect Presence]: sets whether the welcome back object is sending after a touch in the screen or when the proximity sensor detects presence.
Additional Condition [No Additional Condition / Do Not Send Unless All Additional Conditions are 0 / Do Not Send Unless All Additional Conditions are 1 / Do Not Send at Less One of the Additional Conditions is 0 / Do Not Send at Less One of the Additional Conditions is 1]: condition that must be fulfilled for sending the welcome object. When selecting any condition, the following parameter appears:
Number of Condition Objects [1…5]: up to 5 objects can be enabled for the additional condition.
Welcome Back Object (1-Bit) [disabled/enabled]: checkbox to enable the sending of a 1-bit value (through “[General] Welcome back”) when the welcome back function is triggered and the condition (if any) evaluates to true. The desired value should to be set in Value [Send 0 / Send 1].
Welcome Back Object (Scene) [disabled/enabled]: checkbox to enable the sending of a scene run request (through “[General] Scene: send”) when the welcome back function is triggered and the condition (if any) evaluates to true. The desired value should to be set in Scene Number [1…64].

https://www.zennio.com

Tecnical Support: https://support.zennio.com 61

2.2 DISPLAY

Z50 / Z70 v2 / Z100

2.2.1 PAGES
The user interface is organised into pages (up to twelve different pages, in addition to the `Configuration Page’), each of which can be accessed from the Menu page, which (unless the contrary has been parameterised) is automatically shown after the start-up.
The twelve pages are general purpose, at the entire disposal of the integrator, who may include up to twelve controls with different functionalities per page. The remaining Configuration page is specific purpose, as it is provided for user customisation of the device.
The user interface permanently shows a top bar with the current page name, current time of day and temperature, and if desired, a button that allows the user to return to the “Home” page:

Figure 41. “Home” button.
In addition, from the menu page, and provided that it has been enabled, the configuration page can be accessed via a button located in the navigation bar will be possible.

Figure 42. Configuration button

https://www.zennio.com

Tecnical Support: https://support.zennio.com 62

ETS PARAMETERISATION

Z50 / Z70 v2 / Z100

Figure 43. General pages configuration
The parameters available are:
Number of Pages [1…12]: number of general purpose pages that will be activated on the device. For each page a dedicated ETS tab will be shown for configuration.
Default Page [Menu]: dropdown list that sets the page that will behave as the default page. This page will be the one shown after the inactivity time elapsed.
Menu Page [disabled/enabled]: enables o disables a page with direct access to available general-purpose pages.
Home Button in the Navigation Bar [disabled/enabled]: of enabled, the following parameter will be displayed:
Page Linked to the Home Button [Menu]: select the page to which the device will navigate when the “Home” button is press.
Configuration Page [disabled/enabled]: if enabled, direct access to the configuration page from the menu page will be allowed.
Pages Distribution [Empty / 1 Page / … / 12 Page]: set which page, from a list of 12, will be placed in each of the twelve possible boxes on the screen.

https://www.zennio.com

Tecnical Support: https://support.zennio.com 63

Z50 / Z70 v2 / Z100 2.2.1.1 MENU The user interface may have up to twelve pages of general purpose, each of which can host up to twelve different controls or indicators.

Figure 44. Menu Page
ETS PARAMETERISATION The Menu tab allows defining generic options regarding the enabled control pages, which can be accessed from this screen.

Figure 45. Menu.
The parameters available are:
Title: text field that identifies the menu pages. In addition, this field allows changing the name of the tab in ETS left menu, as shown in the Figure 45.

https://www.zennio.com

Tecnical Support: https://support.zennio.com 64

Z50 / Z70 v2 / Z100 Use this Text in the Device [disabled/enabled]: enables the text to be used
as the page title in the device.
Automatic Page Shaping [disabled/enabled]: enables choosing whether the pages in Menu should be automatically distributed depending on the number of pages configured, or be displayed as a static 3×4 grid.
2.2.1.2 CONFIGURATION PAGE
The Configuration page lets the user to know or adjust certain technical values about the device, as well as customise the visual and audio adjustments of the user interface:

Figure 46. Configuration Page
ETS PARAMETERISATION After enabling the Configuration Page from “Pages” screen (see section 2.2.1), a new tab will be incorporated into the tree on the left.

https://www.zennio.com

Tecnical Support: https://support.zennio.com 65

Z50 / Z70 v2 / Z100

Figure 47. Configuration tab

https://www.zennio.com

Tecnical Support: https://support.zennio.com 66

Z50 / Z70 v2 / Z100
Title: text field that identifies the configuration page. In addition, this field allows changing the name of the tab in ETS left menu, as shown in the

Figure 47.
Use this Text in the Device [disabled/enabled]: allows the text to be used as the page title in the device.
Automatic Page Shaping [No / Yes]: allows choosing whether the boxes in the Configuration Page should be automatically distributed depending on the number of boxes configured, or be displayed as a static 3×4 grid.
Protect: sets whether the page will be password-protected or not. Depending on the security levels configured (one or two; see section 2.1.4) this list will contain the following options: One Level:

https://www.zennio.com

Tecnical Support: https://support.zennio.com 67

Z50 / Z70 v2 / Z100
· [No / Yes]: sets whether the page is password-protected at level 1 or without a password.
Two Levels: · [No / Level 1 / Level 2]: sets the level of security to access the configuration page.
Time/Date [disabled/enabled]: if enabled, the date and time of the device can be set directly from the user interface:

Figure 48. Time and date.
Device [disabled/enabled]: enables or disables the “Device” tab in the left menu. For more information, see section 2.2.1.2.1
Profile [disabled/enabled]: enables or disables the “Profile” tab in the left menu. For more information, see section 2.2.1.2.2
Probe Calibration [disabled/enabled]: enables or disables the box to configure the offset of the internal temperature probe.
Alarm Log [disabled/enabled]: enables or disables the alarm log box that provides access to the log file where alarm events are incorporated, in reverse chronological order, with the name, time and date of every alarm event will being shown. In addition, the log will show the current status of each of them:

Alarm State Alarm active Alarm finished, but not confirmed

Icon

https://www.zennio.com

Tecnical Support: https://support.zennio.com 68

Z50 / Z70 v2 / Z100
Alarm confirmed, but not finished Alarm finished and confirmed
Table 2. Alarm Log Icons
This centralised file may be useful when the user needs to check the status of a set of alarm controls distributed across several pages.

Figure 49. Alarm Log
To delete the record, press and hold the button , at the bottom right of the window for more than 3 seconds.
Note: For information on alarms, see section 2.2.2.1.5.4.
VoIP Calls [disabled/enabled] (License required): enables or disables the “VoIP Calls” tab in the left menu. For more information, see section 2.2.1.2.3.
Device Pairing [enabled] (License required): button to access to the pairing function, which must be executed with each device desired to control the Z70 v2 remotely. For more details, please refer to ANNEX III. Remote Control via IP.
Voice Control [enabled] (License required): enable the box to activate or deactivate voice control function. Please refer to the user manual “ZenVoice” (available in the Z70 v2 product section at the Zennio homepage, www.zennio.com) for detailed information about the functionality and the configuration.

https://www.zennio.com

Tecnical Support: https://support.zennio.com 69

Z50 / Z70 v2 / Z100 Note: the voice control and device pairing boxes will always be visible when the Remote Control parameter is enabled and hidden when the Remote Control parameter is disabled. Moreover, for all these controls, the following parameters can be configured: Label: text that will appear to identify the box. Protect [No / Yes] / [No / Level 1 / Level 2]: exactly the same as the page protection explained above, but for the boxes. Object to Show/Hide Box [disabled/enabled]: when this option is enabled, a new 1-bit object appears (“[Config.][Bi] Show/Hide Box”) that allows hiding / showing the box through the KNX bus.
2.2.1.2.1 Device
Z70 v2 configuration page, if Device is enabled, will display a button allowing access to several controls and indicators with device-specific information:

Figure 50. Device.
ETS PARAMETERISATION After enabling the Device from “Configuration Page” screen (see section 2.2.1.2), a new tab will be incorporated into the tree on the left.

https://www.zennio.com

Tecnical Support: https://support.zennio.com 70

Z50 / Z70 v2 / Z100

Figure 51. Configuration Page. Device.

Programming Button [disabled/enabled]: control/indicator that shows the status of the Prog./Test LED of the device. In particular, it permits entering/leaving the programming mode as by pressing the actual programming button of the device.

Reset [disabled/enabled]: enables or disables the box to perform a reset on the device, by pressing more than 3 seconds the button:
Reset Type:

· [Parameters Reset]: similar to restoring the device to the justparameterised state.

· [Application Reboot]: simple device reset, with no data loss.

· [Parameters Reset and Application Reboot]: the above two, combined.

KNX [disabled/enabled]: indicator that shows the individual address of the device.

Program Version [disabled/enabled]: indicates the downloaded firmware and program version.

IP/MAC [disabled/enabled]: indicates the IP and MAC direction.

Serial number [disabled/enabled]: indicates the device serial number.

Moreover, for all these controls, the following parameter can be configured:

https://www.zennio.com

Tecnical Support: https://support.zennio.com 71

Label: text that will appear to identify the box.

Z50 / Z70 v2 / Z100

2.2.1.2.2 Profile

Z70 v2 configuration page, if Device is enabled, will display a button to access the visual and sound settings of the device:

Figure 52. Profile
ETS PARAMETERISATION After enabling the Profile from “Configuration Page” screen (see section 2.2.1.2), a new tab will be incorporated into the tree on the left.

Figure 53. Configuration Page. Profile.
Brightness [disabled/enabled]: enables or disables the box to adjust the brightness of the display.

https://www.zennio.com

Tecnical Support: https://support.zennio.com 72

Z50 / Z70 v2 / Z100 Theme [disabled/enabled]: enables or disables the box for the selection of the theme.
Volume [disabled/enabled]: box to control the volume of pulsation and sending sound. There are three volume levels in addition to the mute option.
Doorbell Volume [disabled/enabled]: box to control the volume of doorbell. There are five volume levels in addition to the mute option.
Doorbell Tone [disabled/enabled]: desired tone (among seven different options) for the acoustic signals emitted on doorbell. Note: Doorbell boxes will be only available if the “Object for Doorbell” parameter is enabled in the custom sounds tab (see section 2.1.10).
2.2.1.2.3 VoIP Calls (License Required)
Z70 v2 configuration page, if VoIP Calls is enabled, will display a button to access the video intercom and internal call settings of the device:

Figure 54. VoIP Calls
ETS PARAMETERISATION After enabling the VoIP Calls from “Configuration Page” screen (see section 2.2.1.2), a new tab will be incorporated into the tree on the left.

https://www.zennio.com

Tecnical Support: https://support.zennio.com 73

Z50 / Z70 v2 / Z100

Figure 55. Configuration page – VoIP calls
Video Intercom Ringtone [disabled/enabled]: box to change the melody to be played when receiving a call from an external unit.
Internal Call Ringtone [disabled/enabled]: box to change the melody to be played when receiving a call for an internal unit.
Ringtone Volume [disabled/enabled]: enables the box to modify the calls tone volume.
SIP ID/IP Address/Gateway [disabled/enabled]: information box showing the ID, IP address and gateway, as configured in “IP Configuration” tab (see section 2.1.12)
“Do Not Disturb” Mode: Enabling [disabled/enabled]: checkbox to enable or disable the do not disturb mode. When enabled, incoming calls will not be received. However, in case of Video Intercom functionality, they will be registered in the call log.
When enabling the mode, the value 1′ is sent through the object “[VoIP] “Do Not Disturb” Mode” and when disabling it is sent the value0′.
Note: if do not disturb mode is enabled during a call, the call will go through normally and the mode will be activated when the call finishes.
“Do Not Disturb” Mode: Timing [disabled/enabled]: this box set the time that the do not disturb mode will be active. A time 0 will activate this mode indefinitely.

https://www.zennio.com

Tecnical Support: https://support.zennio.com 74

Z50 / Z70 v2 / Z100 When enabling the mode, the value 1′ is sent through the object “[VoIP] “Do Not Disturb” Mode” and when the timing expires it is sent the value0′. It is also possible to stop the countdown disabling the mode (by manually or through the communication object).
2.2.1.3 PAGE N Z70 v2 has up to twelve general purpose pages that can be enabled from the “Pages” tab. Thus, a new tab called Page n will be displayed for each of the n enabled pages. Inside each page, the desired controls can be placed as boxes arranged in order, according to the parameters for each page. In addition, larger boxes can be created by grouping 4 boxes, with a format of 2×2. To make this type of grouping it is necessary to configure the page as shown in Figure 56.
Figure 56. 2×2 Boxes Configuration

Figure 57. 2×2 Box Visualization

https://www.zennio.com

Tecnical Support: https://support.zennio.com 75

ETS PARAMETERISATION

Z50 / Z70 v2 / Z100

Figure 58. Configuration Page n
This screen contains the following parameters:
Title: text field that identifies each of the enabled pages. In addition, this field allows changing the name of the tab in ETS left menu, as shown in the Figure 58.
Use this Text in the Device [disabled/enabled]: allows the text to be used as the page title in the device.
Icon [Kitchen]: sets the icon that will represent the page in the Menu page. It could be selected from two available lists [Menu / General].
“Menu” is a list of the most common icons that are configured in the main menu.
“General” is a list of all available icons. At the end of the list, customised icons, that must have been previously imported, can be selected (see section 2.1.11.4).
Note: a list with all icons available can be found in document “Z70 v2 Icon list”, available at www.zennio.com.
Automatic Page Shaping [disabled/enabled]: enables to choose whether the controls should be automatically or be displayed as a static grid.
Note: if automatic page shaping is enabled, grouping of 2×2 cells is not possible.

https://www.zennio.com

Tecnical Support: https://support.zennio.com 76

Z50 / Z70 v2 / Z100 Control Distribution [Nothing / Control 1…Control 180]: enables selecting which control, from a list of 180 controls, will be placed in each of the twelve possible boxes on the screen.
Protect: sets whether the page will be password-protected or not. Depending on the security levels configured (one or two; see section 2.1.4) this list will contain the following options:
One Level: · [No / Yes]: sets whether the page is password-protected at level 1 or without a password.
Two Levels: · [No / Level 1 / Level 2]: sets the level of security to access the page.
Objects to Show/Hide Box [disabled/enabled]: enables or disables a 1-bit object for each enabled box in which a control has been configurated (“[Pn][Bi] Show/Hide Box”) to show or hide the corresponding box.
2.2.2 CONTROLS
User interface can have up to 180 different controls placed on 12 pages. Each of this controls will be configurated independently and placed in the desire box of the page (see section 2.2.1.3).
Within the controls tab, sub-tabs with groupings of up to 15 controls each are displayed to do parameterization easier.
ETS PARAMETERISATION

Figure 59. Controls configuration.
Number of Controls [1…180]: selects the number of controls that will became available. For each of them a new ETS tab will be shown.

https://www.zennio.com

Tecnical Support: https://support.zennio.com 77

Z50 / Z70 v2 / Z100 Buttons Border [disabled/enabled]: sets whether the buttons will have an outline or if only the button icon is displayed. Touch Zone for 1-Button Controls: this parameter defines whether the touch zone for 1-button controls is the entire box or a separated button. The behavior in each case is: [Box]: actions will take place by clicking anywhere in the box. [Button]: a separate button will be displayed in the upper right of the box.
The control will be only executed when the button area is clicked.
Figure 60. Touch zone in box vs in button.
2.2.2.1 CONTROL i This screen contains the following parameters common to all type of boxes:

Figure 61. Control i
Title: text field that identifies each of the enabled controls and their communication objects, which are designated with the prefix “[Cx][Title]”.
In addition, this field allows changing the name of the tab in ETS left menu, as shown in the Figure 61.
Use this Text in the Device [disabled/enabled]: allows the text to be used as the box label where this control is placed in the device.

https://www.zennio.com

Tecnical Support: https://support.zennio.com 78

Z50 / Z70 v2 / Z100
Visualization: box format. The available box formats in Z70 v2 are:
[Indicator]: the box will work as a status indicator.
[1-Button Control]: the box will work as a one-button control.
[2-Button Control]: the box will work not only as a status indicator, but also as a two-button control.
[Climate Control]: the box will act as a climate indicator and a climate control.
[Other]: the box will implement some other special functionality.
Function: depending on the “Visualization” type selected, the parameters below will change. The following sections explain the available parameters depending on the visualization type selected.
Icon and/or Button: drop-down list with the available icons to show in the indicator(s) and/or button(s) of the box. At the end of the list, the custom icons (“Cx”) that must have been previously imported in Z70 v2, can be selected (see section 2.1.11.4).
Note: a list with all icons available can be found in document “Z70 v2 Icon list”, available at www.zennio.com.
Log & Graph [Disable / Record Log / Record Log and Show Graph]: sets if received data through the indicator object will be recorded and if the graph will be displayed. See ANNEX IV. Graphs for more information.
If Record Log and Show Graph is enabled, the following parameters will be displayed:
Show Hour Zoom [disabled/enabled]: sets whether the hour zoom is enabled on the control graph.
Graph Type [Curve / Straight / Step]: graph types available for the control. The options for this parameter will depend on the type of control chosen and will only be displayed for non-binary types.
Polarity [0 = Low Level; 1 = High Level / 0 = High Level; 1 = Low Level]: sets which is the high level and which is the low level depending on the value received. This parameter will only be displayed on binary type controls.

https://www.zennio.com

Tecnical Support: https://support.zennio.com 79

Z50 / Z70 v2 / Z100
Protect: sets whether the box will be password-protected or not. Depending on the security levels configured (one or two; see section 2.1.4) this list will contain the following options:
One Level: · [No / Yes]: sets whether the control is password-protected at level 1 or without a password.
Two Levels: · [No / Level 1 / Level 2]: sets the level of security to operate on the control.
Note: neither indicators nor change-scale buttons can be protected.
2.2.2.1.1 INDICATORS
Controls designed for displaying statuses, showing a numeric or text value, or displaying an icon that represents the current value of a communication object.
2.2.2.1.1.1 Binary
When this function is assigned to a control, the “[Ci] Binary Indicator” communication object become available, as well as following parameters:

Figure 62. Indicator – Binary.
Indicator Type [Icon / Text]: allows selecting whether the status represented by each indicator value will be text type or icon type.
2.2.2.1.1.2 Enumeration
The box will behave analogously to the case of the Binary Indicator however, it will be possible to distinguish up to 6 states.
When this function is assigned to a control, a 1-byte communication object, “[Ci] Enumeration Indicator”, will become available as well as a series of parameters:

https://www.zennio.com

Tecnical Support: https://support.zennio.com 80

Z50 / Z70 v2 / Z100

Figure 63 Indicator – Enumeration
Number of Value [1…2…6]: sets the number of states in the enumerated list. For every distinguished state, the parameter Value [0…255] will become available together with the corresponding indicator.
Indicator Type [Icon / Text]: enables to select whether the status indicator which each value is represented will be text type or icon type. As many drop- down lists of icons or text boxes will be displayed as states have been enabled in the previous parameter.
2.2.2.1.1.3 Numerical Indicators
Indicators configured as “Integer”, “Percentage”, “Float”, “Temperature” and “Cost” are numerical type indicators that show the value of the corresponding communication object, enabled when that control is assigned to a box.

Figure 64 Indicator – Numerical
The range of values allowed for each type and the name of the corresponding object are included in the following table.

Function Integer

Size 1 Byte

Sign Unsigned

Range 0 ­ 255

Related Object [Ci] 1-Byte Unsigned Int Indicator

https://www.zennio.com

Tecnical Support: https://support.zennio.com 81

Z50 / Z70 v2 / Z100

Percentage Float
Temperature
Cost

2 Bytes
4 Bytes 1 Byte 2 Bytes 4 Bytes 2 Bytes 1 Byte
2 Bytes 2 Bytes

Signed Unsigned
Signed Unsigned
Signed
Float Unsigned
Signed Unsigned
Signed Float

-128 ­ 127

[Ci] 1-Byte Signed Int Indicator

0 ­ 65535

[Ci] 2-Byte Unsigned Int Indicator

-32768 ­ 32767

[Ci] 2-Byte Signed Int Indicator

0 ­ 4294967295

[Ci] 4-Byte Unsigned Int Indicator

-2147483648 ­ 2147483647 [Ci] 4-Byte Signed Int Indicator

0 ­ 100

[Ci] Percentage Indicator

-671088.64 ­ 670433.28 [Ci] 2-Byte Float Indicator

-3,403×1038 ­ 3,403×1038 [Ci] 4-Byte Float Indicator

-99 ­ 199

[Ci] Temperature Indicator

0 ­ 255

[Ci] Cost Indicator: 1-Byte Unsigned Int

-128 ­ 127

[Ci] Cost Indicator: 1-Byte Signed Int

0 ­ 65535

[Ci] Cost Indicator: 2-Byte Unsigned Int

-32768 ­ 32767

[Ci] Cost Indicator: 2-Byte Signed Int

-671088.64 ­ 670433.28 [Ci] Cost Indicator: 2-Byte Float

Table 3. Numerical indicators

Units: permits specifying the measuring units of the displayed value.

Note:
For percentage indicator, the symbol % always will be displayed as unit.
The temperature indicator will be shown in ºC or ºF depending on the active locale (see section 2.1.2). In addition, the following parameters will be available for this control type:

· Button to Change between ºC and ºF [disabled/enabled]: enables a control that allows the temperature scale to be changed from the box itself:

Figure 65. Indicator – Temperature (box)
· Include Plus Sign before Positive Numbers [disabled/enabled]: shows the `+’ sign before positive temperature values.
For cost indicator, choosing as a unit the currency associated with it, from a list of available ones, will be mandatory. This will be placed before or after the indicator, according to the active locale (see section 2.1.2).

https://www.zennio.com

Tecnical Support: https://support.zennio.com 82

2.2.2.1.1.4 Text

Z50 / Z70 v2 / Z100

The box will show the text received through the communication object “[Ci] Text Indicator”.

2.2.2.1.2

Figure 66. Indicator – Text.
1-BUTTON CONTROL

The box configured with this control type will have a button (at the top right or throughout the box, see section 2.2.2) and a state indicator. In addition, through Function parameter, it will be possible to select the specific function that the control will perform.

Figure 67 1-Button Control (Box).
2.2.2.1.2.1 Switch
The button of the box will react to user presses by sending a binary value to the bus through the “[Ci] Switch” object. In addition, this control will have associated a dedicated object for the box indicator (“[Ci] Binary Indicator”), which is automatically updated after the control order is sent and can also receive values from the bus.

https://www.zennio.com

Tecnical Support: https://support.zennio.com 83

Z50 / Z70 v2 / Z100
Figure 68. 1-Button Control – Switch
Action [Send 0 / Send 1 / Toggle 0/1]: specifies what value will be sent to the bus after pressing the control button. Indicator Type [Icon / Text]: allows selecting whether the status represented by each indicator value will be text type or icon type. 2.2.2.1.2.2 Two Objects (Short Press/Long Press) The button in the box will react differently to a short press and to a long press, setting a time threshold to distinguish both types of press by parameter.

Figure 69. 1-Button Control – Two Objects
Action on Short / Long Press [Send 0 / Send 1 / Toggle 0/1 / Send 1-Byte Unsigned Integer Value]: sets what value will be sent to the bus before which events.
When the option “Send 1-Byte Unsigned Integer Value” is selected, the value indicated in Value [0…255] parameter will be sent.

https://www.zennio.com

Tecnical Support: https://support.zennio.com 84

Z50 / Z70 v2 / Z100
Different objects are used to send values for short and long pulsations: “[Ci] Two objects – Short Press” and “[Ci] Two objects – Long Press”, respectively.
If the option chosen is “Send 0” or “Send 1”, the object “[Ci] Two objects Indicator” will appear for the box indicator, which is automatically updated after the control order is sent and when values are received from the bus.
Long Press Threshold Time [4…6…50] [ds]: sets the minimum time the user should hold the button in order to consider it a long press.
2.2.2.1.2.3 Hold & Release
This control function allows the user to configure sending a binary value on pressing and a different binary value on releasing the button. In addition, this control will have associated a dedicated object for the indicator (“[Ci] Binary Indicator”), which is automatically updated after the control order is sent and when values are received from the bus.

Figure 70. 1-Button Control – Hold & Release
Action on Hold / Release [Send 0 / Send 1]: permits setting what value will be sent to the bus through the objects “[Ci] Hold & Release”, and before which events.
2.2.2.1.2.4 Scene
When this function is assigned to a control, the box button will react to the different pulses by sending a certain scene value.

https://www.zennio.com

Tecnical Support: https://support.zennio.com 85

Z50 / Z70 v2 / Z100
Figure 71. 1-Button Control – Scene
Action [Run / Run and Save]: sets whether the device will only send scene execution orders (after a short press) or if it will be possible, to send scene save orders (after a long press). Scene Number [1…64]: scene value to be sent. Object to Use [General Scene Object / Individual Box Scene Object]: specifies whether the scene value will be sent through the object “[General] Scenes: Send” or through the individual object “[Ci] Scene: Send”. 2.2.2.1.2.5 Constant Numerical Controls When the functions “Counter Constant”, “Scaling Constant” or “Float Constant” is assigned to a control, the button in the box will react to user presses by sending a certain numerical value. This numerical value will depend on the constant control type selected to the box.

Figure 72. 1-Button Control ­ Constant Numerical

https://www.zennio.com

Tecnical Support: https://support.zennio.com 86

Z50 / Z70 v2 / Z100
Table 4 shows the permitted value range and the name of the object through which the values are sent to the bus.

Function
Integer
Scaling Float

Size 1 Byte
2 Bytes 1 Byte 2 Bytes

Sign Unsigned Signed Unsigned Signed

Range [0…255]

Related Object [Ci] 1-Byte Unsigned Int Control

[-128…0…127] [Ci] 1-Byte Signed Int Control [0…65535] [Ci] 2-Byte Unsigned Int Control [-32768…32767] [Ci] 2-Byte Signed Int Control [0…100] [Ci] Percentage Control [-671088.64…0…670433.28] [Ci] 2-Byte Float Indicator

Table 4. Numerical constant controls

Units: permits specifying the measuring units of the displayed value. For percentage indicators, the symbol % always will be displayed as unit.

2.2.2.1.2.6 Room State

Configuring with this function the box, controlling the states of the room will be possible, as well as show the associated pop-up. Thus, pressing the button in the box will cause the room status to switch between normal and Do Not Disturb or Make Up Room.

Figure 73. 1-Button Control – Room State.
State [Make Up Room / Do Not Disturb]: sets the status to be switched together with Normal. The switched values are sent to the bus via the 1-byte object “[Ci] Room State”.
Show Pop-Up When Activating Normal State [No / Pop-Up 1 / … / Pop-Up 6]: allows to select the pop-up to be displayed when the normal mode is activated.

https://www.zennio.com

Tecnical Support: https://support.zennio.com 87

Z50 / Z70 v2 / Z100 Show Pop-Up When Activating MUR [No / Pop-Up 1 / … / Pop- Up 6]: allows to select the pop-up to be displayed when the MUR mode is activated.
Note: the pop-ups selected must be activated (see section 2.1.14.2).
This control will have associated a dedicated object for the indicator (“[Ci] Room State Indicator”), which is automatically updated after the control order is sent and when values are received from the bus.
2.2.2.1.2.7 Enumeration
The box will behave analogously to the case of the switch, however the communication objects (control object “[Ci] Enumeration Control” and the status “[Ci] Enumeration Indicator”) will be 1-byte. Up to six discrete states can be distinguished depending on the value that the status object acquires from the control or receives from the bus.

Figure 74. 1-Button Control ­ Enumeration.
The available parameters are:
Number of Values [1…2…6]: number of states that will be distinguished. For every distinguished state, the parameter Value [0…255] will become available together with the corresponding indicator.
Indicator Type [Icon / Text]: allows selecting whether the status indicator which each value is represented will be text type or icon type. As many drop- down lists of icons or text boxes will be displayed as states have been enabled in the previous parameter.

https://www.zennio.com

Tecnical Support: https://support.zennio.com 88

2.2.2.1.3 2-BUTTON CONTROL

Z50 / Z70 v2 / Z100

The box configured with this control type will have a button at the right and a state indicator. In addition, through Function parameter, it will be possible to select the specific function that the control will perform.

2.2.2.1.3.1 Switch

Figure 75 2-Button Control (Box)

When the user touches the buttons in the box, a binary value will be sent through the “[Ci] Switch” object, while the status object “[Ci] Binary Indicator” will determine the icon or text shown in the box. The indicator will be updated automatically after each control order, and will also be able to receive values from the bus.

Figure 76. 2-Buttons Control – Switch
Action [Bottom = 0; Top = 1 / Top = 0; Bottom = 1]: sets the value to be sent when pressing each of the two buttons.
Indicator Type [Icon / Text]: allows selecting whether the status represented by each indicator value will be text type or icon type.

https://www.zennio.com

Tecnical Support: https://support.zennio.com 89

2.2.2.1.3.2 Switch + Indicator

Z50 / Z70 v2 / Z100

In the same way the previous control, when pressing in any of the controls configured as switch, Z70 v2 will send the parameterised binary value to the bus through the object “[Ci] Switch”. However, the indicator is independent and will only be updated according to the value received by the dedicated object.

Figure 77. 2-Buttons Control – Switch + Indicator
Action [Bottom = 0; Top = 1 / Top = 0; Bottom = 1]: sets the value to be sent when pressing each of the two buttons.
Indicator Type [Counter / Scaling / Float / Temperature]: sets the indicator type. According to the selected indicator the objects. The range of values allowed in each case and the name of the corresponding object are listed in the table.

Function
Counter
Scaling Float
Temperature

Size 1 Byte

Sign Unsigned Signed

Range 0 ­ 255 -128 ­ 127

Related Object [Ci] 1-Byte Unsigned Int Indicator [Ci] 1-Byte Signed Int Indicator

2 Bytes

Unsigned Signed

0 ­ 65535 -32768 ­ 32767

[Ci] 2-Byte Unsigned Int Indicator [Ci] 2-Byte Signed Int Indicator

1 Byte

0 ­ 100

[Ci] Percentage Indicator

2 Bytes

-671088.64 ­ 670433.28 [Ci] 2-Byte Float Indicator

1 Byte

-99 ­ 199

[Ci] Temperature Indicator

Table 5. Numerical indicators ­ Switch + Indicator

Units: permits specifying the measuring units of the displayed value.

Note:

https://www.zennio.com

Tecnical Support: https://support.zennio.com 90

Z50 / Z70 v2 / Z100 For percentage indicator, the symbol % always will be displayed as unit. The temperature indicator will be shown in ºC or ºF depending on the value
of the active locale (see section 2.1.2). In addition, the following parameters will be available for this control type: · Button to Change between ºC and ºF [disabled/enabled]: enables a
control that allows the temperature scale to be changed from the box itself:
Figure 78. Temperature 2-Buttons Control (Box)
· Include Plus Sign before Positive Numbers [disabled/enabled]: shows the `+’ sign before positive temperature values.
2.2.2.1.3.3 Two Objects (Short Press/Long Press) Control for sending specific binary values both after a short or a long press on any of the two buttons. Two different objects are used to send values for short and long pulsations, “[Ci] Two objects – Short Press” and “[Ci] Two objects – Long Press”.

Figure 79. 2-Buttons Control – Two Objects
Action on Short / Long Press [Bottom = 0; Top = 1 / Top = 0; Bottom = 1]: sets the value to be sent when short / long pressing each of the two buttons.

https://www.zennio.com

Tecnical Support: https://support.zennio.com 91

Z50 / Z70 v2 / Z100 Long Press Threshold Time [4…6…50] [ds]: sets the minimum time the user should hold the button in order to consider it a long press.
State Object [Short Press Object / Long Press Object]: allows setting the control command to which the status indicator, “[Ci] Two Objects – Indicator”, will obey. This object can also receive values from the bus.
Indicator Type [Icon / Text]: allows selecting whether the status indicator which each value is represented will be text type or icon type.
2.2.2.1.3.4 Numerical Controls
If any of the functions “Counter”, “Scaling” or “Float” is assigned to the control, user touches over the buttons will trigger the sending of a certain numerical value to the bus. This value will be progressively increased or decreased with every touch on top button or button bottom, through the control object, while the box itself will permanently reflect the current value of the corresponding status object. This object can also receive values from the bus.

Figure 80. 2-Buttons Control – Numerical Control
The different types of 2-button numerical control available, their configuration options and the objects associated with them are listed in the following table:

https://www.zennio.com

Tecnical Support: https://support.zennio.com 92

Z50 / Z70 v2 / Z100

Function
Counter
Scaling Float

Size Sign Minimum Value Maximum Value

Signed 1 Byte
Unsigned

[-128…127] [0…255] [-128…127] [0…255]

2 Byte

Signed [-32768…32767] Unsigned [0…65535] [-32768…32767] [0…65535]

1 Byte 2 Byte

[0… 100] [-671088.64… …670433.28] [0… 100] [-671088.64… …670433.28]

Increment on short press
[1…127] [1…255] [1…32767] [1…65535] [1…100] [0.1…0.5… …670433.28]

Increment on long press

Related Object

[1…10…127] [Ci] 1-Byte Signed Int Indicator [Ci] 1-Byte Signed Int Control [1…10…255] [Ci] 1-Byte Unsigned Int Indicator [Ci] 1-Byte Unsigned Int Control [1…32767] [Ci] 2-Byte Signed Int Indicator [Ci] 2-Byte Signed Int Control [1…65535] [Ci] 2-Byte Unsigned Int Indicator [Ci] 2-Byte Unsigned Int Control [1…10…100] [Ci] Percentage Indicator [Ci] Percentage Control [0.1…1… [Ci] 2-Byte Float Indicator …670433.28] [Ci] 2-Byte Float Control

Table 6. Numerical Control 2-Button

Units: permits specifying the measuring units of the displayed value. For percentage indicator, the symbol % always will be displayed as unit.

2.2.2.1.3.5 Enumeration

The box will behave analogously to the case of the switch, however the communication objects (control object “[Ci] Enumeration Control” and the status “[Ci] Enumeration Indicator”) will be 1-byte. Up to six discrete states can be distinguished depending on the value that the status object acquires from the control or receives from the bus.

Figure 81. 2-Buttons Control – Enumeration
Number of Values [1…2…6]: number of states that will be distinguished. For every distinguished state, the parameter Value [0…255] will become available together with the corresponding indicator.

https://www.zennio.com

Tecnical Support: https://support.zennio.com 93

Z50 / Z70 v2 / Z100
Indicator Type [Icon / Text]: allows selecting whether the status indicator which each value is represented will be text type or icon type. As many drop- down lists of icons or text boxes will be displayed as states have been enabled in the previous parameter.
2.2.2.1.3.6 Two Scene
Analogously to the 1-button scene control, 2-button scene controls allows sending the KNX bus a scene value, however in this case there will be two buttons in the box, each of which can be configured independently.

Figure 82 2-Button Control ­ Two Scenes
Top / Bottom Scene [1…64]: value of the scene that will be sent to the bus after pressing on the top and bottom button.
Action [Run / Run and Save]: sets whether the device will only send orders to execute specified scene (after a short press) or if will be possible to send orders to save the scene (after a long press).
Object to Use [General Scene Object / Individual Box Scene Object]: specifies whether the scene value will be sent through the object “[General] Scenes: Send” or through the individual object for each: “[Ci] Top Scene: Send” and/or “[Ci] Bottom Scene: Send”.

https://www.zennio.com

Tecnical Support: https://support.zennio.com 94

2.2.2.1.3.7 Shutter

Z50 / Z70 v2 / Z100

Shutter control permits sending move up and move down (“[Ci] Shutter – Move”) or stop (“[Ci] Shutter ­ Stop/Step”) to control a shutter actuator connected to the bus by pressing the buttons in the box. In addition, the box will contain an indicator that will permanently show, as a percentage, the value of the status object (“[Ci] Shutter Position”).

Figure 83 2-Buttons Control – Shutter
Type: set the desired behaviour for the buttons:
[Standard]: a long press will make the device send to the KNX bus an order to start moving the shutter (upwards or downwards, with the top or bottom button respectively), while a short press will make it send a stop order (or step up / step down).
[Hold & Release]: as soon as the button is held, the device will send the KNX bus an order to start moving the shutter (upwards or downwards, with the top or bottom button respectively). Once the button is released, it will send an order to stop the shutter.
Show Percentage indicator [disabled/enabled]: enables or disables the shutter position indicator (in percentage) in the box.
Additionally, the shutter control will have the percentage object “[Ci] Shutter Positioning (Only Schedulers and Macros)” which will be used by schedulers and macros for a precise regulation of the shutter.

https://www.zennio.com

Tecnical Support: https://support.zennio.com 95

2.2.2.1.3.8 Dimmer

Z50 / Z70 v2 / Z100

The light control function permits making use of the two buttons in the box to send orders to a light dimmer, either through a binary object or through a 4-bit object. Moreover, the box will permanently display the current value of the dimming status object (“[Ci] Light ­ Dimming Indicator”), which needs to be linked to the analogous object from the dimmer (as it does not get automatically updated on button presses).

Figure 84. 2-Buttons Control – Dimmer
The parameters available are:

Maximum Dimming Step on Long Press [100% / 50% / 25% / 12.5% / 6.25% / 3.1% / 1.5%]: sets the increase or decrease in the light level that will be requested, via object “[Ci] Light ­ Dimming”, from the dimmer with each long press on the top or bottom button respectively.

After a short press on the top button the value “1” will be sent through the “[Ci] Light – On/Off” binary object, while a short press on the bottom button will trigger the sending of the value “0”.

Show Percentage Indicator [disabled/enabled]: enables or disables the shutter status indicator in the box.

Note: most light dimmers implement light step dimming progressively (i.e., sending a dimmer a step order of 25% typically does not imply that the light level is suddenly incremented/decremented by 25%, but a progressive increment or decrement of the light level by 25% which is in fact interrupted if a stop order arrives (such order is sent by Z70 v2 when the user releases the button). Due to this behaviour, it is advised to parameterise dimming steps of 100%, so that the user can perform a complete dimming (from totally off to totally on, or vice versa) or a partial dimming by simply holding the button and then

https://www.zennio.com

Tecnical Support: https://support.zennio.com 96

Z50 / Z70 v2 / Z100
releasing it as soon as he gets the desired light level, therefore with no need of performing successive long presses for regulations greater than the parameterised step.
Additionally, the dimmer control will have the 1-byte object “[Ci] Precise Dimming (Only Schedulers and Macros)” which will be used by schedulers and macros for a precise lighting control.
2.2.2.1.3.9 Room State
Configuring with this function the box, controlling the states of the room will be possible, as well as show the associated pop-up. Thus, pressing on the top button will cause the room status to switch between normal and Make Up Room, while with the bottom button, the state will be switch between normal and Do Not Disturb.

Figure 85. 2-Buttons Control – Room State
Show Pop-Up When Activating Normal State [No / Pop-Up 1 / … / Pop-Up 6]: allows to select the pop-up to be displayed when normal mode is activated.
Show Pop-Up When Activating MUR [No / Pop-Up 1 / … / Pop-Up 6]: allows to select the pop-up to be displayed when Make Up Room mode is activated.
Show Pop-Up When Activating DND [No / Pop-Up 1 / … / Pop-Up 6]: allows to select the pop-up to be displayed when Do Not Disturb mode is activated.
Note: the pop-ups selected must be activated (see section 2.1.14.2).

https://www.zennio.com

Tecnical Support: https://support.zennio.com 97

Z50 / Z70 v2 / Z100
This control will have associated a dedicated object for the indicator (“[Ci] Room State Indicator”), which is automatically updated after the control order is sent and when values are received from the bus.
2.2.2.1.4 CLIMATE CONTROL
This category covers a set of functions related to the climate control. The available options for Function (and for the dependent parameters) are as follows:
2.2.2.1.4.1 Temperature Setpoint
This function permits controlling the temperature setpoint of an external thermostat by means of a two-button box and of the parameters enabled to that effect: “[Ci] (Climate) Setpoint Temperature Control” for the control and “[Ci] (Climate) Setpoint Temperature Indicator” for the status. It is also

References